7. WIRING CHART
CENTRAL CONTROL
MONITOR(CCM)
INDOOR UNIT
OUTDOOR UNIT
COMPUTER
INDOOR UNIT
INDOOR UNIT
Power
(
(
220-240V
~
50/60Hz
)
the shielded twisted-pair wire
The reserved function is indicated in broken line table,users
can select it when necessary.
1
Take out the faceplate,then dismantle the display cover
plate.(see
Fig.7-1)
faceplate
display cover plate
NOTE
Please refer to installation instructions for the refrigerant
piping conection of the air conditioner that with throttle
device inside.
Tightening Torque
Φ
6.4
Outer diameter(mm)
of connection piping
Φ
9.5
Tightening Torque
(N.m)
32.7~39.9
Φ
15.9
61.8~75.4
Φ
19.1
97.2~118.6
14.2~17.2
Table 6-2
Φ
12.7
49.5~60.3
7
installation manual
CAUTION
S faceplate
wiring cover plate
Fig.7-1
faceplate
the wire holder of power
cord(three-position))
the wire holder of signal
line (five-position))
display cover plate
dial switch
2 Individually connect the power cord and signal line,adjust the
dial switch.
(see
Fig.7-2)
S faceplate
Fig.7-2
the wire holder of power
cord(three-position))
the wire holder of signal
line (five-position))
wiring cover plate
dial switch
An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the nati-
onal rule.
CAUTION
Model(W)
1500~7100
15
5A
3x2.5
2x4.0+1x2.5
(Add eletrical auxiliary heat)
8A
(Add eletrical auxiliary heat)
Manual switch
(A)
Indoor unit power wiring (mm
2
)
Indoor/outdoor connectingwiring
(mm
2
) (Electric signal)
Power
Phase
Fuse (A)
1-Phase
220-240V~ 50/60Hz
Frequency and volt
3x0.75(3x0.75)