Menu Level 1
Menu Level 2
Menu Level 3
Explanation
Functions
External DI
External DI
Active Wireless:
DI1/..DI20
Assign to:
—/DI-5/DI7
External DI menu only
available if one or several
“Input modules” are bound to
the system. Active wireless
DI1-20 is depended on actual
node for “Input module”.
Node shown in “Wireless”
menu which node
representing DI module
inputs.
Eg.
Node 1 type: DI. Active
wireless DI1 and DI2
Node 2 type: DI. Active
wireless DI3 and DI4
Node 10 type: DI. Active
wireless DI19 and DI20
Active wireless DI1-20 are
available to assign to DI1-5
and DI7 for the system in the
air handling unit.
DI6 is not available as
selection, used by the system
in the air handling unit.
Unsigned DI is shown as –
(none).
To reset a previously
assigned DI, select “–”
and confirm the selection.
Functions
Wireless
External DI
Note:
1 Type:
None
State:
No Network
Data:
0
Wireless system status.
Node: Shows number of
bound wireless module.
Type: None/UI: User
Interface (Control panel)/DI:
Digital Input module/CO2:
CO2 sensor module/RH: RH
sensor module.
State: No Network: No
gateway connected to the
system for air handling
unit/Unbound: No bonded
module/OK: Successful
binding of module
Data: The actual value
from module/Comm fail:
Communication failure, se
manual for actual module for
troubleshooting.
To reset all bound nodes,
see user manual for Gateway
Wireless.
SAVE VTR 200/B
Installation and Service
208061
31
Systemair Sverige AB