Menu Level 1
Menu Level 2
Menu Level 3
Explanation
Functions
Analog output
Analog output
A01 auto/man/off
A02 auto/man/off
A03 auto/man/off
Shows
current analogue
outputs in 0–10 V to hot/cold
water actuator or electrical
re-heater and rotor drive /
bypass damper.
Set
AO1(Analogue output
to hot water actuator or
electrical re-heater) to auto,
man or off.
Default value: auto.
Set
AO2 (Analogue output to
cold water actuator) to auto,
man or off.
Default value: auto.
Set
AO3 (Analogue output to
rotor drive or bypass damper)
to auto or man. Default is
auto. Selecting man enables
the user to manually control
the actuator/damper with a
0–10 V signal. 0 V completely
closed and 10 V completely
opened actuator/bypass
damper.
Functions
Digital input
Digital input
DI1 ON/OFF
DI2 ON/OFF
DI3 ON/OFF
DI4 ON/OFF
DI5 ON/OFF
DI6 ON/OFF
DI7 ON/OFF
Shows
current status of the
digital inputs ON or OFF
DI1: Fan configuration
DI2: Fan configuration
DI3: Fan configuration
DI4: Heater deactivated
DI5: Extended/forced running
DI6 for rotating heat
exchanger:
Rotor sensor
DI6 for counter flow heat
exchanger:
Bypass damper limit switch
DI7: Home/leave
SAVE VTR 200/B
Installation and Service
208061
27
Systemair Sverige AB