9.3 Manual and automatic summer mode
Manual summer mode occurs if no temperature step is selected. The temperature symbol on the main
menu is then completely empty.
If the electrical re-heater is activated, it will switch off during manual summer mode. Manual summer
mode goes automatically to step 1 (setpoint 12 °C) after two minutes if the supply air temperature is
+5 °C or below.
If a water heater battery is installed and activated, the manual summer mode goes automatically to step 1
(setpoint 12 °C) if the outdoor air or supply air temperature is +5 °C or below.
The unit will automatically alternate between winter operation with heat recovery and summer operation
without heat recovery.
9.4 Cool recovery
If the outdoor air is warmer than the extract air and the supply air is above the setpoint, cool recovery
occurs. This condition blocks the heat regulation process.
9.5 Service menu overview
Enter the service menu by selecting the service symbol in the display.
Menu Level 1
Menu Level 2
Menu Level 3
Explanation
Service
Password
Password
Password XXXX
Locked YES/NO
Enter the service level
by typing 1111. Use the
SELECTION knob for each
digit and confirm with the
ENTER button after each
set digit.
NO
will unlock the
system and allow parameter
changes.
Service
Change
Password
Change password
Actual
XXXX
New
XXXX
Confirm XXXX
Set
new password if
necessary.
In case the new password
would be forgotten or
misplaced, it’s still possible
to enter the service level by
writing 8642. This overrides
the earlier set password.
Service
Filter period
Filter period
Time to replace:
12month
Reset NO/YES
Shows
selected time interval
between filter change.
Set
Reset of the filter period
to YES after completed filter
change.
Set
time between filter
changes.
SAVE VTR 200/B
Installation and Service
208061
21
Systemair Sverige AB