![SystemAir SAVE VTR 200/B Installation And Service Download Page 25](http://html1.mh-extra.com/html/systemair/save-vtr-200-b/save-vtr-200-b_installation-and-service_1423139025.webp)
Menu Level 1
Menu Level 2
Menu Level 3
Explanation
Week program
Airflow
Airflow
On level:
low/nom/high/auto
Off level:
off/low/nom/high
Use this dialogue frame to
determine the ON and OFF
function for the fans in the
week schedule.
Set
ON level.
Choose between Low, Nom,
High or Auto.
Default value: Nom
Set
OFF level.
Choose between OFF, Low,
Nom or High.
Default value: Low.
Service
Airflow log
Airflow log
Level:
1–5
Reset:
NO/YES
SF: 140
/140
EF: 140
/140
Use this dialogue frame
to see how the fans have
operated during the time (h)
they have been active.
The airflow are shown in 5
different levels:
• Level 1: 0%
• Level 2: 1 – 29%
• Level 3: 30 – 44%
• Level 4: 45 – 59%
• Level 5: 60 – 100%
Choose between the levels
to see the time in hours the
fans have been active in the
different levels.
Reset Yes resets the SF and
EF time in the left column for
all levels. The right column
continues to count ahead and
can not be reset.
Note:
Factory reset (see
Functions –>Factory
reset
) will not affect this
function
SAVE VTR 200/B
Installation and Service
208061
23
Systemair Sverige AB