Menu Level 1
Menu Level 2
Menu Level 3
Explanation
Functions
DI 4–7
DI 4–7
4 Stop heat
5 Ext run
6 Rotor
7 Home/Leave
DI 4–7 are default set
from factory and can’t
be changed by the
user. Below follows a
short description of each
function.
DI4: Makes it possible to
turn the electrical re-heater
battery on or off. Activated
input means that the
electrical re-heater is
blocked.
DI5: Activate the
Extended/forced running
function. The function
overrides current set fan
speed settings and runs in
forced mode according to
the settings in
Service->
Ext/Force run
. Choose
between Low, Nom and
High for this function..
The input is calculated
based on the signals from
an impulse-switch. If a
standard switch is used,
the countdown of the set
time starts when the switch
is switched off.
DI6: Rotor sensor.
DI7: Switching on this
input decreases the supply
air temp set point with
10°C.
This function is used when
the building is uninhabited
for a longer period.
It is recommended to
connect DI7 and DI1 or
DI3 in parallel. If DI7 is
activated, set the fans
speed to min. Fan speed
settings are done when
configuring DI1/DI3.
Note:
The “Home/Leave”
function is not working if
Water heater is activated.
SAVE VSR 300/500
Installation and Service
208115
32