13
Scheme of connecting servo drive
Belimo BE 24-12ST
Technical data
BE 24-ST, BE24-12-ST
Nominal voltage
AC24V 50/60 Hz DC 24V
Nominal voltage range
AC19.2 ... 28.8 V
For wire sizing
18 VA (lmax. 8.2A @ 5 ms)
Power consumption
- motoring
12W
- holding
0,5W
Connection cable
- motor
lead 1 m, 3 x 0.75 mm
2
(halogen-free), with 3-pole plug connectors
- auxiliary switch
lead 1 m, 6 x 0.75 mm
2
(halogen-free), with 6-pole plug connectors
Auxiliary switch
2 x EPU
K
Contact rating (contacts gold plate on silver)
1 mA ... 6 A, DC 5 V ...AC 250 V
Switching points
3° / 87° (referred to 0 ... 90°)
Tolerance
±2
o
Angle of rotation
100° (incl. 5° mechanical overrun on each side)
Torque (nominal torque)
40 Nm
Blocking torque
-dynamic
40 Nm
- steady-state
50 Nm
Direction of rotation
Selected by mounting L/R
Damper stem
form-fit 14x14mm, form-fit 12x12mm
Running time
<60 s for 90°
Sound power level
Max. 62 dB (A)
Position indication
Mechanical with pointer
Service life
At least 10‘000 cycles
Protection class
III Safety extra-low voltage
Degree of protection
IP54
Ambient temperature range
-normal duty
–30 ... +50°C
-safety duty
see text/ graph crash case
Non-operating temperature
–40 ... +80°C
Ambient humidity range
CE according to89/ 336/EWG, 92/31/EWG, 93/68/EWG
Mode of operation
type 1.C (EN 607 30)
EMV low-voltage directive
CE according to 89/ 336/EWG, 92/31/EWG, 93/68/EWG
Maintenance
maintenance- free
Weight
appr. 2,7 kg
Summary of Contents for PKI-C EI120S
Page 1: ...www systemair com Systemair Fire damper...
Page 21: ...Declaration of conformity...
Page 37: ...PVM Fire air grilles www systemair com Systemair Fire damper...
Page 45: ...DKI Smoke dampers www systemair com Systemair Fire damper...
Page 53: ...10 Scheme of principle of BKSE 24 6 example...