SystemAir PKI-C EI120S Manual Download Page 38

2

General

PVM Partition Fire Dampers are used as a fire shut- off
element, which connects two two adjacent fire areas
without connecting duct.
Fire Air Grille is tightly installed into the dividing fire
construction. In case of fire, blades of the grille close
the openings and stop the fire from spreading to other
fire area.

Grilles IMOS- PVM Partition Fire Dampers are manu-
factured from fire resistant material (D1) based on STN
73 0852, tested according to STN EN 1634-1:2001 and
classified according to STN EN 13501-2:2005 as 
EI

1

90, El

2

120, E120 and EW60 and manufactured with

servomotor El

1

60, El

2

120, E120 and EW60.

Construction Features

1.

Frame

2.

Dividing insulating blades         

3.

Closing mechanism with spring

4a. Fusible link 

4b. Actuator driven with thermal link cut-off switch
5.

Protecting grille

6.

Protecting box of mechanism

7.

Active fire sealing

Figure 1- PVM 

Figure 2- Grille PVM with Actuator

Material Final Manufacture

The frame1 of the grille is made of zinc-plated con-
struction steel. Blades 2 which rotation axis is horizon-
tal are placed in the frame. Dividing insulating blades
are made of calcium silicate sheets. Blades are closing
contradictory with help of closing mechanism 3(shifter
and spring) or servo drive and spring 3+4b. Blades are
maintained in open position by fusible link until the air
temperature reaches above 72

o

C.

When PVM units are Actuator driven, blades are main-
tained in open position with the motor itself.The
damper mechanism is driven to closed position by the

actuator  when the air temperature exceeds 72

o

C.

Protection grille 5 prevents the contact with surface of
the blades that have higher temperature when fire.At
the same time, protecting grille forms air space be-
tween the blades and the grille where the air flows and
cools down the surface of blades. Protection grilles are
delivered painted as standard with  powder RAL 9007
Protecting box 6 stops the heat to get through closing
mechanism. Intumescent self expanding seals 7 fill the
spaces between the frame and blades and between the
blades themselves by changing their volume, which is
caused by the heat.

The present technical specifications define sizes, properties, scope of utility and manufacture of fire partition
dampers.The specifications apply to the design, ordering, production, acceptance and use of these products from
June 1st, 2006.

Summary of Contents for PKI-C EI120S

Page 1: ...www systemair com Systemair Fire damper...

Page 2: ...maintains the damper blade in open position by maintaining the current through its mechanism Upon shut off electrical current the Electromagnet automatically releases the damper blade mechanism and th...

Page 3: ...chanism 24V Release on cut off of electricity plus 24V End and Begin switches indicating damper Closed and Open position DV6 Electromagnetic release mechanism 24V Release on cut off of electricity plu...

Page 4: ...manufactures DV3 DV6 5 terminal switch for manufactures DV1 2 5 6 two terminal switch for manufactures DV1 2 2 2 5 2 6 2 6 inspection control lid 7 actuator for manufactures DV7 DV9 T and DV9 T ST th...

Page 5: ...C with tolerance 1 5 C for the period of 30 to 60 seconds Electromagnet maintains the damper blade in open position by maintaining the current through its mechanism Upon shut off electrical current t...

Page 6: ...ed and Open position DV6 Electromagnetic release mechanism 24V Release on cut off of electricity plus 230V End switch indicating damper Closed position DV6 2 Electromagnetic release mechanism 24V Rele...

Page 7: ...46 7 49 4 52 2 550 15 9 18 1 19 3 20 6 22 1 23 6 25 4 27 5 29 8 32 5 35 5 38 4 42 0 45 8 50 3 53 2 56 2 600 17 2 19 6 20 9 22 3 23 9 25 5 27 5 29 7 32 3 35 2 38 4 41 6 45 5 49 6 54 5 57 7 60 9 700 18...

Page 8: ...damper flanges Further more the damper should not bare any weight from the above or surrounding construction of the wall this can result in distortion of the casing and ultimately malfunction of the f...

Page 9: ...m the above or surrounding construction of the wall this can result in distortion of the casing and ultimately malfunction of the fire damper Limit of damper embedding into the wall or the ceiling is...

Page 10: ...g diameter of d 60 mm is required for each size of fire damper for it to be properly imbedded into wall cross section Outer diameter of cover plates for closure are normally d X as standard see fig 12...

Page 11: ...fered to d are stated in the tables Pressure loss for exact damper is stated by calculation according to the scheme pz vL 2 2 pz pressure loss resistance coefficient vL 2 flow velocity in cross sectio...

Page 12: ...damper to the wall opening The entire opening between the fire damper and the wall in the full depth of the wall around the fire damper must be filled perfectly with Rockwool of Density 80 100 kg m3...

Page 13: ...500 1 02 0 89 0 83 0 78 0 72 0 68 560 0 85 0 8 0 76 0 7 0 66 0 61 630 0 82 0 77 0 73 0 67 0 64 0 6 0 54 710 0 73 0 7 0 65 0 62 0 58 0 53 0 49 800 0 66 0 61 0 59 0 56 0 51 0 47 0 44 900 0 56 0 57 0 54...

Page 14: ...o connect these devices to el power according to the wiring schemes Damper mechanical function check After putting the damper into operation leaf opening it is necessary to check damper function By pu...

Page 15: ...ring part must easily fit into securing mechanism 8 9 2 1 Fig 36b Putting the damper with mechanical regulation into operation Wiring the electrical accessories If a damper is equipped with electromag...

Page 16: ...ithin app 20 30 seconds depends on operation temperature Position of the leaf is possible to check visually through inspection lid or the leaf position is signaled by control system which the damper i...

Page 17: ...n OPEN to position CLOSED Closing the damper is provided by spring 10 Securing pivot 2 fits into holder 5 and by that is the damper leaf secured against opening After actuating the damper immediately...

Page 18: ...replacement Replacement of Fusible link valid only for PK I R to diameter 200 mm including Heat fuse is located inside the damper casing From the design point of view it is a part of the panel with re...

Page 19: ...holding the switch situated on thermo electrical release device heat fuse as shown in fig 37 Doing this simulate failure of heat fuse It is necessary to hold the switch in ON mode during the whole da...

Page 20: ...Putting the Fire damper into operation Date of putting into operation Text found faults and defects Signature and date of control ling technician Special controls Date of control Text found faults and...

Page 21: ...Declaration of conformity...

Page 22: ...dictable production defects occur on the product the producer shall secure their free of charge removal during the warranty period 3 The customer may apply for the warranty service only in written for...

Page 23: ...2 Electromagnet Connector KSZ 31B for cable 6 8 Electromagnet spool EVJ1142 Electromagnet EVJ1142 Fig 13 Wiring scheme of electromagnet Electromagnet Electromagnet is used to release the damper to clo...

Page 24: ...Fig 10 Fig 11 Installation in partition concrete wall Fire damper valves are suitable to be installed into concrete partition walls directly onto the rigid ventilation duct Fire damper valves are test...

Page 25: ...0mm BFD fire dampers are manufactured from Galvanized mild steel casing and silicate butterfly damper blades Ordering codes 60S 90S 120S Dimension Fire resistance class BFD EI ITFG Intumescent transfe...

Page 26: ...th fire resistance barrier for 60 and 120minutes Constructed with intumescent strips housed in plastic all blades are set horizontal and vertically to assure lowest pressure loss for air transfer IFG...

Page 27: ...er leaf is in operation position open After disconnecting the el feeding or breaking the heat fuse the damper leaf closes with energy of return spring accident position Thermoelectrical release device...

Page 28: ...t means that the damper leaf is in operation position open After disconnecting the el feeding or breaking the heat fuse the damper leaf closes with energy of return spring accident position Thermoelec...

Page 29: ...Connecting cable Auxiliary switch BLF24 T 1 m 6 x 0 75 mm 2 halogen free BLF24 T ST 1 m 6 x 0 75 mm 2 halogen free with plug connectors suitable for BKN230 24 Angle of rotation Max 95 incl 5 spring p...

Page 30: ...switch 1 m 6 x 0 75 mm 2 halogen free Angle of rotation Max 95 incl 5 spring pre tensioning Damper rotation Form fit 12 mm 10 mm with adapter supplied Torque motor Min 6 Nm spring return Min 4 Nm Run...

Page 31: ...nectors suitable for BKN230 24 auxiliary switch BF24 T 1 m 6 x 0 75 mm 2 halogen free BF24 T ST 1 m 6 x 0 75 mm 2 halogen free with plug connectors suitable for BKN230 24 Angle of rotation Max 95 incl...

Page 32: ...switch 1 m 6 x 0 75 mm 2 halogen free Angle of rotation Max 95 incl 5 spring pre tensioning Damper rotation Form fit 12 mm 10 mm with adapter supplied Torque motor Min 18 Nm spring return Min 12 Nm Ru...

Page 33: ...230 V 2 plug in contacts for Belimo actuator 24 V 3 screw terminals 7 poles 4 cable inputs for Belimo actuator 5 cable input for 2 wire conductor 6 transparent protection cover 7 LED indication green...

Page 34: ...advantage of this system is the possibility to connect unit BKS24 1B ZSO 11 into higher central systems of building control and control of damper position could be then remote controlled without the...

Page 35: ...The advantage of this system is the possibility to connect unit BKS24 9A into higher central systems of building control and control of damper position could be then remote controlled without the nee...

Page 36: ...Systemair AB SE 739 30 Skinnskatteberg Sweden Tel 46 222 440 00 Fax 46 222 440 99 mailbox systemair se www systemair com...

Page 37: ...PVM Fire air grilles www systemair com Systemair Fire damper...

Page 38: ...sulating blades are made of calcium silicate sheets Blades are closing contradictory with help of closing mechanism 3 shifter and spring or servo drive and spring 3 4b Blades are maintained in open po...

Page 39: ...200 x 220 6 6 x 0 020 500 x 220 11 2 x 0 062 320 9 2 10 1 0 028 320 15 5 16 5 0 088 420 11 8 13 0 0 036 420 19 9 21 2 0 114 520 14 4 15 8 0 045 520 24 3 26 0 0 149 620 17 0 18 7 0 053 620 28 6 30 6 0...

Page 40: ...slot between the fire rated partition wall and cover of the grille After installation the grille is tested to prevent prob lems with opening and closing of the blades By ZV DV1 and DV2 is the protecti...

Page 41: ...ction with variable thickness Figure 5 Dismounting of the terminal block from IMOS PVM with actuator Scheme 1 Limit switch XCKN2118G11 manufacture DV1 and DV2 Technical parameters XCKN2118G11 pover vo...

Page 42: ...e plug BLF24 T ST with connector plugs suitable for BKN230 24 Operating angle 95o incl 5o pre tension of spring Dumper shaft formed end 12 mm with att adapter 8 10 mm Torisonal moment motor min 4 Nm d...

Page 43: ...d with the use of ordinary means of transport and the cost is also to be borne by the customer The grilles must be pro tected against damage and weather conditions Storage It is recommended that the g...

Page 44: ...Systemair AB SE 739 30 Skinnskatteberg Sweden Tel 46 222 440 00 Fax 46 222 440 99 mailbox systemair se www systemair com Systemair Condesign Info Productions January 2008 Art no E XXXX...

Page 45: ...DKI Smoke dampers www systemair com Systemair Fire damper...

Page 46: ...Leaf detail These specifications define the size properties and application range and construction features of DKI smoke dampers The specifications apply to designing ordering manufacturing acceptanc...

Page 47: ...y servo drive which is based on electrical impulse from smoke box or remote con trolled with help of electric fire signalization central Based on such a signal the damper leaf opens or closes accordin...

Page 48: ...20 5 500 17 0 18 5 19 4 20 4 21 6 22 7 600 20 6 21 7 22 9 24 3 25 7 27 3 29 2 700 23 1 24 5 26 0 27 5 29 3 32 5 800 26 2 27 8 29 5 33 0 36 4 39 4 900 29 9 31 7 35 2 39 4 42 7 1000 34 0 37 9 42 4 46 0...

Page 49: ...54 0 50 700 0 73 0 70 0 65 0 62 0 53 0 49 800 0 66 0 61 0 59 0 51 0 47 0 44 900 0 56 0 57 0 49 0 45 0 42 1000 0 54 0 47 0 43 0 40 1100 0 53 0 45 0 42 0 38 1200 0 43 0 41 0 36 1300 0 4 0 41 0 35 1400 0...

Page 50: ...tal damper fitting on the duct EN 1366 9 Fig 4 Horizontal damper fitting in the duct EN 1366 9 Fig 5Vertical damper fitting on the duct EN 1366 9 Fig 6Vertical damper fitting in the duct EN 1366 9 Dam...

Page 51: ...central unit BELIMO BKSE 24 6 to one central unit it is possible to connect minimum one and maximum 6 smoke dampers Scheme of connecting smoke damper with servo drive for 230V to electro installation...

Page 52: ...min 1 s input impedance R terminals10 11 66 kohm R terminals10 12 66 kohm Input 2 Priority 2 terminals 8 9 isolated from input 1 input level DC U high DC 18 30V U low DC 12V input current DC I 5 0 5 m...

Page 53: ...10 Scheme of principle of BKSE 24 6 example...

Page 54: ...th actuator Power consumption 10 W with actuator Connections mains lead 1 m halogen free without plug actuator 6 pin plug 3 pin plug 2 wire connector screw terminals for wire 2 x 1 5 mm Recommended ca...

Page 55: ...e Torque nominal torque 40 Nm Blocking torque dynamic 40 Nm steady state 50 Nm Direction of rotation Selected by mounting L R Damper stem form fit 14x14mm form fit 12x12 mm Running time 60s for 90o So...

Page 56: ...ion 100 incl 5 mechanical overrun on each side Torque nominal torque 40 Nm Blocking torque dynamic 40 Nm steady state 50 Nm Direction of rotation Selected by mounting L R Damper stem form fit 14x14mm...

Page 57: ...R Angle of rotation Max 105 incl 5 mechanical overrun on each side Running time 30 s for 90 Sound power level Max 60 dB A Damper stem 12mm Position indication Mechanical with pointer Service life At...

Page 58: ...N EN 1366 1 Servo drive can be opened and repaired only by the producer Servo drive contains electronic and electric components Regulation Open Close AC 250V 2 wire open close control The actuator is...

Page 59: ...que steady state 30 Nm Torque nominal torque min 15 Nm nominal voltage Direction of rotation Selected by mounting L R Angle of rotation Max 105 incl mechanical overrun on each side Running time 30 s f...

Page 60: ...pers DKI 1 Mounting operation maintenance Mounting operation and maintenance of dampers is subject to specific Operation guidelines published by the manufacturer and is attached to every product when...

Page 61: ...ldings Common statements STN CR 12792 12 0001 Ventilation of buildings Symbols and terminology STN EN 1505 Ventilation of buildings Metal sheet pipes and shaped pieces of square cross section Dimensio...

Page 62: ......

Page 63: ...Systemair AB SE 739 30 Skinnskatteberg Sweden Tel 46 222 440 00 Fax 46 222 440 99 mailbox systemair se www systemair com Systemair Inhouse studio January 2006 Art no E8003...

Reviews: