Circular Fire Dampers
Fire Dampers
Actuator driven Fire Dampers:
DV7
; Spring return actuator driven fire damper (230V) complete
with Thermal release mechanism and Auxiliary Switches
DV9-T
; Spring return actuator driven fire damper (24V)
complete with Thermal release mechanism and Auxiliary
Switches
DV9-T-ST
; Spring return actuator driven fire damper (24V)
complete with Thermal release mechanism, Auxiliary Switches
and Belimo BKN230-24 communication unit
Electrical accessories
BKS1
- Communication and control unit BKS24-1B with plug
socket ZSO-11 for one remotely controlled fire damper (for DV9-
T-ST only)
BKS9
- Communication and control unit BKS24-9A for up
to nine remotely controlled fire dampers (for DV9-T-ST only)
Circular fire damper with actuator
L
Ø d + 110
Ø d / 2 + 90
45
45
Ø D
7
8
6
2
1
6
8
7
L1
L2
Damper parts description:
1. Damper blade
2. casing
3.
release mechanism (for manufactures ZV
and DV1-DV6)
4. electromagnet (for manufactures DV3-DV6)
5. terminal switch (for manufactures DV1,2,5,6) /
two terminal switch (for manufactures DV1-2, 2-2,
5-2, 6-2)
6. inspection (control) lid
7. actuator (for manufactures DV7, DV9-T and DV9-
T-ST)
thermo-electrical release device (for manufactures
DV7, DV9-T and DV9-T-ST)
Main dimensions:
Diameter
Ø d [mm]
Length
L [mm]
Damper Blade
extension
L1 [mm]
Damper Blade
extension
L2 [mm]
Weight
Q [kg]
100
-
-
4
125
-
-
4
160
-
-
5
180
-
-
5
200
400
-
-
6
225
-
-
7
250
-
-
7
280
-
-
8
315
-
-
9
355
-
5
11
400
450
-
28
13
450
-
53
16
500
-
78
19
560
-
108
22
630
-
143
25
710
23
183
29
800
68
228
35
900
118
278
41
1000
500
168
328
48
Tab. 1a Round dampers with actuator
L1 – Extension of damper blade outside of the casing in full open position
L2 – Extension of damper blade outside of the casing in full open position
Ordering codes:
-
-
-
-
Dimension
D
Manual reset lever
ZV
Switches & Actuators
DV1 to DV9-T-ST
Standard
0
Rubber gaskets
NT
Mounting flanges
P
BKS1
BKS9
PR
Control
Accessories
Installation accessories
Connection
types
Communication & Control Units
60S, 90S and 120S
PK-I -R-EI
Fire resistance class
Operation type
NOTE:
E = Casing integrity, I = Insulation class, S = Smoke leakage
Summary of Contents for PKI-C EI120S
Page 1: ...www systemair com Systemair Fire damper...
Page 21: ...Declaration of conformity...
Page 37: ...PVM Fire air grilles www systemair com Systemair Fire damper...
Page 45: ...DKI Smoke dampers www systemair com Systemair Fire damper...
Page 53: ...10 Scheme of principle of BKSE 24 6 example...
Page 62: ......