Shut-Off fire dampers and Intumescent Grills
BFD:
BFD fire damper shutter valves are designed to be used for
small ventilation applications. Ideal for small to multi
residential buildings to protect the habitants of fire and Smoke
risks.
BFD fire dampers are tested and are conform to EN 1366-2 to
suit installations of 60, 90 and 120minuts.
Fire dampers are equipped with fusible link set to release at
temperatures above 72
C.
BFD fire dampers are easily placed in circular ducts, whilst
the special designed rubber gasket will maintain the unit in
place and keep smoke integrity as designed.
Available in 4 dimensions, sizes
100, 125, 160 and 200mm.
BFD fire dampers are manufactured from Galvanized mild
steel casing and silicate butterfly damper blades
Ordering codes:
-
-
60S, 90S, 120S
Dimension
Fire resistance class
BFD-EI
ITFG:
Intumescent transfer fire grills are designed to be non-
vision fire grills for the door or wall application.
Constructed from Plastic profiles filled with intumescent
strips, are easy to install in rigid walls or doors.
ITFG can be supplied with a mounting frame to suite a
doors and walls.
Mounting frame provides a fixed (code FF)or variable
installation depth (code AF)
ITFG are tested in accordance to, EN 1364-1, 1364-2
and EN-1634-1
Available sizes are from 100x100mm to 800x400mm
ITFG is tested and classified as EI30, EI60 and EI90(v
e
)
Ordering codes:
-
-
-
30, 60 and 90
L (100-800mm)
Dimension
H (100-400mm)
FF
AF
Accessories (counter frame)
Fire resistance class
ITFG-EI
Summary of Contents for PKI-C EI120S
Page 1: ...www systemair com Systemair Fire damper...
Page 21: ...Declaration of conformity...
Page 37: ...PVM Fire air grilles www systemair com Systemair Fire damper...
Page 45: ...DKI Smoke dampers www systemair com Systemair Fire damper...
Page 53: ...10 Scheme of principle of BKSE 24 6 example...
Page 62: ......