![SystemAir MAXK Series Installation And Operating Instructions Manual Download Page 9](http://html1.mh-extra.com/html/systemair/maxk-series/maxk-series_installation-and-operating-instructions-manual_1423289009.webp)
5
Total weight
without heating
battery
kg
880
1000
1200
1390
1620
1840
Total weight with
heating battery
kg
956
1093
1330
1521
1792
2031
* with built in filters (outdoor air F7 and extract air M6).
Additional installed units such as, for example, heating battery reduce the available external pressure
4.5
Acoustics
MAXK-I3 DC
Sound level*
Casing
Supply air
Extract air
Outdoor air
Exhaust air
2000 DC
dB(A)
63,7
79,2
60,3
58,6
78,4
3000 DC
dB(A)
64,8
75,2
68,6
68,6
75,2
4000 DC
dB(A)
65,8
80,4
73,3
73,3
80,4
5000 DC
dB(A)
66,7
82,3
76,3
76,3
82,3
6000 DC
dB(A)
67,9
80,7
74,3
74,3
80,7
7000 DC
dB(A)
63,6
78,3
63,6
61,8
79,6
* Operation at the upper limit.
5
Transport and storage
5.1
General
MAXK-I3 DC air handling units are delivered in transport
units. The width of the lorry (inside width approx. 2,34 m
) resp. loading level (inside width approx. 2,55 m – width
for a jumbo approx. 2,9 up to 3,05 m ) determine the
quantity of the single parts.
Note:
The quantiy of the single parts is shown in the
detailed drawing.
Important
• The shaft of the ventilator must always be arranged horizontally during the transport
• Units for outdoor installation with weather roof: weights without snow load!
Warning
• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use
protective clothing.
• The unit must not be put into operation before the enclosed parts are removed and installed properly.
|