10
6.6
Mounting indications for wet parts
Cooler parts have to be mounted and filled very
thoroughly
Detail A: tub protruding at the bottom
Detail B: tub flush at the bottom
7
Internal components
7.1
V-cell-filter
Due to its large filter surface has a high air throughput.
The pollution must be controlled with a differential
pressure device (U-tube, inclined tube). Filter cells have to
be renewed completely after the maximum difference
pressure has been reached. Check the standard frame as
to the correct fitting resp. check the sealing when
exchanging the filter. Torn filters and filters with low
qualitiy pollute built-in parts which are connected in
series. The bottom of the filter units must be cleaned
monthly (wipe – cleaning)
• Extract air filter = M6
• Supply air filter= F7
|