SystemAir MAXK Series Installation And Operating Instructions Manual Download Page 13

Installation |

9

Important

Through jolting during the transportation bore chips can loosen from the bolting connections and fall on the
ground. Please vacuum these chippings immediately from the housing parts since rust spots can ensue.

6.5

Mounting indications for the kind of delivery: „dismantled assembly group“

• Kind of delivery: delivery of devices partially screwed resp. completely

dismantled

Before plugging on the
device profiles, the stops
of the plug-in corners
have to be sprayed off
with a permanently
elastical mass.

Duo-Taptite screws 8 x 16
cross recess Z

6.5.1

Unit profile

• door and ceiling parts are regularly designed as complete units, if the opening to bring in the parts, permits this.

|

Summary of Contents for MAXK Series

Page 1: ...Document in original language MAXK Installation and Operating Instructions GB...

Page 2: ...air AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agree...

Page 3: ...indications for the kind of delivery dismantled assembly group 9 6 5 1 Unit profile 9 6 6 Mounting indications for wet parts 10 7 Internal components 10 7 1 V cell filter 10 7 2 Air heater air cooler...

Page 4: ......

Page 5: ...Declaration of Incorporation 1 1 Declaration of Incorporation...

Page 6: ...Carry out this action 1 Carry out this action if applicable further actions 2 Carry out this action 3 if applicable further actions 2 2 Notes on the documentation Warning Hazard as a result of improp...

Page 7: ...system Take care not to damage the water battery when connecting water pipes to connectors Use a spanner to tighten the connection 4 Product information 4 1 General This installation manual concerns a...

Page 8: ...for application in residential construction At an external pressure of Pa 190 Also suitable for application in residential construction Effective heat recovery rate 84 84 84 84 84 87 Electric power co...

Page 9: ...B A 63 6 78 3 63 6 61 8 79 6 Operation at the upper limit 5 Transport and storage 5 1 General MAXK I3 DC air handling units are delivered in transport units The width of the lorry inside width approx...

Page 10: ...Use only forks which extend to the whole width of the single parts Note lenght of fork width of equipment approx 100 mm Too short forks cause damages at the range of the floor covering 5 4 Big units S...

Page 11: ...rning The devices have to be adjusted to vibration elements Mafund Asozell Silomer a s o to avoid a transmission of structure borne noise and to guarantee the ventilation of the device base floor The...

Page 12: ...guaranteed Thus the function of the devices is guaran teed and leakages at doors or device connections are prevented Step 1 Check the mounting surfaces as to their planeness Unplane mounting surfaces...

Page 13: ...ndications for the kind of delivery dismantled assembly group Kind of delivery delivery of devices partially screwed resp completely dismantled Before plugging on the device profiles the stops of the...

Page 14: ...pollution must be controlled with a differential pressure device U tube inclined tube Filter cells have to be renewed completely after the maximum difference pressure has been reached Check the stand...

Page 15: ...the piping General rule for Cu Alu register The water forerun has to be connected on that collector which is situated very close to the air outlet Attention In case of mounting the connection must be...

Page 16: ...s a minimum of wear On heaters with higher ratings part of the output are controlled by a step controller However fine adjustment of the temperature is always carried out by the electronic ON OFF cont...

Page 17: ...ors at pressure side release chains only after standstill of the ventilators 7 8 Silencer To avoid fan noise being transferred via the duct system silencers should be installed both on supply and extr...

Page 18: ...ents and rubber sleeves are automatically delivered parts 1 to 5 The syphon may not be connected directly with a drain conduction but it must be guaranteed that it can run out freely Before putting in...

Page 19: ...wing of the tub is preprogrammed 8 1 Syphon for cooler Pressure operation Note For tubs which have to be connected within the overpressure range hand made syphons must be installed These must have a r...

Page 20: ...e weather protection roof cannot be bought immediately the top of the unit must be covered watertight The outside joints of outdoor units have to be permanently elastic sealed While assembly work the...

Page 21: ...t roof frame insulated extra charge detail drip ledge Mounting of the drip ledge install set up bolt the device screw the drip ledge with a drilling screw 4 8 x 19 at the device brace Mount pre fabric...

Page 22: ...east 150 mm Caution If the unit is installed in a cold place make sure that all joints are covered with insulation and tape well Duct connections duct ends should be covered during storage and install...

Page 23: ...amage is caused due to your failure to observe these instructions the guarantee is invalidated 11 3 Maintenance instructions Performance Component Activity Periodic If required Number per year 1 Fan 1...

Page 24: ...e filter and document the filter change x 8 Weather protection guard 8 1 Examine for dirt mounting damage and corrosion x 1 8 2 Function sustenance cleaning x 9 Damper 9 1 Examine for dirt damage and...

Page 25: ...om the power supply and contact the manufacturer Fan running roughly unsteady Imbalance of the impeller Rebalancing by spcialized company Wrong direction of rotation of the impeller Consultation with...

Page 26: ...defect Contact the manufacturer Air handling unit does not cool or cools insufficiently Air in the water cooling battery Venting To high temperature of the cooling coil Control the temperature of the...

Page 27: ......

Page 28: ...MAXK Installation and Operating Instructions en_GB 2017 06 13 Systemair GmbH Seeh fer Str 45 97944 Boxberg Germany Tel 49 0 7930 9272 0 Fax 49 0 7930 9273 92 info systemair de www systemair de...

Reviews: