SystemAir MAXK Series Installation And Operating Instructions Manual Download Page 11

Installation |

7

6

Installation

6.1

Installation site

Floors, foundations, ceilings or steel construction must be checked as to the planeness. Unplaneness causes a more dif-
ficult mounting and the canting of the doors. The consequences among other things are doors which can heavily be
opened and which are untight.

Additional stripy foundations resp. cross slides are necessary as from a device width of 2,4 m (e.g.: ventilator parts con-
sisting of 2 box parts because of maximal load width).

When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec-
tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components.

The outdoor air intake of the building should if possible be put in the northern or eastern side of the building and away
from other exhaust outlets like kitchen fan outcasts or laundry room outlets.

Warning

The devices have to be adjusted to vibration elements (Mafund, Asozell, Silomer a.s.o.) to avoid a
transmission of structure-borne noise and to guarantee the ventilation of the device base floor.
The unit must be duct connected or in some other way provided with protection so that it is not possible to
come in contact with the fans through the duct connections.

6.1.1

Roof installations

Roof units and roof platforms have to be fixed with screws to the delivered baseframe after the mounting to prevent a
slipping because of wind load. The drillings and screws have to be fixed on site.

Important

• wind load of the devices

• our weight indications of the devices do not include snow loads

6.2

Operating doors

The device is to be set up so that all operating doors can
be opened completely in order to carry out maintenance
work without hindrance (filter change, cleaning, etc.)

6.3

Mounting of device units

Important

Tighten screws only after pushing the parts of the unit together!

Appliances like bar clamps or winches are compulsory.

Check elastic joints for cracks after assembly and in annual cycle, if necessary seal again.

|

Summary of Contents for MAXK Series

Page 1: ...Document in original language MAXK Installation and Operating Instructions GB...

Page 2: ...air AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agree...

Page 3: ...indications for the kind of delivery dismantled assembly group 9 6 5 1 Unit profile 9 6 6 Mounting indications for wet parts 10 7 Internal components 10 7 1 V cell filter 10 7 2 Air heater air cooler...

Page 4: ......

Page 5: ...Declaration of Incorporation 1 1 Declaration of Incorporation...

Page 6: ...Carry out this action 1 Carry out this action if applicable further actions 2 Carry out this action 3 if applicable further actions 2 2 Notes on the documentation Warning Hazard as a result of improp...

Page 7: ...system Take care not to damage the water battery when connecting water pipes to connectors Use a spanner to tighten the connection 4 Product information 4 1 General This installation manual concerns a...

Page 8: ...for application in residential construction At an external pressure of Pa 190 Also suitable for application in residential construction Effective heat recovery rate 84 84 84 84 84 87 Electric power co...

Page 9: ...B A 63 6 78 3 63 6 61 8 79 6 Operation at the upper limit 5 Transport and storage 5 1 General MAXK I3 DC air handling units are delivered in transport units The width of the lorry inside width approx...

Page 10: ...Use only forks which extend to the whole width of the single parts Note lenght of fork width of equipment approx 100 mm Too short forks cause damages at the range of the floor covering 5 4 Big units S...

Page 11: ...rning The devices have to be adjusted to vibration elements Mafund Asozell Silomer a s o to avoid a transmission of structure borne noise and to guarantee the ventilation of the device base floor The...

Page 12: ...guaranteed Thus the function of the devices is guaran teed and leakages at doors or device connections are prevented Step 1 Check the mounting surfaces as to their planeness Unplane mounting surfaces...

Page 13: ...ndications for the kind of delivery dismantled assembly group Kind of delivery delivery of devices partially screwed resp completely dismantled Before plugging on the device profiles the stops of the...

Page 14: ...pollution must be controlled with a differential pressure device U tube inclined tube Filter cells have to be renewed completely after the maximum difference pressure has been reached Check the stand...

Page 15: ...the piping General rule for Cu Alu register The water forerun has to be connected on that collector which is situated very close to the air outlet Attention In case of mounting the connection must be...

Page 16: ...s a minimum of wear On heaters with higher ratings part of the output are controlled by a step controller However fine adjustment of the temperature is always carried out by the electronic ON OFF cont...

Page 17: ...ors at pressure side release chains only after standstill of the ventilators 7 8 Silencer To avoid fan noise being transferred via the duct system silencers should be installed both on supply and extr...

Page 18: ...ents and rubber sleeves are automatically delivered parts 1 to 5 The syphon may not be connected directly with a drain conduction but it must be guaranteed that it can run out freely Before putting in...

Page 19: ...wing of the tub is preprogrammed 8 1 Syphon for cooler Pressure operation Note For tubs which have to be connected within the overpressure range hand made syphons must be installed These must have a r...

Page 20: ...e weather protection roof cannot be bought immediately the top of the unit must be covered watertight The outside joints of outdoor units have to be permanently elastic sealed While assembly work the...

Page 21: ...t roof frame insulated extra charge detail drip ledge Mounting of the drip ledge install set up bolt the device screw the drip ledge with a drilling screw 4 8 x 19 at the device brace Mount pre fabric...

Page 22: ...east 150 mm Caution If the unit is installed in a cold place make sure that all joints are covered with insulation and tape well Duct connections duct ends should be covered during storage and install...

Page 23: ...amage is caused due to your failure to observe these instructions the guarantee is invalidated 11 3 Maintenance instructions Performance Component Activity Periodic If required Number per year 1 Fan 1...

Page 24: ...e filter and document the filter change x 8 Weather protection guard 8 1 Examine for dirt mounting damage and corrosion x 1 8 2 Function sustenance cleaning x 9 Damper 9 1 Examine for dirt damage and...

Page 25: ...om the power supply and contact the manufacturer Fan running roughly unsteady Imbalance of the impeller Rebalancing by spcialized company Wrong direction of rotation of the impeller Consultation with...

Page 26: ...defect Contact the manufacturer Air handling unit does not cool or cools insufficiently Air in the water cooling battery Venting To high temperature of the cooling coil Control the temperature of the...