![SystemAir MAXK Series Installation And Operating Instructions Manual Download Page 18](http://html1.mh-extra.com/html/systemair/maxk-series/maxk-series_installation-and-operating-instructions-manual_1423289018.webp)
14
| Syphon
7.9.1
Roof units
Lights are wired on internal terminal boxes. Internal
wiring of the terminal boxes between each other resp.
from component to component must be made on site.
8
Syphon
1a Rubber sleeve 40–30
1b Rubber sleeve 40–30
2 Jaining piece 40–40
3 Sleeve nut 1 1/2“
4 Sealing Ø 40
5 Arc Ø 40
6 Plunger tube Ø 40
7 Sleeve nut 1 1/2”
8 Bearing ring Ø 40
9 Sealing Ø 40
10 Terminal arc Ø 40
11 Sealing 1 1/2”
12 Check valve with drain
13 Sealing 1 1/2”
14 Screw cap 1 1/2”
15 Ball
16 Screw cap 1 1/2”
For each device drain a syphon must be provided. The installation can be
seen in picture 1. The length of the arc (5) and plunger tube (6) has to
be adapted to the existing negative pressure. In case of drains of ¾“ up
to 1 ½“ connecting elements and rubber sleeves are automatically
delivered (parts 1 to 5). The syphon may not be connected directly with
a drain conduction but it must be guaranteed that it can run out freely.
Before putting into operation the device or longer standstill periods the
syphon must be cleaned (cleaning 4 times a year). Also the drop
separators have to be cleaned half - yearly with a steam vacuum
cleaner. If there are several drains in one device then a separate syphon
has to be put on each sleeve. Do not connect on one common
conduction. If the syphons are regulary delivered a functional test must
be made in time to avoid water damages.
negative
pressure in
unit P (Pa)
shortening
of the
plunger
tube no. 6
by mm
shortening
of the arc
no. 5 by
mm
2000
1900
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
100
110
110
110
110
110
-
-
-
-
-
-
-
-
-
-
10
20
30
40
0
10
20
30
40
50
60
70
Note:
Other types of construction may only be used after consultation.
|