8-1
| Connection of EC fan motor, diagnostics/faults and configuration of speed control
Annex 8 Connection of EC fan motor, diagnostics/faults and configuration of speed
control
8.1
Connection of ECbluefin fan motor
12.3
Connection diagrams
Adhere to the further information under Mains connection.
UL: Input (Line)
Copper connecting leads with an insulation temperature of at least 80
°
C must be used!
AP00001C
28.08.2018
24V 10V GND D1
E1
DC Out
(I
m
a
x
= 7
0 m
A
)
DC Out
(I
m
a
x
= 1
0 m
A
)
Digital In
Analog In
L3/N
L2
L1
ECblue BASIC-MODBUS
(_ _ _ _ _-_I_.D_._ _ _ _), (_ _ _ _ _-_I_.G_._ _ _ _)
K1
Netzspannung
Leistungsschild
Line voltage
Rating-plate
Eingang
Input
0...10 V
4...20 mA
+
Externe Drehzahlvorgabe
External speed setting
4
5
2
10 kΩ
1
Kontaktbelastung
Contact rating
max. AC 250 V 2 A
PE
PE
L1
L2
L3
L1
N
14
NO
11
CO
12
NC
GND
ID1 GND
ID2
A
(D+)
A
(D+)
B
(D-)
B
(D-)
GND
GND MODBUS
(RS-485)
Addressing
Addressing
MODBUS
(RS-485)
PORT 1
PORT 2
3
0
1
Aus / Ein
Off / On
1
Line voltage see rating plate
2
Relay output "K1" for fault reporting (factory function), max. contact load AC 250 V 2 A
- During operation the relay is energised, i.e. the connections "11" and "14" are bridged
- In case of a fault, the relay is de-energised, i.e. the connections "11" and "12" are bridged
- In case of a shutdown using the enable (D1 = Digital In 1) the relay remains energised
3
Digital enable input (factory function)
- Device "ON" when contact closed
- Device "Off" when contact open
4
External speed setting
5
Input 0...10 V, 4...20 mA
6
PWM input, f = 1...10 kHz
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Enclosure
L-BAL-F078D-GB 1939 Index 003
Part.-No.
73/78
output |