Speed control for rotary heat exchanger |
5-1
Annex 5 Speed control for rotary heat exchanger
5.1
Speed control
The cabinet with the speed control system for the rotor is installed behind the inspection door.
The cabinet contains the speed controller with all components, terminal blocks, LED displaying the operation mode, the
dual position DIP switch with 8 sliding levers for programming the rotor motor signal and a button for the activation of
the test mode.
Through the different combinations of the 8 sliding levers of this dual position DIP switch, the correct signal is available
for the 2 different motors used for the 7 sizes of Geniox Core air handling units. The sliding levers are set and the
function is checked at the factory. The positions of the levers appear from the tables below.
5.1.1
Selection of correct signal via the 8 DIP switch levers
Position
Function
Code
Up
Active = ON
1
Down
Deactivated = OFF
0
The factory sets the positions of the 8 DIP switch levers for the maximum of 12 revolutions per minute for standard
temperature exchangers and for sorption-hybrid exchangers. The position of each of the 4 DIP switches to the left is
shown below.
Geniox
Core
Pulley
Position for DIP switches to the left
Motor
10
54
0000
90TYD-S214-M 2.8Nm
11
54
0000
12
54
1000
14
77
0000
16
77
1000
18
77
1000
20
85
0100
120TYD-S214-M 5.5Nm
The factory sets the positions of the 8 DIP switch levers for the maximum of 20 revolutions per minute for sorption
exchangers. The position of each of the 4 DIP switches to the left is shown below.
Geniox
Core
Pulley
Position for DIP switches to the left
Motor
10
70
1000
90TYD-S214-M 2.8 Nm
11
77
1000
12
95
1000
14
95
1000
16
118
0100
120TYD-S214-M 5.5 Nm
18
112
1100
20
118
1100
5.1.2
Indication of operation mode via red and green LED as well as test of motor
The LED is in the cover of the cabinet.
LED indication
Value
No indication
Power off
Green
Ordinary operation
Green – flashes
Ready for operation
Green/redstrobe,slow
Magnet on the rotor has activated rotor guard
output |