background image

10

D200-41-00

Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy

TESTING

Testing should only be carried out by qualified
personnel.  Before undertaking any testing ensure that
the proper authorities have been informed, and if
necessary, that the unit has been isolated from the fire
control panel to prevent unwanted alarms.

Sensor Testing

With the unit powered up and the top cover removed
the sensors can be tested for functionality using methods
described by the manufacturer (for example aerosol spray
or magnet test).

System Testing

Alarm:  The installed system must be checked with the top
cover securely fitted.  As a minimum, smoke should be
introduced to the furthest sampling point from the A300E
unit on each branch of the pipe. The choice of smoke
source is dependant on the installation but in all cases the
smoke must be present for the duration of the test –
aerosol sprays for point detectors DO NOT work on
aspirated systems.

If it is possible to get close to the sampling point then a
basic, functional check can be carried out with smoke
matches or lighted taper etc. But for measurable
performance tests then refer to Appendix A of the FIA Code
of Practice for Aspirating Systems to select the
appropriate test for the installation.

Fault:  Simulate a fault on the A300E unit (for example,
remove the power) and check that a fault is signalled at the
fire panel.

MAINTAINANCE

With normal use, the filter elements will eventually become
contaminated with dust particles, impeding airflow. It is
recommended that it be changed every six months.

To change the filter:

1. Unscrew the top cover
2. Lift out the foam filter elements from its housing

3. Fit a new filter kit so that it lies flush with the top of its

housing

4. Replace the top cover

5. Test the unit as described above.

IMPORTANT

To ensure maximum efficiency and longevity of the filter,
when fitting the replacement filter element kit, the Coarse
filter needs to be fitted first into the pipe.

ACCESSORIES

The following accessories are available to order:

Model Number

Product

02-FL50

Replacement Filter Element Kit

20-LA0015

Replacement Key to Open Detector

Table 5:  Problem Solving

Table 4:  A300E Current Consumption

Fan Speed

Current mA

Bargraph Value

0

110

1

120

2

130

3

150

4

170

5

190

6

220

7

235

8

265

9

300

Table 3:  Typical Flow Sensitivity Settings

PIPE SETUP

RECOMMENDED

FLOW

(all 50m lengths unless otherwise stated)

FAN SPEEDS

SENSITIVITY

13 x 3mm Sampling Holes, 1 x 6mm End Hole

9

9

8 x 3mm Sampling Holes, 1 x 6mm End Hole

6-9

9

4 x 3mm Sampling Holes, 1 x 6mm End Hole

6-9

7

1 x 5mm Sampling Hole, 1 x 5mm End Hole

6-9

5

1 x 8mm End Hole

5-9

2

1 x 8mm End Hole (10m Pipe)

3-9

1

Problem

Possible Solutions

Power light flashing.

Ensure supply to external power
connector within limits.

No lights on display.

Ensure  supply  leads  correctly

Fan not running

orientated. Ensure that FUSE
correctly seated in socket and fuse
not blown.

No lights on display.

Ensure ribbon cable fully seated into

Fan running OK.

main & display boards.

Flow HI/LO light on

Ensure  sampling  pipes  correctly
installed, lid fitted and box fully sealed.
Ensure filters not blocked.
Ensure flow calibration procedure has
been carried out

Flow reading on Bargraph Decrease  Flow  sensitivity  setting
display  moves  erratically.

and re-calibrate air flows

Flow reading on

Increase Flow sensitivity setting

Bargraph  unresponsive

and re-calibrate air flows

to broken/blocked pipes

Sensor(s) unresponsive

Ensure sampling pipe installed correctly

to  smoke  tests

and undamaged.  Ensure that holes
and pipe length do not exceed limits
for detector. Ensure that
recommended test method is used.

Summary of Contents for A310E

Page 1: ...e INTRODUCTION There are many instances where aspirated smoke detectors are specified but where the very high sensitivity that is normally inherent in these devices is an unnecessary expense The A300E Series Aspirated Smoke Detector provides the perfect solution A300E Series aspirating smoke detectors are available in single or dual channel formats giving a large monitored area using sampling hole...

Page 2: ...re 2 CapillaryTube Sample Holes End Cap The end of the pipe should be terminated with an end cap having a central hole typically 6mm in diameter If the end cap is not used then practically no air will be drawn through the side holes Without a hole in the end cap the contributions from the side holes will tend to be very unbalanced Bends Bends are either 45 or 90 degrees For the 90 degree bends it ...

Page 3: ... Figure 4 A300E SERIESTerminal Layout ASPIRATING SYSTEM CHANNEL 2 FAULT CONTACTS A320E DUAL CHANNEL UNIT ONLY NO COM NC NO COM NC EXTERNAL POWER SUPPLY TO ASPIRATING SYSTEM ASPIRATING SYSTEM CHANNEL 1 FAULT CONTACTS BOTH A310E AND A320E 24VDC 0VDC FUSE LOOP IN LOOP IN LOOP OUT LOOP OUT Sensor Connection The loop terminals are linked via a ribbon cable to the terminals mounted on the front display ...

Page 4: ...rrect wiring to the device or base LOOP IN LOOP IN LOOP OUT LOOP OUT Sensor Arrangement 1 See figure 5 Two analogue addressable sensors are wired through the aspirating unit Loop connections are made to the terminal block on the A300E main PCB Note This configuration can increase the loop impedance by up to one Ohm If this is likely to cause a problem use Sensor Arrangement 2 below MAIN PCB DISPLA...

Page 5: ...logue addressable sensors are wired through the aspirating unit Loop connections are made to the terminal block on the A300E main PCB Figure 30 Wiring Configuration 1 with Isolator Bases A300E ASPIRATING SYSTEM ENCLOSURE DISPLAY PCB MAIN PCB SENSOR 2 SENSOR 1 LOOP IN LOOP IN LOOP OUT LOOP OUT Sensor Arrangement 2 with Isolator Bases See Figure 40 The analogue sensors are connected directly to the ...

Page 6: ...th channels of the A320E is sufficient within the system see Figure 60 If the wiring and module must remain within the aspirating unit an M503ME micro module can be used in place of the M210E 47K R 47K R 47K R Figure 50 Suggested Wiring for A310E A320E Using M210E M220E Module A300E ASPIRATING SYSTEM ENCLOSURE DISPLAY PCB MAIN PCB SENSOR 2 SENSOR 1 EXTERNAL PSU 24V EXTERNAL PSU 0V M210E OR M220E I...

Page 7: ... AIRFLOW SPEED BAR GRAPH POSITION FOR SECOND SENSOR IF REQURIED AIRFLOW INDICATOR OK HIGH LOW FAN FAULT A320E ASPIRATING SYSTEM LAYOUT Figure 7b Display Functions Dual ChannelVersion POWER GENERAL FAULT AND CODE ENTRY INDICATORS ARE COMMON TO BOTH CHANNELS UNLOCK INSTALL SENSOR HERE INSTALL SECOND SENSOR HERE AIRFLOW INDICATORS AND AIRFLOW SPEED BARGRAPH REFER TO THE CHANNEL IN WHICH THEY ARE LOCA...

Page 8: ...itivity is selected to accept and cycle to next mode 3 Set High air flow limit Hi LED flashes Press CHANGE to set upper air flow limit as indicated on bar graph Press SELECT once desired high air flow limit is selected to accept and cycle to next mode 4 Set Low air flow limit Lo LED flashes Press CHANGE to set lower air flow limit as indicated on bar graph Press SELECT once desired low air flow li...

Page 9: ...nnel 1 Bar Graph Sensitivity Channel 1 OK LED Flashes Press CHANGE to set air flow sensitivity as indicated on Channel 1 bar graph Press SELECT once desired sensitivity is selected to accept and cycle to next mode 3 Set Channel 2 Bar Graph Sensitivity Channel 2 OK LED Flashes Press CHANGE to set air flow sensitivity as indicated on Channel 2 bar graph Press SELECT once desired sensitivity is selec...

Page 10: ...he top of its housing 4 Replace the top cover 5 Test the unit as described above IMPORTANT To ensure maximum efficiency and longevity of the filter when fitting the replacement filter element kit the Coarse filter needs to be fitted first into the pipe ACCESSORIES The following accessories are available to order Model Number Product 02 FL50 Replacement Filter Element Kit 20 LA0015 Replacement Key ...

Page 11: ... the fan speed will be to increase or decrease the transport time Default settings are programmed into the detector for the high and low flow limits It should not normally be necessary to change these settings NOTE If using a sensor other than the 7251 Laser see section 3 1 Sensors Certified for use with the A300 in the Appendices Table 6 A300E Series Pipe Installation Limits The following figures...

Page 12: ...oles First Hole 4 0 m from Riser Pipe No Hole Fan Alarm Length of 3mm Spacing Speed Level m Holes m 2 x 100 2 x 18 5 3 9 1 Pipe No Hole Fan Alarm Length of 3mm Spacing Speed Level m Holes m 2 x 100 2 x 18 5 9 1 Aspirating Smoke Detector 6mm End Hole Pipe Lengths Including Riser Up to 100 m Ceiling Height 2 5 m Height From Ground 1 5 m Riser Height 1 0 m 25mm Pipe Diameter with 3mm Sampling Holes 1...

Page 13: ... of the sampling holes etc In Figure 1 2 1 a room has a single sampling pipe that provides detection for the whole room Aspirating Unit containing detector and fan Fan draws air down pipe system for detector to sample smoke plume rises and enters pipe system through sampling point holes Figure 1 2 1 Single Sampling Pipe In Figure 1 2 2 the same room has a two channel sensor allowing two sampling p...

Page 14: ...ests 1 5 The Design Process When designing the actual sampling pipe network there are many factors that need to be considered The site must be carefully surveyed and as much information as possible should be gathered 1 5 1 Requirements The first consideration is to precisely ascertain the requirements of the installation Once these have been decided the type of situation can be looked at 1 5 2 Act...

Page 15: ...5 deg Elbow Large Bore 25mm 02 1005 25 Removable Union Large Bore 25mm 02 1007 25 T Piece 25mm 02 1006 25 End Cap for Large Bore 25mm 02 FLU2 Filter Unit 25mm With Filter Element for Harsh environment 2 2 Common Accessories There are a number of accessories that can be used Model Number Product Description 02 1008 15 Flush Capilary Sampling Point T Piece 1 5m Capillary Tube For use with false ceil...

Page 16: ...ign of a system The air temperatures at which the room operates must be taken into account If the aspirating pipe network is inside the cold room the following points should be noted 1 The pipes should be suspended or attached further away than usual from the ceiling or wall as these may contract and expand with large changes in air temperature 2 Sampling holes should be drilled on the side of the...

Page 17: ...ipes Running Parallel to the Roofline Max 10m Max 10m Pipes Run the Length of the Building Parallel to the Roofline Aspirating Detectors Figure 4 4 1 High Roof Example 1 Pipes Running Across theWidth of the Roofline Aspirating Detector Maximum 10m Between Pipes at the Roof Pipes Run theWidth of the Building across the Roofline The second alternative shows the pipes running in parallel along the ro...

Reviews: