background image

 

Page 1 

 

 

Photoelectric Smoke Detector 

 

F11-Y1-xx 

 

Operation Instruction Manual 

 

 

 

 

 

 

 

 

 

 

ES1103 K0 

 

Thank you for purchasing this product. 

In this manual, we have shown the important notice in order for you 

to use the device just and the method of handling this system. 

In  addition  to  you  read  this  manual  well  before  the  utilization, 

understanding well, and use. 

After you read, in the place where it is seen with anytime, please be 

sure to keep. 

Summary of Contents for F11-Y1 Series

Page 1: ...his product In this manual we have shown the important notice in order for you to use the device just and the method of handling this system In addition to you read this manual well before the utilization understanding well and use After you read in the place where it is seen with anytime please be sure to keep ...

Page 2: ...3 Outline Dimensions 6 3 Install 7 3 1 Installation place 7 3 2 Method of installation 8 4 Specifications 10 4 1 Part Number 10 4 2 Electric specifications 10 4 3 Mechanical specifications 10 4 4 Environmental specifications 11 5 Self check Function 12 6 Maintenance and Inspection 12 6 1 Daily Inspection 12 6 2 Periodic Inspection 12 7 Disposal 13 8 Support 13 ...

Page 3: ...ind and flood breakdown and the loss by the thunderbolt and other natural disasters etc After the shipping transporting and moving and falling etc at your corporation breakdown and the loss with inadequate handling When cause of breakdown due to the reason other than the payment item Caution Warning The Warning symbol is used to indicate situations and conditions that can cause operator serious in...

Page 4: ...unit pardons the damage which is induced by the breakdown of the payment item 2 Name and Function of each section 2 1 Detector Type F11 Y1 State Indication LED Normal supervision 10 seconds interval Alarm mode 2 seconds interval Trouble mode Off not blinking Address Seal It indicates detector s address Smoke chamber The embedded sensor is to detect a smoke concentration Flashing time is also longe...

Page 5: ... terminals are internally connected Please wire to another Base Wiring Screw It s a wiring screw Do not put a line into this terminal except communication line It causes trouble Tighten the wiring screw with the specified torque If it s loose it causes fire and malfunction torque 0 5N m Reference value Conformity wire 18 26AWG Incase of Pin terminal under φ2mm Strip length 4 5mm Warning Warning ...

Page 6: ...730110 K0 頁 6 ES1103 2 3 Outline Dimensions Detector Mounting Base ...

Page 7: ...ses trouble Do not install wrong location The smoke detector cannot detect a smoke Be sure to install the detector away from sources of electrical noise such as high voltage and high current switches Isolation from electric noise source such as power line The signal conductor which is connected to the detector please wires over 20cm separating from the power line Case it is not possible please pas...

Page 8: ...tted wires with or run them close to Incorrect loading of the equipments can cause a malfunction failure or drop Tighten the screw in the specified torque range Under tightening can cause a drop short circuit or malfunction Over tightening can cause a drop short circuit or malfunction due to damage to the screw or he equipments and malfunction and fire Tighten the wiring screw with the specified t...

Page 9: ...Turn a Detector Clockwise until make a sound with a snick See above Put Insert guides Detector Terminal and Attachment together correctly It causes trouble Do not turning a detector too much Also do not make a lack of insertion Do not remove a detector Fire can not be detected Do not use detector which have impacted And also do not paint or cover a detector Warning ...

Page 10: ...t blinking Trouble mode gives priority over the Alarm mode 6 Self Check Function Sensitivity revise The Detector revise own sensitivity changes automatically once a day Use of Environment and Dirty and Degradation of Optics parts cause of sensitivity changes Limit the amount of sensitivity revision come and failure 7 Address Addresses are stored in EEPROM If EEPROM has problem Detector will be tro...

Page 11: ...85 R H Non condensing 4 Resistance to corrosion No tolerance to acid and alkaline Use the detector in an environment that meets the general specifications contained in this manual Otherwise it causes trouble and erroneous operation Working temperature and humidity will affect the life span of equipment Please consider derating and use Caution Warning ...

Page 12: ... user s manual for the control unit Do not needs to check smoke detect function with real smoke such as Tobacco incense etc Because this smoke detector has self check functions Refer to 5 Self check function Please do visual inspection periodically There are possibilities that an entrance of the smoke chamber cover with dust and foreign matter and continue to use and malfunction If there are Adhes...

Page 13: ...sal Disposal methods are specific criteria depending on each municipality 8 Support Please inquire about this product to Fenwal Controls of Japan Co Ltd Tokyo headquarters Fenwal Controls of Japan Co Ltd 1 5 10 Iidabashi Chiyoda Tokyo 102 0072 Japan Tokyo headquarters 81 3 3237 3565 ...