Edit Equipment (cont’d)
Notes:
5. If the dbinit jumper is changed, the NTP password has to be re-
entered.
6. A span must have been put into service using the ENT-EQPT
command before setting the ENSEMBLER and SSM
parameters.
7. When setting alarm integration time (SEVERITY or SERAFF),
the type of alarm (HOLDOVER, GPS, LOS, AIS, or ERROR) has
to be specified. For example, ED-EQPT::TS3500:CTAG:::
ALARM=HOLDOVER, TIME=72-00, SEVERITY1=EV,
SERAFF1=NSA, SEVERITY2=MJ, SERAFF2=SA; will generate a
holdover event as soon as the condition is detected with an NSA
flag. Once this condition has existed for 72 hours, TS3500 will
generate a major alarm with an SA flag. These parameters can
then be verified using the RTRV-EQPT command.
8. All commands on DCDUSERPORT having TID which equals
SID of the DCD are forwarded to the DCD. Similarly, the
responses from the DCD are sent to the provisioned
DCDUSERPORT.
Response Format:
<sid> <date> <time>
M <ctag> COMPLD
/*LINK:<link>,CMD:<command>*/
;
Summary of Contents for TimeSource 500
Page 1: ...TimeSource 3500 GPS Primary Reference Source 097 72050 01 Issue 7 August 2003 ...
Page 6: ...6 TimeSource 3500 Contents 097 72050 01 Issue 7 August 2003 ...
Page 161: ...4 Chapter TL1 Reference This chapter provides information for using the TL1 language ...
Page 271: ...6 Chapter Specifications This chapter provides equipment specifications ...
Page 297: ...Index ...