114
TimeSource 3500
Installation
097-72050-01 Issue 7: August 2003
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
3
Alarms Output
Connect the TimeSource 3500 alarms to the office alarm panel at
the critical (CR), major (MJ), and minor (MN) wire-wrap pins. See
Figure 26 for the location of the alarm pins, and Figure 29 for the
connections.
Connect at the upper group of pins (AUD) for audible alarms and
at the lower group of pins (VIS) for visible alarms. Connect the
alarm circuit between the NO and C pins for normally open
contacts, or between the NC and C pins for normally closed
contacts.
Figure 29. Alarm Connections
GPS Antenna
Use the supplied 90 degree adapter to connect the coaxial cable
from the lightning suppressor or IF downconverter to the TNC
connector labeled GPS ANT. Refer to Figure 26 for the connector
location.
AU
D
CR
MJ
MN
VI
S
NC
C
NO
NC
C
NO
Summary of Contents for TimeSource 500
Page 1: ...TimeSource 3500 GPS Primary Reference Source 097 72050 01 Issue 7 August 2003 ...
Page 6: ...6 TimeSource 3500 Contents 097 72050 01 Issue 7 August 2003 ...
Page 161: ...4 Chapter TL1 Reference This chapter provides information for using the TL1 language ...
Page 271: ...6 Chapter Specifications This chapter provides equipment specifications ...
Page 297: ...Index ...