098-00028-000 Revision F – May, 2012
TimeProvider 5000 User’s Guide 333
Chapter 4 Provisioning
Provisioning TP 5000 for Expansion Shelf
4. Type
set output-pps holdover on
and press
Enter
.
5. Type
set output-pps fast-track squelch
and press
Enter
.
6. Type
set output-pps state enable
and press
Enter
.
Provisioning 10 MHz Port
To enable the 10 MHz output port and provision its output behavior as Squelch for
the warm-up state, on for the free-run state, and Squelch for the holdover state, use
the following procedure:
1. Login at the Admin or Config-user level.
2. Type
set output-10m warm-up squelch
and press
Enter
.
3. Type
set output-10m free-run on
and press
Enter
.
4. Type
set output-10m holdover squelch
and press
Enter
.
5. Type
set output-10m fast-track squelch
and press
Enter
.
6. Type
set output-10m state enable
and press
Enter
.
Provisioning TP 5000 for Expansion Shelf
Verify that the TP 5000 and expansion are connected as shown in
It is critical that each expansion shelf be configured with a unique shelf ID (0-9)
using the rotary switch on its front panel.
The following actions are required to provision the TP 5000 to support the operation
of expansion shelves:
Enable ETH on TP 5000 IMC module’s DTI / ETH connector to allow
communication with the expansion shelves
Enable DTI on the IMC module
Enable DTI on the I/O module
Summary of Contents for TimeProvider 5000
Page 12: ...Table of Contents 12 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 16: ...List of Figures 16 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 20: ...List of Tables 20 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...
Page 56: ...56 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 Chapter 1 Overview Alarms ...
Page 534: ...Index W W 534 TimeProvider 5000 User s Guide 098 00028 000 Revision F May 2012 ...