TimeProvider 5000 CLI Command Set
show eia-232
This command displays the serial port’s operating parameters: baud rate, parity,
word length, and stop bits.
Command Syntax:
show eia-232
Example:
tp5000> show eia-232
Response:
Baud rate- 57600
Stop bit - 1
Parity
- 0
Data length- 8
Flow control- none
Remarks:
The system's serial interface is fixed at 57.6K, 0, 8, 1; there is no
handshaking. There is no associated Set command.