Configuration Menu
Page 20/28
Programming instructions of the
SYCLOPE INDIG’O
®
Name
Signification
Setting
range
Default
value
Additional load
Minimum dosing action
0 to 30 %
0 %
Dosage mode
Proportional control or Hysteresis
threshold
Prop. or Hyst.
Prop.
Direction
Version pH
Control direction
Acid or Alkali
Acid
Direction
Version Redox
Control direction
Reducer or
Oxidant
Oxidant
Control chart according to the dosing mode set Proportional or Hysteresis.
Proportional dosing mode
Setpoint
2,0
1,5
1,0
0,5
Controlling
value in %
100
Setpoint : 2,00 mg/l
Xp : 1 mg/l
Value in
mg/l
Time
0
75
50
25
0
Time
Hysteresis threshold mode
Setpoint
2,0
1,5
1,0
0,5
Controlling
value in %
100
Setpoint : 1,50 mg/l
Hyst. : 1 mg/l
Value in
mg/l
Temps
0
75
50
25
0
Time
Low Threshold
Hysteresis
High Threshold
Hysteresis