Configuration Menu
Page 19/28
Programming instructions of the
SYCLOPE INDIG’O
®
VII.
Configuration Menu
The Configuration Menu allow you to configure the machine. Keep pressing during 5 sec the “
MENU
”
key to access to this level. Then, press again the Menu key to drive into the different steps.
Menu
Key
Action
Page
Configuration
Press during 5 sec
Dosage
Control relay
Analog output
Flow switch
Sensor (Polarization)
Test
1)
Dosing mode : Page “Dosage”
According to the version of the product, this page allow to set :
Additional load : This value, expressed in %, permit to keep a minimum dosing action even
once the setpoint reached.
Then, according to the version of the machine :
In 4-20 mA version, the dosing mode : Proportional mode (Prop.) or On/Off with hysteresis
(Hyst.)
In pH version, the direction : Direction of the dosing (Acid or pH-) or (Alkali or ph+)
In ORP version, the direction : Oxidant or Reducer
The direction in the 4-20 mA version is always a rising action. The value should be below the
setpoint to have an action of the dosing unit.
In the 4-20 mA version, if the Hysteresis dosing mode is set, the control range should be set
in the “Control” page of the Setting Menu instead of the Xp value in proportional dosing mode.
This value is also expressed in the measuring unity (For example, mg/l).
Dosage
Control relay An
0
Additional
load :
%
Hyst.
Dosage mode :
Prop.
Dosage
Control relay An
0
Additional
load :
%
Oxidant
Direction :
Reducer
Dosage
Control relay An
0
Additional
load :
%
Direction :
Acid (pH-)
Alkali (pH+)
Version 4-20 mA
Version pH
Version ORP