Setting Menu
Page 17/28
Programming instructions of the
SYCLOPE INDIG’O
®
2)
Control settings : Page “Control”
This page allow you to set:
The set point: value to control in your water
The Xp value: value for the proportional action on the metering unit
Name
Signification
Setting range
Default value
Set point
Set point value for
control
4-20 mA : 10% to 85%*
pH : 2 to 12
ORP : 300 à 850
4-20 mA : 20%*
pH : 7,2
ORP : 460 mV
Xp
Value of the
proportional action
4-20 mA : 10% to 500%*
pH : 0,1 to 70
ORP : 1 to 100
4-20 mA : 10%*
pH : 7,2
ORP : 460 mV
(*) : In % of the measured full scale set for the sensor
Details :
-Setpoint : Means value to be reached and stabilized along processing time.
-XP value : Difference between the measuring value and the setpoint for which the regulation is at the
maximum. (Controlling value* at 100%).
*Controlling value : It represent the proportional action on the dosing unit (For example, a dosing pump)
to reach the setpoint. This value is displayed on the main screen and call “
Dosage : xx %
” (See
picture)
Example : Setpoint is 2 mg/l and Xp is 1 mg/l
If difference is 1.5 (> to 1) then Controlling value = 100%
If difference is 1.0 (= to 1) then Controlling value = 100%
If difference is 0.5 (< to 1) then Controlling value = 50%
If difference is 0.25 (< to 1) then Controlling value = 25%
Free Cl
mg/l
1,50
REG
ALR
Dosage : 50%
Setpoint : 2,00 mg/l
Output : 6,400 mA
Alarms
Calibration
Control
2,00
mg/l
Set point :
1,00
mg/l
Xp :
Alarms
Calibration
Control
7,20
(pH)
Set point :
0,30
(pH)
Xp :
Alarms
Calibration
Control
460
mV
Set point :
30
mV
Xp :
Version 4-20 mA
Version pH
Version ORP