background image

GB.GOLDSKFPX.210324

We reserve the right to alter specifications.

www.swegon.com     7

3.2 Adjusting the Duct System 
and air diffusers

In order to prevent the fans from consuming more power than 
necessary, it is important to keep the pressure drop in the system 
at the lowest possible level. It is also important that duct sys-
tems and air diffusers are correctly commissioned to provide the 
comfort expected.
When commissioning air diffusers and the duct systems for the 
GOLD, it is appropriate to follow the proportionality method.
This means that the ratio between the airflows in branch ducts 
remains constant even if you change the airflow in the main 
ducts. The same ratio applies to the air diffusers in the installa-
tion.
When commissioning the duct system there is provision for 
locking the speed of the fans in the air handling unit to provide 
a specific preset flow rate, see Section 4.1.7 in the Function 
Manual, Installation.

3.2.1 Adjustment Sequence

The system should be adjusted in the following order:
1.  Adjust of the air diffusers in each branch duct.
2.  Adjust the branch ducts.
3.  Adjust the main ducts.

3.2.2 Commissioning procedure

1. Set all the air diffusers and dampers to the fully open position.
2. Calculate the quotient between the airflow reading and the 

design airflow of all the air diffusers, branch ducts and main 
ducts. The air diffuser in every branch that has the lowest 
quotient should be fully open. Use this air diffuser as an 
INDEX AIR DIFFUSER. The same applies to branch dampers 
and main dampers.

  When you’ve finished commissioning, one air diffuser in every 

branch, one branch damper and one main damper should 
consequently be fully open.

Example on how to make an adjustment

– Start adjusting duct branch B, since this one has the 
highest quotient.
– The last air device, B3, has the lowest quotient and 
should be fully open.
Adjust the other air devices, B1 and B2, so that these 
will have the same quotientas air device B3 (see item 5 
above).
– Now adjust the air devices in branch duct C. Air 
device C4 should be fully open; throttle the others to 
the same quotient.
– Adjust the air devices in branch duct A. The index air 
device here is air device A3, which means that you first 
throttle air device A4 (the reference device) to device 
A3:s quotient. Then adjust the others to the same quo-
tient as air device A4.
– Throttle branch damper B to the same quotient as 
branch damper A, throttle branch damper C to the 
same quotient as branch damper A.
Check that all dampers have the same quotient.
When commissioning has been completed, 3 air devices 
and one branch damper should stand fully open to 
obtain the lowest possible pressure in the system.

qp = design airflow (l/s)
qm = flow reading (l/s)
  

qm

K (Quotient) =
  

qp

3. Start adjusting the main duct that has the highest quotient 

and the branch duct in the main duct that has the highest 
quotient. Starting from this point enables you to then "press" 
the air in front of you toward the sections of the system that 
have the least air.

4. Adjust the last air diffuser on the duct branch so that it will 

have the same quotient as the index air diffuser. This air 
diffuser becomes the REFERENCE AIR DIFFUSER. The last air 
diffuser on the branch is often the one that has the lowest 
quotient and this air diffuser should be open. In this case, the 
index air diffuser and the reference air diffuser will be one 
and the same.

5. Throttle the other air diffusers in the branch to the same quo-

tient as the reference device.

  NOTE! The quotient in the reference terminal will change 

every time another air diffuser is throttled, so in practice 
the quotient for the reference air diffuser can be set slightly 
higher. The reference device must be measured in between 
each air diffuser throttled.

6. Go to the branch that had the next highest quotient and 

adjust the air diffusers there, etc.

  NOTE! All branch dampers should be fully open until all air 

diffusers have been adjusted.

7. Throttle the branch damper that had the highest quotient to 

the same quotient as the branch that had the lowest quo-
tient.

  NOTE! Keep in mind that the index damper changes quotient; 

proceed as described in item 5.

8. When all branches have been commissioned, throttle the main 

dampers in the same manner.

See also Adjustment example below.

Summary of Contents for GOLD PX

Page 1: ...OPERATION MAINTENANCE INSTRUCTIONS GOLD PX Generation F...

Page 2: ...4 1 2 Installing new filters 8 4 2 Cleaning and Inspection 9 4 2 1 General 9 4 2 2 Filter spaces 9 4 2 3 Heat exchangers 9 4 2 4 Fans and fan spaces 9 4 3 Service and Functionality Check 10 4 4 Warran...

Page 3: ...h On the size 004 005 007 008 011 012 and 014 020 units the safety isolating switch is externally located on the connection hood On the 025 030 and 035 040 size units the safety isolating switch is ex...

Page 4: ...side of the air handling unit and on a wall inside the fan section Refer to the particulars on the product identification plate when you contact Swegon 2 3 Mechanical Design The GOLD PX units are ava...

Page 5: ...nsor outdoor air 6 Electrical equipm cubicle with control unit 7 Valve actuators shut off and bypass dampers 8 Handheld terminal 9 Temperature relative humidity sensor extract air RECOfrost only 10 Ex...

Page 6: ...tallation Program the time switch operating mode temperatures airflows and functions according to Section 4 in the Function Manual Installation Select whether the airflow unit of measurement shall be...

Page 7: ...should be fully open throttle the others to the same quotient Adjust the air devices in branch duct A The index air device here is air device A3 which means that you first throttle air device A4 the r...

Page 8: ...andard filters Pull out the handles A to free the filters from the filter holder Withdraw the filters Possible pre filters inside the air handling unit Withdraw the filters 4 1 2 Installing new filter...

Page 9: ...n against the regular direction of airflow Cleaning must only be done by blowing with compressed air vacuum cleaning with a soft nozzle or wet cleaning with water and or solvent Before you begin clean...

Page 10: ...also be reset via a communication network not applicable to frost guard alarm 5 1 3 To Change Alarm Priority See Section 4 8 6 in the Function Manual Installation 4 4 Warranty To submit a warranty cl...

Page 11: ...supplied with full face end connection panel ac cessory Size A B C D F G H J L Weight kg 004 005 822 825 240 345 230 460 920 579 2333 315 349 387 007 911 5 995 277 5 440 271 543 1085 749 2503 400 435...

Page 12: ...X 76 K 76 K 14 52 380 18 72 284 284 45 45 J 72 The air handling unit is supplied without end connec tion panel if a duct accessory housed in an insulated casing will be connected The AHU can also be s...

Page 13: ...E F H I J K L Weight kg 004 617 825 1300 334 798 1085 238 579 2534 315 480 484 005 617 825 1300 334 798 1085 238 579 2534 315 480 492 007 647 995 1517 350 878 1295 288 749 278 2811 400 599 613 008 64...

Page 14: ...er specifications 14 www swegon com GOLD PX Top 011 012 16 52 D 52 45 45 J F E F E I I PX 380 18 76 72 Size A B D E F H I J L Weight kg 011 827 1199 1631 332 500 1295 332 953 3285 500 814 826 012 827...

Page 15: ...200 1811 405 1354 200 3825 200 203 1235 1451 035 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1792 2038 040 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1818 2082 PX M M L D E...

Page 16: ...G O P N M F E I M F E I Size A B D E F G H I J K L M N O P Weight kg 014 020 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1083 1175 View from above 45 82 45 J 100 21 B 52 52 K...

Page 17: ...ntact function Optional Normally open normally closed 14 15 External low speed External contact function Oversteers the timer from stop to low speed operation 16 17 External high speed External contac...

Page 18: ...15 50 Hz 10 AT GOLD 007 capacity variant 1 1 phase 3 wire 230 V 10 15 50 Hz 10 AT or 3 phase 5 wire 400 V 10 15 50 Hz 10 AT GOLD 007 capacity variant 2 1 phase 3 wire 230 V 10 15 50 Hz 16 AT or 3 pha...

Page 19: ...2 4 kW 030 1 4 0 kW 16 025 1 2 4 kW 030 2 5 0 kW 16 025 2 3 4 kW 025 2 3 4 kW 16 025 2 3 4 kW 030 1 4 0 kW 16 025 2 3 4 kW 030 2 5 0 kW 16 030 1 4 0 kW 030 1 4 0 kW 16 030 1 4 0 kW 030 2 5 0 kW 20 030...

Page 20: ...V 50 Hz GOLD 007 Motor shaft power 0 8 kW motor control system 1 x 230 V 50 Hz or Motor shaft power 1 15 kW motor controller 1 x 230 V 50 Hz GOLD 008 Motor shaft power 1 15 kW motor control system 1 x...

Page 21: ...A Fan A size capacity variant Fan B size capacity variant Fan A Fan B Safety isolating switch A 014 020 14 1 14 1 6 3 6 3 25 14 1 14 2 6 3 6 3 14 1 20 1 6 3 6 3 14 1 20 2 6 3 7 0 14 2 14 2 6 3 6 3 14...

Page 22: ...1 3 6 040 2 5 6 7 Appendices 7 1 Declaration of Conformity For Declaration of Conformity see our home page at www swegon com under Products Services 7 2 Building Materials Declaration For a complete D...

Page 23: ...2250 012 2 Aluminium 422 Domel 2 4 A Static Yes 1 01 66 0 55 3 72 7 62 2 30 1 48 965 2500 014 1 Aluminium 422 Domel 1 6 A Static Yes 1 01 66 8 53 8 75 0 62 1 66 1 26 821 2250 014 2 Aluminium 422 Domel...

Page 24: ...GB GOLDSKFPX 210324 We reserve the right to alter specifications 24 www swegon com All documentation is available in digital form and can be downloaded from www swegon com...

Reviews: