6.2 Connection to Wiring Terminals

SD

WLAN

CPU 1

CPU 2

1

A

2

B

3

GND

4

+

5

-

6

+

7

-

8

+

9

-

10

+

11

-

12

+

13

-

SA Temp

Com 5

Com 4

Com 3

Com 2

Com 1

14

+

15

-

16

+

17

-

18

+

19

-

Heat

Cool

20

C

21

NO

22

C

23

NO

24

C

25

NO

26

C

27

NO

28

P

29

G

30

G0

31

G

32

G0

24V AC

Sensor 1 Sensor 2

Sensor 4

Sensor 3

Com 6

Com 7

Com 8

Com 9

Com 10 Com 11

+

33

-

34

G

35

G0

36

Y

37

U

38

39 40

24V AC In

41 42

18V AC In

45 46

230V AC In

47

43 44

230V AC Out

Digital inputs, terminals 4-17, are of extra-low voltage type. Analogue input, terminals 18-19 have an input impedance of 66 k

Ω

.

230 VAC control voltage is on external terminals 101 (L) and 102 (N).

Wiring 
terminal

Function

Remarks

1,2,3

Connections for EIA -485

1= Communication connection A/RT+, 2= Communication connection B/RT–, 3= GND/COM.

4,5

External stop

Stops the unit by opening the circuit. On delivery, this function is fitted with a jumper. If the connec-
tion is interrupted, the unit will stop.

6,7

External fire/smoke function 1

External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is 
interrupted, the function will trip and initiate an alarm.

8,9

External fire/smoke function 2

External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is 
interrupted, the function will trip and initiate an alarm.

10,11

External alarm 1

External contact function. Optional: Normally open/normally closed. 

12,13

External alarm 2

External contact function. Optional: Normally open/normally closed. 

14,15

External low speed

External contact function. Oversteers the timer from stop to low speed operation.

16,17

External high speed

External contact function. Oversteers the timer from stop or low speed to high speed operation.

18,19

Demand control

Input for 0-10 V DC. The input signal influences the supply air/extract airflow set point if the unit is 
operating in the demand control mode. For connection of sensors, for example CO

2

, CO and VOC

20,21

Circulation pump, heating circuit

Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a heating load.

22,23

Circulation pump, cooling circuit or 
cooling on/off, 1-step operation

Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.

24,25

Cooling, on/off, 2-step operation

Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.

26,27

In-operation indication

Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes when the unit is operating.

28,29,30

Damper control

24 VAC. 28= Controlled 24 VAC (G), 29= 24 VAC (G), 30= 24 VAC (G0). 

31,32

Control voltage 

1)

24 VAC control voltage. Terminals 31-32 are loaded with a total of 16 VA. Opened by means of the 
safety isolating switch.

33,34

Reference voltage

Output for constant 10 VDC. Max. permissible load: 8 mA.

35,36,37,38 Control, recirculation damper

The recirculation damper can be loaded with max. 2 mA at 10 VDC. 35= 24 V AC (G), 36= 24 V AC (G0), 
37= 0-10 V DC control signal, 38= 0-10 VDC feedback signal.

The max permissible common load on terminals 31-32, outputs for Heat/Cool and damper output (terminals 28-30) is max 32 VA (SD) eller 50 VA (RX/PX/CX).

The max. permissible load on the correspond-
ing connection is 16 VA.

Glass fuse, 3.15A

Summary of Contents for GOLD PX

Page 1: ...OPERATION MAINTENANCE INSTRUCTIONS GOLD PX Generation F...

Page 2: ...4 1 2 Installing new filters 8 4 2 Cleaning and Inspection 9 4 2 1 General 9 4 2 2 Filter spaces 9 4 2 3 Heat exchangers 9 4 2 4 Fans and fan spaces 9 4 3 Service and Functionality Check 10 4 4 Warran...

Page 3: ...h On the size 004 005 007 008 011 012 and 014 020 units the safety isolating switch is externally located on the connection hood On the 025 030 and 035 040 size units the safety isolating switch is ex...

Page 4: ...side of the air handling unit and on a wall inside the fan section Refer to the particulars on the product identification plate when you contact Swegon 2 3 Mechanical Design The GOLD PX units are ava...

Page 5: ...nsor outdoor air 6 Electrical equipm cubicle with control unit 7 Valve actuators shut off and bypass dampers 8 Handheld terminal 9 Temperature relative humidity sensor extract air RECOfrost only 10 Ex...

Page 6: ...tallation Program the time switch operating mode temperatures airflows and functions according to Section 4 in the Function Manual Installation Select whether the airflow unit of measurement shall be...

Page 7: ...should be fully open throttle the others to the same quotient Adjust the air devices in branch duct A The index air device here is air device A3 which means that you first throttle air device A4 the r...

Page 8: ...andard filters Pull out the handles A to free the filters from the filter holder Withdraw the filters Possible pre filters inside the air handling unit Withdraw the filters 4 1 2 Installing new filter...

Page 9: ...n against the regular direction of airflow Cleaning must only be done by blowing with compressed air vacuum cleaning with a soft nozzle or wet cleaning with water and or solvent Before you begin clean...

Page 10: ...also be reset via a communication network not applicable to frost guard alarm 5 1 3 To Change Alarm Priority See Section 4 8 6 in the Function Manual Installation 4 4 Warranty To submit a warranty cl...

Page 11: ...supplied with full face end connection panel ac cessory Size A B C D F G H J L Weight kg 004 005 822 825 240 345 230 460 920 579 2333 315 349 387 007 911 5 995 277 5 440 271 543 1085 749 2503 400 435...

Page 12: ...X 76 K 76 K 14 52 380 18 72 284 284 45 45 J 72 The air handling unit is supplied without end connec tion panel if a duct accessory housed in an insulated casing will be connected The AHU can also be s...

Page 13: ...E F H I J K L Weight kg 004 617 825 1300 334 798 1085 238 579 2534 315 480 484 005 617 825 1300 334 798 1085 238 579 2534 315 480 492 007 647 995 1517 350 878 1295 288 749 278 2811 400 599 613 008 64...

Page 14: ...er specifications 14 www swegon com GOLD PX Top 011 012 16 52 D 52 45 45 J F E F E I I PX 380 18 76 72 Size A B D E F H I J L Weight kg 011 827 1199 1631 332 500 1295 332 953 3285 500 814 826 012 827...

Page 15: ...200 1811 405 1354 200 3825 200 203 1235 1451 035 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1792 2038 040 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1818 2082 PX M M L D E...

Page 16: ...G O P N M F E I M F E I Size A B D E F G H I J K L M N O P Weight kg 014 020 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1083 1175 View from above 45 82 45 J 100 21 B 52 52 K...

Page 17: ...ntact function Optional Normally open normally closed 14 15 External low speed External contact function Oversteers the timer from stop to low speed operation 16 17 External high speed External contac...

Page 18: ...15 50 Hz 10 AT GOLD 007 capacity variant 1 1 phase 3 wire 230 V 10 15 50 Hz 10 AT or 3 phase 5 wire 400 V 10 15 50 Hz 10 AT GOLD 007 capacity variant 2 1 phase 3 wire 230 V 10 15 50 Hz 16 AT or 3 pha...

Page 19: ...2 4 kW 030 1 4 0 kW 16 025 1 2 4 kW 030 2 5 0 kW 16 025 2 3 4 kW 025 2 3 4 kW 16 025 2 3 4 kW 030 1 4 0 kW 16 025 2 3 4 kW 030 2 5 0 kW 16 030 1 4 0 kW 030 1 4 0 kW 16 030 1 4 0 kW 030 2 5 0 kW 20 030...

Page 20: ...V 50 Hz GOLD 007 Motor shaft power 0 8 kW motor control system 1 x 230 V 50 Hz or Motor shaft power 1 15 kW motor controller 1 x 230 V 50 Hz GOLD 008 Motor shaft power 1 15 kW motor control system 1 x...

Page 21: ...A Fan A size capacity variant Fan B size capacity variant Fan A Fan B Safety isolating switch A 014 020 14 1 14 1 6 3 6 3 25 14 1 14 2 6 3 6 3 14 1 20 1 6 3 6 3 14 1 20 2 6 3 7 0 14 2 14 2 6 3 6 3 14...

Page 22: ...1 3 6 040 2 5 6 7 Appendices 7 1 Declaration of Conformity For Declaration of Conformity see our home page at www swegon com under Products Services 7 2 Building Materials Declaration For a complete D...

Page 23: ...2250 012 2 Aluminium 422 Domel 2 4 A Static Yes 1 01 66 0 55 3 72 7 62 2 30 1 48 965 2500 014 1 Aluminium 422 Domel 1 6 A Static Yes 1 01 66 8 53 8 75 0 62 1 66 1 26 821 2250 014 2 Aluminium 422 Domel...

Page 24: ...GB GOLDSKFPX 210324 We reserve the right to alter specifications 24 www swegon com All documentation is available in digital form and can be downloaded from www swegon com...

Reviews: