2. General

2.1 Handling the air handling 
unit before commissioning

The air handling unit and its duct connections should be pro-
tected against wetness and condensation until the unit is com-
missioned.

2.2 Range of Application

The GOLD units are designed for use in comfort ventilation appli-
cations. Depending on the variant selected, GOLD units can be 
utilised in buildings such as office buildings, schools, day nurser-
ies, public buildings, shops, residential buildings, etc.
The GOLD PX units can also be used for the ventilation of moder-
ately humid buildings; however not where the humidity is con-
tinuously high, such as in indoor swimming baths. 
In order to fully obtain all the benefits the GOLD system has to 
offer, it is important to take the special characteristics of the air 
handling units into account when planning them into the pro-
ject, installing, commissioning and operating them.
The air handling unit in its basic design should be installed 
indoors. The TBTA/TBTB accessory should be used if the air 
handling units are installed outdoors. If the duct accessories are 
installed outdoors, they must be housed in an insulated casing 
(type TCxx).
The GOLD PX is designed and tested for temperatures, in the sur-
roundings and the air stream, from -40°C to +40°C. 
The fans are approved for continuous operation in temperatures 
of up to 40°C.
The fans are tested for, and can manage operation for one hour 
at 70°C.

Important!

Always read the safety instructions in Section 1 that 
explain the risks involved in running the unit and desig-
nate who shall be permitted to operate and service the 
unit, and carefully follow the installation instructions 
provided in each paragraph.

The product identification plates are located on the inspection 
side of the air handling unit and on a wall inside the fan section. 
Refer to the particulars on the product identification plate when 
you contact Swegon. 

2.3 Mechanical Design

The GOLD PX units are available in 6 physical sizes and for 12 
airflow ranges. 
The outer sheet steel skin is painted in Swegon’s grey metallic 
colour (closest RAL colour: 9007). The handles and decor strips 
and connection hood are black. Internal material: aluminium-
zinc plated sheet steel and Magnelis. Environmental Class C4.  
Panel thickness of 52 mm with intervening insulation consisting 
of mineral wool. 
GOLD PX has supply air filters and extract air filters made of glass 
fibre in filter class ePM10 60% (M5) or ePM1 50% (F7). 
The plate heat exchangers are as standard equipped with bypass 
and shut-off dampers for variable and automatic control of the 
heat exchanger’s efficiency on heat recovery.
The supply air and extract air fans are of GOLD Wing+ type, an 
axi-centrifugal fan with backward-curved blades. The fans are 
direct-driven and have a motor control system for variable speed 
control. 

2.4 Control System

The IQlogic control system is microprocessor-based and is inte-
grated into the air handling unit. It controls and regulates the 
fans, heat exchanger, temperatures, airflows, Operation times 
and a large number of internal and external functions as well as 
alarms.

2.5 Environmental  
Documentation

For a complete Declaration of Construction Materials, see our 
home page at www.swegon.com (applicable to Sweden only).
The air handling unit is designed in such a way that it can be 
easily dismantled into its component parts. When the unit has 
ended its useful product life, the services of an accredited recy-
cling company should be utilised for disposal.
The recyclable weight of the GOLD is about 94% of its initial 
weight.
Swegon AB is associated with the REPA Register, No. 
5560778465. 
Contact Swegon AB, Phone: +46 (0)512-322 00, if you have 
any questions regarding the dismantling instructions or the air 
handling unit’s impact on the environment.

Summary of Contents for GOLD PX

Page 1: ...OPERATION MAINTENANCE INSTRUCTIONS GOLD PX Generation F...

Page 2: ...4 1 2 Installing new filters 8 4 2 Cleaning and Inspection 9 4 2 1 General 9 4 2 2 Filter spaces 9 4 2 3 Heat exchangers 9 4 2 4 Fans and fan spaces 9 4 3 Service and Functionality Check 10 4 4 Warran...

Page 3: ...h On the size 004 005 007 008 011 012 and 014 020 units the safety isolating switch is externally located on the connection hood On the 025 030 and 035 040 size units the safety isolating switch is ex...

Page 4: ...side of the air handling unit and on a wall inside the fan section Refer to the particulars on the product identification plate when you contact Swegon 2 3 Mechanical Design The GOLD PX units are ava...

Page 5: ...nsor outdoor air 6 Electrical equipm cubicle with control unit 7 Valve actuators shut off and bypass dampers 8 Handheld terminal 9 Temperature relative humidity sensor extract air RECOfrost only 10 Ex...

Page 6: ...tallation Program the time switch operating mode temperatures airflows and functions according to Section 4 in the Function Manual Installation Select whether the airflow unit of measurement shall be...

Page 7: ...should be fully open throttle the others to the same quotient Adjust the air devices in branch duct A The index air device here is air device A3 which means that you first throttle air device A4 the r...

Page 8: ...andard filters Pull out the handles A to free the filters from the filter holder Withdraw the filters Possible pre filters inside the air handling unit Withdraw the filters 4 1 2 Installing new filter...

Page 9: ...n against the regular direction of airflow Cleaning must only be done by blowing with compressed air vacuum cleaning with a soft nozzle or wet cleaning with water and or solvent Before you begin clean...

Page 10: ...also be reset via a communication network not applicable to frost guard alarm 5 1 3 To Change Alarm Priority See Section 4 8 6 in the Function Manual Installation 4 4 Warranty To submit a warranty cl...

Page 11: ...supplied with full face end connection panel ac cessory Size A B C D F G H J L Weight kg 004 005 822 825 240 345 230 460 920 579 2333 315 349 387 007 911 5 995 277 5 440 271 543 1085 749 2503 400 435...

Page 12: ...X 76 K 76 K 14 52 380 18 72 284 284 45 45 J 72 The air handling unit is supplied without end connec tion panel if a duct accessory housed in an insulated casing will be connected The AHU can also be s...

Page 13: ...E F H I J K L Weight kg 004 617 825 1300 334 798 1085 238 579 2534 315 480 484 005 617 825 1300 334 798 1085 238 579 2534 315 480 492 007 647 995 1517 350 878 1295 288 749 278 2811 400 599 613 008 64...

Page 14: ...er specifications 14 www swegon com GOLD PX Top 011 012 16 52 D 52 45 45 J F E F E I I PX 380 18 76 72 Size A B D E F H I J L Weight kg 011 827 1199 1631 332 500 1295 332 953 3285 500 814 826 012 827...

Page 15: ...200 1811 405 1354 200 3825 200 203 1235 1451 035 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1792 2038 040 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1818 2082 PX M M L D E...

Page 16: ...G O P N M F E I M F E I Size A B D E F G H I J K L M N O P Weight kg 014 020 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1083 1175 View from above 45 82 45 J 100 21 B 52 52 K...

Page 17: ...ntact function Optional Normally open normally closed 14 15 External low speed External contact function Oversteers the timer from stop to low speed operation 16 17 External high speed External contac...

Page 18: ...15 50 Hz 10 AT GOLD 007 capacity variant 1 1 phase 3 wire 230 V 10 15 50 Hz 10 AT or 3 phase 5 wire 400 V 10 15 50 Hz 10 AT GOLD 007 capacity variant 2 1 phase 3 wire 230 V 10 15 50 Hz 16 AT or 3 pha...

Page 19: ...2 4 kW 030 1 4 0 kW 16 025 1 2 4 kW 030 2 5 0 kW 16 025 2 3 4 kW 025 2 3 4 kW 16 025 2 3 4 kW 030 1 4 0 kW 16 025 2 3 4 kW 030 2 5 0 kW 16 030 1 4 0 kW 030 1 4 0 kW 16 030 1 4 0 kW 030 2 5 0 kW 20 030...

Page 20: ...V 50 Hz GOLD 007 Motor shaft power 0 8 kW motor control system 1 x 230 V 50 Hz or Motor shaft power 1 15 kW motor controller 1 x 230 V 50 Hz GOLD 008 Motor shaft power 1 15 kW motor control system 1 x...

Page 21: ...A Fan A size capacity variant Fan B size capacity variant Fan A Fan B Safety isolating switch A 014 020 14 1 14 1 6 3 6 3 25 14 1 14 2 6 3 6 3 14 1 20 1 6 3 6 3 14 1 20 2 6 3 7 0 14 2 14 2 6 3 6 3 14...

Page 22: ...1 3 6 040 2 5 6 7 Appendices 7 1 Declaration of Conformity For Declaration of Conformity see our home page at www swegon com under Products Services 7 2 Building Materials Declaration For a complete D...

Page 23: ...2250 012 2 Aluminium 422 Domel 2 4 A Static Yes 1 01 66 0 55 3 72 7 62 2 30 1 48 965 2500 014 1 Aluminium 422 Domel 1 6 A Static Yes 1 01 66 8 53 8 75 0 62 1 66 1 26 821 2250 014 2 Aluminium 422 Domel...

Page 24: ...GB GOLDSKFPX 210324 We reserve the right to alter specifications 24 www swegon com All documentation is available in digital form and can be downloaded from www swegon com...

Reviews: