6.3.3 Electrical Equipment Cubicle

6.3.3.1 Size 004-012

The fuse protection of the air handling unit must not exceed the 
value stated in Section 6.3.1.

SAFETY ISOLATING SWITCH

Capacity variant 1

GOLD PX 004-011:   

 

 

 

20 A

GOLD PX 012:     

 

 

 

25 A

Capacity variant 2

GOLD PX 005-007: 

   

 

 

20 A

GOLD PX 008-012:   

 

 

 

25 A

Fans

GOLD 004-007, GOLD 008, capacity variant 1,  

GOLD 011 capacity variant 1

PX

Two 2-pole, 10A automatic circuit breakers 

GOLD 008, capacity variant 2, GOLD 011, capacity 

variant 2, GOLD 012:

PX

Two 6.3A protective motor switches

FUSES IN THE ELECTRICAL EQUIPMENT CUBICLE

230 V control current

All the sizes/variants: 
One 2-pole, 6A automatic circuit breaker

FUSES IN THE CONTROL UNIT
3.15 AT, incoming 230V. For mounting, see Section 6.2. For 
replacement, dismantle the control unit's plastic enclosure. 

6.3.2 Fans

RATED DATA PER FAN
GOLD 004:    Motor shaft power: 0.8 kW (0.41 kW)*, 
 

  motor controller: 1 x 230 V, 50 Hz

GOLD 005:    Motor shaft power: 0.8 kW, 
 

  motor control system, 1 x 230 V, 50 Hz 

 

or

  Motor shaft power: 1.15 kW, 

 

  motor controller: 1 x 230 V, 50 Hz

GOLD 007:    Motor shaft power: 0.8 kW, 
 

  motor control system, 1 x 230 V, 50 Hz 

 

or

  Motor shaft power: 1.15 kW, 

 

  motor controller: 1 x 230 V, 50 Hz

GOLD 008:    Motor shaft power: 1.15 kW, 
 

  motor control system, 1 x 230 V, 50 Hz 

 

or

  Motor shaft power: 1.6 kW, 

 

  3 x 400 V, 50 Hz

GOLD 011:    Motor shaft power: 1.15 kW, 
 

  motor control system, 1 x 230 V, 50 Hz 

 

or

  Motor shaft power: 1.6 kW, 

 

  3 x 400 V, 50 Hz

GOLD 012:    Motor shaft power: 1.6 kW, 
 

  motor control system, 3 x 400 V, 50 Hz 

 

or

  Motor shaft power: 2.4 kW, 

 

  motor control system, 3 x 400 V, 50 Hz

GOLD 014/020:   Motor shaft power: 1.6 kW,  

 

 

   

motor controller, 3 x 400 V, 50 Hz 

 

or

   

Motor shaft power: 2.4 kW,   

 

 

   

motor controller, 3 x 400 V, 50 Hz

 

or

   

Motor shaft power: 3.4 kW,   

 

 

   

motor controller, 3 x 400 V, 50 Hz

GOLD 025/030:   Motor shaft power: 2.4 kW,  

  

 

   

motor controller, 3 x 400 V, 50 Hz 

 

or

   

Motor shaft power: 3.4 kW,   

 

 

   

motor controller, 3 x 400 V, 50 Hz

 or

    

Motor shaft power: 4.0 kW,  

  

 

   

motor controller, 3 x 400 V, 50 Hz 

 

or

   

Motor shaft power: 5.0 kW,   

 

 

   

motor controller, 3 x 400 V, 50 Hz

GOLD 035:    Motor shaft power: 4.0 kW, 

 

  

 

  motor control system, 3 x 400 V, 50 Hz 

 

or

  Motor shaft power: 5.0 kW, 

  

 

 

  motor control system, 3 x 400 V, 50 Hz

GOLD 040:    Motor shaft power: 6.5 kW, 

 

  

 

  motor control system, 3 x 400 V, 50 Hz 

 

or

  Motor shaft power: 10 kW, 

  

 

 

  motor control system, 3 x 400 V, 50 Hz

*) The motor controller limits the output power to the value 
specified.

Summary of Contents for GOLD PX

Page 1: ...OPERATION MAINTENANCE INSTRUCTIONS GOLD PX Generation F...

Page 2: ...4 1 2 Installing new filters 8 4 2 Cleaning and Inspection 9 4 2 1 General 9 4 2 2 Filter spaces 9 4 2 3 Heat exchangers 9 4 2 4 Fans and fan spaces 9 4 3 Service and Functionality Check 10 4 4 Warran...

Page 3: ...h On the size 004 005 007 008 011 012 and 014 020 units the safety isolating switch is externally located on the connection hood On the 025 030 and 035 040 size units the safety isolating switch is ex...

Page 4: ...side of the air handling unit and on a wall inside the fan section Refer to the particulars on the product identification plate when you contact Swegon 2 3 Mechanical Design The GOLD PX units are ava...

Page 5: ...nsor outdoor air 6 Electrical equipm cubicle with control unit 7 Valve actuators shut off and bypass dampers 8 Handheld terminal 9 Temperature relative humidity sensor extract air RECOfrost only 10 Ex...

Page 6: ...tallation Program the time switch operating mode temperatures airflows and functions according to Section 4 in the Function Manual Installation Select whether the airflow unit of measurement shall be...

Page 7: ...should be fully open throttle the others to the same quotient Adjust the air devices in branch duct A The index air device here is air device A3 which means that you first throttle air device A4 the r...

Page 8: ...andard filters Pull out the handles A to free the filters from the filter holder Withdraw the filters Possible pre filters inside the air handling unit Withdraw the filters 4 1 2 Installing new filter...

Page 9: ...n against the regular direction of airflow Cleaning must only be done by blowing with compressed air vacuum cleaning with a soft nozzle or wet cleaning with water and or solvent Before you begin clean...

Page 10: ...also be reset via a communication network not applicable to frost guard alarm 5 1 3 To Change Alarm Priority See Section 4 8 6 in the Function Manual Installation 4 4 Warranty To submit a warranty cl...

Page 11: ...supplied with full face end connection panel ac cessory Size A B C D F G H J L Weight kg 004 005 822 825 240 345 230 460 920 579 2333 315 349 387 007 911 5 995 277 5 440 271 543 1085 749 2503 400 435...

Page 12: ...X 76 K 76 K 14 52 380 18 72 284 284 45 45 J 72 The air handling unit is supplied without end connec tion panel if a duct accessory housed in an insulated casing will be connected The AHU can also be s...

Page 13: ...E F H I J K L Weight kg 004 617 825 1300 334 798 1085 238 579 2534 315 480 484 005 617 825 1300 334 798 1085 238 579 2534 315 480 492 007 647 995 1517 350 878 1295 288 749 278 2811 400 599 613 008 64...

Page 14: ...er specifications 14 www swegon com GOLD PX Top 011 012 16 52 D 52 45 45 J F E F E I I PX 380 18 76 72 Size A B D E F H I J L Weight kg 011 827 1199 1631 332 500 1295 332 953 3285 500 814 826 012 827...

Page 15: ...200 1811 405 1354 200 3825 200 203 1235 1451 035 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1792 2038 040 1038 5 1990 2400 806 600 1400 2159 479 1744 295 4477 240 1818 2082 PX M M L D E...

Page 16: ...G O P N M F E I M F E I Size A B D E F G H I J K L M N O P Weight kg 014 020 1039 1400 1836 120 400 1000 1551 106 1154 528 3914 300 1200 200 100 1083 1175 View from above 45 82 45 J 100 21 B 52 52 K...

Page 17: ...ntact function Optional Normally open normally closed 14 15 External low speed External contact function Oversteers the timer from stop to low speed operation 16 17 External high speed External contac...

Page 18: ...15 50 Hz 10 AT GOLD 007 capacity variant 1 1 phase 3 wire 230 V 10 15 50 Hz 10 AT or 3 phase 5 wire 400 V 10 15 50 Hz 10 AT GOLD 007 capacity variant 2 1 phase 3 wire 230 V 10 15 50 Hz 16 AT or 3 pha...

Page 19: ...2 4 kW 030 1 4 0 kW 16 025 1 2 4 kW 030 2 5 0 kW 16 025 2 3 4 kW 025 2 3 4 kW 16 025 2 3 4 kW 030 1 4 0 kW 16 025 2 3 4 kW 030 2 5 0 kW 16 030 1 4 0 kW 030 1 4 0 kW 16 030 1 4 0 kW 030 2 5 0 kW 20 030...

Page 20: ...V 50 Hz GOLD 007 Motor shaft power 0 8 kW motor control system 1 x 230 V 50 Hz or Motor shaft power 1 15 kW motor controller 1 x 230 V 50 Hz GOLD 008 Motor shaft power 1 15 kW motor control system 1 x...

Page 21: ...A Fan A size capacity variant Fan B size capacity variant Fan A Fan B Safety isolating switch A 014 020 14 1 14 1 6 3 6 3 25 14 1 14 2 6 3 6 3 14 1 20 1 6 3 6 3 14 1 20 2 6 3 7 0 14 2 14 2 6 3 6 3 14...

Page 22: ...1 3 6 040 2 5 6 7 Appendices 7 1 Declaration of Conformity For Declaration of Conformity see our home page at www swegon com under Products Services 7 2 Building Materials Declaration For a complete D...

Page 23: ...2250 012 2 Aluminium 422 Domel 2 4 A Static Yes 1 01 66 0 55 3 72 7 62 2 30 1 48 965 2500 014 1 Aluminium 422 Domel 1 6 A Static Yes 1 01 66 8 53 8 75 0 62 1 66 1 26 821 2250 014 2 Aluminium 422 Domel...

Page 24: ...GB GOLDSKFPX 210324 We reserve the right to alter specifications 24 www swegon com All documentation is available in digital form and can be downloaded from www swegon com...

Reviews: