GB.GOLDSKFPX.210324
We reserve the right to alter specifications.
20 www.swegon.com
6.3.3 Electrical Equipment Cubicle
6.3.3.1 Size 004-012
The fuse protection of the air handling unit must not exceed the
value stated in Section 6.3.1.
SAFETY ISOLATING SWITCH
Capacity variant 1
GOLD PX 004-011:
20 A
GOLD PX 012:
25 A
Capacity variant 2
GOLD PX 005-007:
20 A
GOLD PX 008-012:
25 A
Fans
GOLD 004-007, GOLD 008, capacity variant 1,
GOLD 011 capacity variant 1
PX
Two 2-pole, 10A automatic circuit breakers
GOLD 008, capacity variant 2, GOLD 011, capacity
variant 2, GOLD 012:
PX
Two 6.3A protective motor switches
FUSES IN THE ELECTRICAL EQUIPMENT CUBICLE
230 V control current
All the sizes/variants:
One 2-pole, 6A automatic circuit breaker
FUSES IN THE CONTROL UNIT
3.15 AT, incoming 230V. For mounting, see Section 6.2. For
replacement, dismantle the control unit's plastic enclosure.
6.3.2 Fans
RATED DATA PER FAN
GOLD 004: Motor shaft power: 0.8 kW (0.41 kW)*,
motor controller: 1 x 230 V, 50 Hz
GOLD 005: Motor shaft power: 0.8 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.15 kW,
motor controller: 1 x 230 V, 50 Hz
GOLD 007: Motor shaft power: 0.8 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.15 kW,
motor controller: 1 x 230 V, 50 Hz
GOLD 008: Motor shaft power: 1.15 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.6 kW,
3 x 400 V, 50 Hz
GOLD 011: Motor shaft power: 1.15 kW,
motor control system, 1 x 230 V, 50 Hz
or
Motor shaft power: 1.6 kW,
3 x 400 V, 50 Hz
GOLD 012: Motor shaft power: 1.6 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 2.4 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 014/020: Motor shaft power: 1.6 kW,
motor controller, 3 x 400 V, 50 Hz
or
Motor shaft power: 2.4 kW,
motor controller, 3 x 400 V, 50 Hz
or
Motor shaft power: 3.4 kW,
motor controller, 3 x 400 V, 50 Hz
GOLD 025/030: Motor shaft power: 2.4 kW,
motor controller, 3 x 400 V, 50 Hz
or
Motor shaft power: 3.4 kW,
motor controller, 3 x 400 V, 50 Hz
or
Motor shaft power: 4.0 kW,
motor controller, 3 x 400 V, 50 Hz
or
Motor shaft power: 5.0 kW,
motor controller, 3 x 400 V, 50 Hz
GOLD 035: Motor shaft power: 4.0 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 5.0 kW,
motor control system, 3 x 400 V, 50 Hz
GOLD 040: Motor shaft power: 6.5 kW,
motor control system, 3 x 400 V, 50 Hz
or
Motor shaft power: 10 kW,
motor control system, 3 x 400 V, 50 Hz
*) The motor controller limits the output power to the value
specified.