Specifications are subject to alteration without notice.
30 www.swegon.se
15 general technical Data
Cooler size
14
18
24
34
48
60
Capacity
Cooling capacity, kW
1
14
18
4
34
48
60
Power demand, kW
7,6
9,6
11,8
16
0
Brine
Type of evaporator
Plate
Plate
Plate
Plate
Plate
Plate
heat
heat
heat
heat
heat
heat
exchanger
exchanger
exchanger
exchanger
exchanger
exchanger
Number
Brine flow (l/s)
0,7
1,0
1,1
1,4
1,35
1,63
Max. available
external pressure, kPa
50
70
40
50
60
70
Compressor
Type of compressor
Piston
Piston
Piston
Piston
Scroll
Scroll
Number
Capacity control, stages
3
3
3
3
3
3
Condenser/
Cooling agent cooler
Type
Direct
Direct
Plate
Plate
Plate
Plate
expansion
expansion
heat
heat
heat
heat
exchanger
exchanger
exchanger
exchanger
Number
–
–
Cooling agent flow (l/s)
–
–
0,6
0,83
0,95
1,17
Max. available
external pressure, kPa
–
–
10
1
30
5
Cooling agent
Type
R134a/
R134a/
R134a/
R134a/
R134a/
R134a/
R407c
R407c
R407c
R407c
R407c
R407c
Number of circuits
Volume, R134a, Kg
,3
,9
,3
4,5
5,4
8,
Volume, R407c, Kg
,1
3,0
4,0
4,9
8,0
8,0
electrical connections
Power supply, Volt
400
400
400
400
400
400
Frequency, Hz
50
50
50
50
50
50
Fuse, A (delayed/delta-characteristic)
0
5
3/35
35
63
63
Suitable for air-
handling unit
GOLD
08, 14/0
14/0
14/0, 5/30, 5/30, 35/40 5/30, 35/40, 35/40, 50/60
35/40
50/60
BCEA/BASIC
004
006
006, 009
009, 014
014
–
sizing
1) The cooling capacities tabulated above are applicable to the following
data: Supply air upstream of the cooling coil 28 °C, 50% RH. Exhaust air
upstream of the COOLER (14 and 18) or cooling agent cooler (24-60) 32
°C. These data presuppose cooling energy recovery by means of a rotary
heat exchanger which then provides an outdoor temperature of 32 °C,
40% RH and an extract air temperature of 26 °C.
2) Applicable to operation under conditions described in footnote 1)
above.
Many factors influence which size of cooling unit and
which coils are required.
The new cooling unit is designed for meeting a variety of
conditions.
For sizing, it is recommendable to utilize the unit selection
program called PMWIN.
gB.Cooler.inSt.060501