9.3
settings Menus
INFO : INST : : TEST : LARM
* COOLER * TUES 1:49
STOP
AUTO OPER
▼
Main menu.
: : :RET : PROG
** OPER MODE **
AUTO OPER
▼
The preset operating mode is shown on the second line.
Pressing PROG changes the image to the settings menu.
1 = SWITCHED OFF and = AUTO OPER.
Select appropriate number and confirm by pressing SET.
: : :RET : PROG
* REGULATION SPEED*
STAGE TIME 600S
▼
Preset value for the STAGE TIME, delayed switching in
from compressor stage 1 to stage and vice-versa. Same
delay also applies to switching between stage and stage
3.
Pressing PROG changes the image to the settings menu.
The step time can be set between 0 and 600 s.
: : :RET : PROG
*** COOLER ***
SIZE 4
▼
The preset COOLER SIZE is shown on the second line. The
preset size must agree with current unit size and should
only be changed if the control circuit card is replaced.
Pressing PROG changes the image to the settings menu.
The sizes 14, 18, 4 , 34, 48 and 60 can be set.
: : :RET : PROG
* ACTTUAL TIME *
WED TIME 07:30
DATE 17/03 - 003
▼
Shows preset ACTUAL TIME. The second line shows the
current day of the week and time. The third line shows
current date. (dd/mm – year)
Pressing PROG changes the image to the settings menu.
: : :RET : PROG
* SPRåK/LANGUAGE *
ENGLISH
▼
Shows preset LANGUAGE. The second line shows current
language selected.
Pressing PROG changes the image to the settings menu.
Press the arrow up or down to advance to the desired lan-
guage from the current list and confirm by pressing SET.
If the Cooler is connected to the GOLD unit by means of
a communication cable, same language appears in both
displays.
: : :RET : PROG
FACTORY SETTING
0
Activating the FACTORY SETTING. The factory setting
function resets all the parameters back to their original
settings. This function should only be used when problems
with settings have arisen.
Pressing PROG changes the image to the settings menu.
Set the value to 1, confirm by pressing SET. The param-
eters will be reset when the display image returns to the
Main Menu.
gB.Cooler.inSt.060501