8 Operation
Analog output
Select the physical flow unit and set the scaling of the
analog output
。
After you select a moisture unit, the corresponding
standard scaling values are displayed. Adjust the
scaling values if needed.
Based on this setting, the flow sensor can convert the
flow values from digit signal to 4 ... 20 mA analog
signal, and then transfer the analog signal to a PLC or
SCADA system.
Some sensors support active and passive analog outputs.
Flow setting
Inner diameter:
Set for the flow calculation.
Gas type:
Select the gas type. (Some gases require real
gas calibration. Please contact the manufacturer).
Constant:
Shows the gas constant of the selected gas, or
enter a constant for mixed gas or not-listed gas.
Flow unit:
Select a desired flow unit.
Consumption unit:
Select the desired consumption unit.
References pressure:
Set for the standard flow
calculation.
Reference temperature:
Set for the standard flow
calculation.
More setting
Std: consumption:
Set the internal consumption counter.
Rev. consumption:
Some sensors support bi-directional
flow measurement. This is the counter for the reverse
direction.
Altitude:
Enter the altitude level. Default value: 0.
User slope:
To correct the flow by a factor, enable the
user slope.
Copy setting
Applicable to S551-P6.
Modbus
settings
Applicable to sensors with the Modbus interface.
Set the Modbus communication parameters.
Sensor info
Shows the sensor information for service inquiries.
22