8 Operation
Ch2 setting
(counter only)
Measure type:
Only counter is selectable.
Description:
Enter a channel name.
Predefine unit:
Select a physical unit.
Customer unit:
Enter a name for the measurement unit
as you want.
Count/pulse:
Enter how many consumption units one
pulse is equal to.
8.5.5 Power meter S110-P setting
S110-P comes with the Modbus output. Please connect it to connector M
of S551.
Sensor type
Select the right CT type (100 A, 1000 A, or 3000 A)
Wire type
Select the wiring type (1-phase 2-wire, 3-phase 2-wire,
or 3-phase 4-wire)
Frequency
Select the frequency (50 Hz or 60 Hz)
Sensor status
Shows the connection status.
If the displayed value is shown as “–– -.-”, it usually
results from a wrong connection with the CTs or voltage
measurement devices.
8.5.6 Analog extension module
Extension module comes with the Modbus output. Please connect it to
connector M. The analog extension module offers additional 8 x 0 ... 20
mA channels. Similar to the analog input channels provided on
connector 3 or 4, the sensor type can be specified through the “Sensor
settings” menu.
8.5.7 Laser particle counter S130
S130 comes with the SDI and Modbus outputs. Please connect it to
connector 1 or 2 or to connector M.
8.5.8 Ultrasonic liquid flow meter S460
For information about the operation and installation, see the instruction
manual of the ultrasonic flow meter S460.
25