Appendix-B- Rack Mounting
The box your chassis was shipped in should include four mounting screws, which you will need if
you intend to install the system into a rack.
Choosing a Setup Location
Leave enough clearance in front of the rack to enable you to open the front door completely
(~25 inches).
Leave approximately 30 inches of clearance in the back of the rack to allow for sufficient
airflow and ease of servicing.
This product is for installation only in a Restricted Access Location (dedicated equipment
room, service closet, etc.).
Rack Mounting Considerations
Ambient Operating Temperature:
If installed in a closed or multi-unit rack assembly, the ambient
operating temperature of the rack environment may be greater than the ambient temperature
of the room. Therefore, consideration should be given to installing the equipment in an
environment compatible with the manufacturer’s maximum rated ambient temperature (Tmra).
Reduced Airflow: Equipment should be mounted into a rack so that the amount of airflow
required for safe operation is not compromised.
Mechanical Loading: Equipment should be mounted into a rack so that a hazardous condition
does not arise due to uneven mechanical loading.
Circuit Overloading: Consideration should be given to the connection of the equipment to the
power supply circuitry and the effect that any possible overloading of circuits might have on
over current protection and power supply wiring. Appropriate consideration of equipment
nameplate ratings should be used when addressing this concern.
Reliable Ground: A reliable ground must be maintained at all times. To ensure this, the rack itself
should be grounded. Particular attention should be given to power supply connections other
than the direct connections to the branch circuit (i.e. the use of power strips, etc.).
Rack Mounting Instructions
This section provides information about installing the Orion-VX1000 into a rack unit. There are a
variety of rack units on the market, which may mean the assembly procedure will differ slightly.
You should also refer to the installation instructions that came with the rack unit you are using.