INSTALLATION

Mounting the Receiver

Install the MLR-MX in a closed 19" rack or cabinet with a
locking rear access door. Cover all unused spaces with blank
metal plates. The LCD screens on the receiver are designed to
be viewed below eye level. If the unit must be mounted where
the screens are above eye level, angle the unit downwards to
improve visibility. The following items can be supplied for a
complete installation:

Stand-up Unit (61.25" tall up to 30 telephone lines)

Part # SG-MLR2-CL

Parts:

• Rack

• Door with lock and ventilation
• Blank plates 21" (2)
• Blank plate 5.25" (3)
• Screws
• Washers
• Clipnuts
• FROST 16V 175VA transformer
• AC Utility Box
• AC Cable Clamps (2)
• 8' Battery Cables

• 18 gauge 3-conductor AC Cable

NOTE: If 30 telephone lines are not used, cover each unused
location with a blank plate

Desk-mount Unit (28" tall up to 30 telephone lines)

Part # SG-MLR2-CM

Parts:

• Rack
• Louvered door back plate
• Blank Plate 1.75"
• Back Plate 7"
• Blank Plates 5.25 (4)
• Screws
• Washers
• Clipnuts
• FROST 16V 175VA Transformer
• AC Utility Box
• AC Cable Clamp for 3/8" cable
• 8' Battery Cable
• 18 gauge 3-conductor AC Cable

NOTES: If 15 modules are not used, cover each unused
location with a blank plate.

Use only UL Listed components with programmable output
on the MLR-MX.

Ex: UL Listed Buzzer part # PKB5-3A0

UL Listed Relay part # HAS-112-12

Grounding

For maximum resistance to static and electrical noise, the 19"
rack frame should be connected to earth ground through the
AC utility box.

Power Supply

Ensure that all electrical connections are made correctly. After
verifying all connections, connect the RED and BLACK leads to
a 12VDC sealed rechargeable battery. Be sure to observe polarity
when connecting the battery. When the battery is connected,
test the system under battery power only.

If a separate DC input is used to power the LCD backlighting
during AC power failures, connect it to the BLGT terminal. It
must be a listed Fire-Protective Signalling System power supply
rated 12VDC. Connect the positive lead from the DC supply to
the BLGT terminal; connect the negative lead from the DC
supply to the GND terminal.

CAUTION:  Connecting a positive (+) terminal to a nega-
tive (-) terminal may cause a fire and possibly serious personal
har m.

For 4-hour standby, a 12-volt 35Ah rechargeable battery should
be used in conjunction with an engine driven power Generator.

Battery Charging Current

The maximum battery charging current is factory set at 1A.

firealarmresources.com

Summary of Contents for SG Security MLR-MX

Page 1: ...MLR MX and Sure Signal CSR Installation and Operation Manual Version 1 0 firealarmresources com...

Page 2: ...ouraged to try to correct the interference by one or more of the following measures Re orient the receiving antenna Increase the separation between the equipment and receiver Connect the equipment int...

Page 3: ...8 Radio Status 8 Radio Status Printer Outputs 8 Max Account Limits 8 User Programming 8 Entering Commands 9 Entering Data 9 SG CPM2 Central Processing Module 10 General Information 10 Features 10 CPM...

Page 4: ...onditions are reported on the LCD screens and sent to the MLR MX Backplane Connection Diagram P6 MV3 MV2 P5 P4 P2 R13 R11 R4 R6 R7 R12 printer and the computer The DRL MX Line Card Module verifies com...

Page 5: ...t is suggested that the receiver be tested before actual installation becoming familiar with the connections and setup of the unit on the work bench will make final installation more straightforward T...

Page 6: ...sed cover each unused location with a blank plate Use only UL Listed components with programmable output on the MLR MX Ex UL Listed Buzzer part PKB5 3A0 UL Listed Relay part HAS 112 12 Grounding For m...

Page 7: ...id numbers for the line card The list will scroll through the hexadecimal numbers 01 to 0F 1 to 15 when the desired number is displayed press the ACK and CANCEL buttons together The serial connection...

Page 8: ...the alarm messages in the event buffer will be transmitted to the CPM2 Display Program Version PROGRAM VERSION PROGRAM VERSION PROGRAM VERSION PROGRAM VERSION PROGRAM VERSION ACK menu SEL sel ACK men...

Page 9: ...etwork name The printer will then print L11 Cantel L11 is the receiver and line number Cantel is the current network Note This network name does not need to be saved in the MLR MX 2D request network l...

Page 10: ...between the Sure Signal and the network The display will show the following message 5004455 22 5004455 22 5004455 22 5004455 22 5004455 22 Low Signal Low Signal Low Signal Low Signal Low Signal The p...

Page 11: ...tions will be set as reserved Option 01 Linecard Number this sets the Physical number on the linecard and all reports are reported using this linecard number Option 0F Mute Buzzer option This option i...

Page 12: ...to be programmed for the Option enter a 2 digit hexadecimal number Sc Second Code is a code or value that is only used with SCADA commands if required enter a 2 digit hex number Entering Data The foll...

Page 13: ...turn the ACK light OFF and silence the buzzer The ACK button is also used in the Configuration Mode to select menu items ACK light Flashes when a message is received from the Line Card and COM1 is dis...

Page 14: ...tions available on the CPM2 To enter the Configuration Mode press the Escape button this message will be displayed Enter MASTER ID Enter MASTER ID Enter MASTER ID Enter MASTER ID Enter MASTER ID Enter...

Page 15: ...knowledge signal is not received from COM1 When using the Star DP8340 printer the CPM2 is able to print in both red and black If an IBM compatible printer is selected the CPM2 will print in black only...

Page 16: ...message will be displayed Contrast Level Contrast Level Contrast Level Contrast Level Contrast Level Press the Enter button to increase the contrast press the Backspace button to reduce the contrast W...

Page 17: ...ts the number of times the CPM2 tries to resend the message to COM1 this value should be 1 during normal communication 06 represents the acknowledge received from COM1 To disable the diagnostics featu...

Page 18: ...displayed This message will be displayed Receiver Number Receiver Number Receiver Number Receiver Number Receiver Number 01 Chg to xx 01 Chg to xx 01 Chg to xx 01 Chg to xx 01 Chg to xx Enter a new r...

Page 19: ...0 45 Feb 23 07 30 45 AC Power LOST AC Power LOST AC Power LOST AC Power LOST AC Power LOST Standby Mode Message During normal standby operation this message will be displayed Feb 23 07 30 45 Feb 23 07...

Page 20: ...rd __ Comd __ LCard __ Comd __ LCard __ Comd __ LCard __ Comd __ Op __ Cd __ Sc __ Op __ Cd __ Sc __ Op __ Cd __ Sc __ Op __ Cd __ Sc __ Op __ Cd __ Sc __ LCard Enter a 2 digit hexadecimal number from...

Page 21: ...e messages will be displayed in order from the most recent to the oldest Press the Backspace button to scroll from the oldest message to the most recent When finished viewing the messages press the Es...

Page 22: ...e signal varies and it can support the maximum 63 byte data block transmission from the control panel When this optional protocol is selected all SIA information will be sent to the host computer usin...

Page 23: ...20 UPS CONNECTION P6 MV3 MV2 P5 P4 P2 R13 R11 R4 R6 R7 R12 P6 MV3 MV2 P5 P4 P2 R13 R11 R4 R6 R7 R12 firealarmresources com...

Page 24: ...rds CAFE 03 Number of Line Cards E 04 Printer Select Backup 0 Enable 1 05 COM1 Configuration Baud 1200 Data 7 bits Parity 2 06 COM1 Format 1 07 ACK Wait Delay 4 0 seconds 08 Heartbeat Select 30 second...

Page 25: ...nal for the CPM2 Contact the software manufacturer for a software upgrade Increase the acknowledge wait time with CPM2 Configuration Option 07 Check COM1 baud rate and communication format using CPM2...

Page 26: ...24 7C 0111 1100 125 7D 0111 1101 126 7E 0111 1110 127 7F 0111 1111 DEC HEX BINARY 128 80 1000 0000 129 81 1000 0001 130 82 1000 0010 131 83 1000 0011 132 84 1000 0100 133 85 1000 0101 134 86 1000 0110...

Page 27: ...B0 30 0 B1 31 1 B2 32 2 B3 33 3 B4 34 4 B5 35 5 B6 36 6 B7 37 7 B8 38 8 B9 39 9 C1 41 A C2 42 B C3 43 C C4 44 D C5 45 E C6 46 F C7 47 G C8 48 H C9 49 I CA 4A J CB 4B K CC 4C L CD 4D M CE 4E N CF 4F O...

Page 28: ...s in parts and workmanship and not to damage incurred in shipping or handling or damage due to causes beyond the control of SG Security Communications such as lightning excessive voltage mechanical sh...

Page 29: ...0 SG Security Communications A Division of Sur Gard Security Systems Ltd 401 Magnetic Drive Units 24 28 Downsview Ontario Canada M3J 3H9 Tel 416 665 4494 Fax 416 665 4222 Toll Free 1 800 418 7618 www...

Reviews: