6.2.3 Setpoint Parameters (SEtP)
No.
Sign
Range
Default
Description
Set
200
Lo
0~99999
1000
DO1Weight Lower Limit / Weight Setpoint 1
201
HI
0~99999
9000
DO2 Weight Upper Limit / Weight Setpoint 2
202
nL
0~50000
50
Non-load Zero Range
‘
Net Weight > Non-load Zero Range
’
for triggering
the Peak Value detection process.
‘
Net Weight
≤
Non-load Zero Range
’
for stopping
the Peak Value detection process.
203
dA
0~2
0
Data Compared with Weight Setpoints
0. groS
[Gross Weight]
1. nEt
[Net Weight]
2. PnEt
[Net Weight Peak Value]
204
do
0~1
1
DO Output Permission
0: oFF
1: on
205
dL
0.1~5.0
0.5
DO Bounce-back Delay Time
[s]
Used for avoiding that the DO alarm switch turns on
and off frequently with its related real-time data
being at the critical point.
Min. Interval Time for Peak Value Detection
[s]
Only after the time delayed, the triggered Peak
Value detection process is allowed to be stopped by
‘
Net Weight
≤
Non-load Zero Range
’
. And only
after the time delayed, the stopped Peak Value
detection process is allowed to be triggered again by
‘
Net Weight > Non-load Zero Range
’
.
206
Ao
0~3
0
AO Signal
0. groS
[Gross Weight]
1. nEt
[Net Weight]
2. dISP
[Displayed Weight]
3. PnEt
[Net Weight Peak Value]
207
AE
0.00~21.00
4.00
Min. AO Value of Weight Signal
[mA or V]
It
’
s the AO current or v
oltage
output value of
weight signal when
‘
Weight value
≤
0
’
.