6.6 F4-CLn Data Clearing
Data Clearing Mode Description:
Manual Clearing Mode
1 Clear Screen: Clear Totalized Weight and Totalized Weight Pulse Count. But Totalized Weight of Current
Shift will not be cleared, so this operation has no effect on recording of weight per shift.
2 Clear Weight: Clear Totalized Weight, Totalized Weight Pulse Count and Totalized Weight of Current
Shift. The cleared value of Totalized Weight of Current Shift will not be recorded.
3 Clear Records: Clear History Records of Totalized Weight. But Current Totalized Weight, Totalized
Weight Pulse Count and Totalized Weight of Current Shift will not be cleared.
Timing Auto Clearing Mode
The parameter „[P606] Auto-clear‟ can be set to „0: OFF / 1: Per Shift / 2: Per Day / 3: Per Month‟, and its
default value is „0: OFF‟.
„Timing Auto Clearing‟ has no effect on recording of weight per shift.
[P606]=„1: Per Shift‟: After recording Totalized Weight per Shift, do operation „Clear Screen‟ automatically.
[P606]=„2: Per Day‟: After recording Totalized Weight of the last Shift per Day, do operation „Clear Screen‟
automatically.
[P606]=„3: Per Month‟: After recording Totalized Weight of the last Shift per Month, do operation „Clear
Screen‟ automatically.
Auto Clearing Before Overflowing Mode
When Totalized Weight value reaches to the maximum value 2×10
9
[Scale Unit], do operation „Clear Screen‟
automatically.
„Auto-clear Before Overflowing‟ has no effect on recording of weight per shift.
RUN AUTO
EXT ALARM
kg
t
t/h
kg/m
Main Display Interface
【
MENU
】
+
【
▲
】
【
▼
】
:
≡
F4-CLn
≡
【
ENT
】
+
【
▲
】
【
▼
】
: ---CLS--
【
ENT
】
M
【
MENU
】
: Exit
【
ENT
】
: Enter
M
【
▲
】
【
▼
】
:
YES/NO
CLS: Clear Screen; CLt: Clear Weight; CLr : Clear Records