SUPERSERVER 2027TR-H72RF/H72QRF/H72FRF USER'S MANUAL
Figure 2-6: Installing into a Rack
Ball-Bearing
Shuttle
Standard Chassis Installation
Installing the Chassis into a Rack (Figure 2-6)
1. Confi rm that the inner rails are properly installed on the chassis.
2. Confi rm that the outer rails are correctly installed on the rack.
3. Pull the middle rail out from the front of the outer rail and make sure that the
ball-bearing shuttle is at the front locking position of the middle rail.
4. Align the chassis inner rails with the front of the middle rails.
5. Slide the inner rails on the chassis into the middle rails, keeping the pressure
even on both sides, until the locking tab of the inner rail clicks into the front of
the middle rail, locking the chassis into the fully extended position.
6. Depress the locking tabs of both sides at the same time and push the chassis
all the way into the rear of the rack.
7. If necessary for security purposes, use screws to secure the chassis handles
to the front of the rack.
Summary of Contents for SUPERSERVER 2027TR-H72FRF
Page 1: ...SUPERSERVER 2027TR H72RF 2027TR H72QRF 2027TR H72FRF SUPER USER S MANUAL Revision 1 0...
Page 5: ...v SUPERSERVER 2027TR H72RF H72QRF H72FRF USER S MANUAL Notes...
Page 10: ...SUPERSERVER 2027TR H72RF H72QRF H72FRF USER S MANUAL x...
Page 30: ...2 12 SUPERSERVER 2027TR H72RF H72QRF H72FRF USER S MANUAL Notes...
Page 34: ...SUPERSERVER 2027TR H72RF H72QRF H72FRF USER S MANUAL 3 4 Notes...
Page 54: ...4 20 SUPERSERVER 2027TR H72RF H72QRF H72FRF User s Manual Notes...
Page 89: ...Chapter 6 Advanced Chassis Setup 6 7 Figure 6 5 Replacing a System Fan in the Fan Housing...
Page 130: ...A 2 SUPERSERVER 2027TR H72RF H72QRF H72FRF USER S MANUAL Notes...