FIREPLACE INSTALLATION

SELECTING LOCATION

To determine safest and most efficient location for fireplace, you 

must take into consideration the following guidelines:

1.  Location must allow for proper clearances (see Figures 1 and 2).
2.  Consider a location where fireplace will not be affected by drafts, 

air conditioning ducts, windows or doors.

3.  A location that avoids cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see Optional 

Outside Air Kit on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Back and sides of fireplace                                      3/4" minimum*
Floor**                                                                       0" minimum
Perpendicular wall to opening                                   12" minimum
Top spacers                                                                0" minimum
Mantel clearances                                            see Mantels, page 6 

Chimney outer pipe surface                                        1" minimum

* Not required at nailing flanges

** See step 2 of Framing

 WARNING: DO NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

Minimum/Maximum Chimney Height

Minimum height of chimney, measured from base of fireplace to 

flue gas outlet of termination, is 14.5 feet for straight flue or a flue 

with one elbow set. Maximum distance between elbows is 6 feet. For 

systems with two elbow sets, minimum height is 22 feet. Maximum 

height of any system is 50 feet. This measurement includes fireplace, 

chimney sections and height of termination assembly at level of flue 

gas outlet (see Figure 20, page 12).

FRAMING

1.  Frame opening for fireplace using dimensions shown in Figures 

1 and 2.

2.  If fireplace is to be installed directly on carpeting, tile (other than 

ceramic) or any combustible material other than wood flooring, 

fireplace must be installed upon a metal or wood panel extending 

full width and depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

4.  Check level of fireplace and shim with sheet metal if necessary.

5.  Before securing fireplace to prepared framing, ember protector 

must  be  placed  between  hearth  extension  (not  included)  and 

under bottom front edge of fireplace to protect against glowing 

embers falling through. If fireplace is to be installed on a raised 

platform, a Z-type ember protector (not included) must be fabri

-

cated to fit your required platform height. Ember protector should 

extend under fireplace a minimum of 1 

1

/

2

".  Ember  protector 

should be made of galvanized sheet metal (28 gauge minimum) 

to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

22"

37 

5

/

8

"

44 

1

/

4

"

Figure 1 - Framing Dimensions

52 

1

/

2

"

15 

7

/

8

"

22 

1

/

2

"

72 

7

/

8

"

Maintain 3/4"

Clearance at

Sides and

Back of

Fireplace

3/4" Clearance Not 

Required at Nailing Flanges  

Figure 2 - Corner Installation

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a 

minimum of 12" beyond each side of fireplace opening is required 

to protect combustible floor construction in front of fireplace. Fab-

ricate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of k = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
  0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such 

as sand-cement grout (see Figure 3, page 6).

Summary of Contents for WCT2042WS

Page 1: ...s appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes WARNING If the information in these instructions is not...

Page 2: ...nufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous operation of the fireplace Consult the local bu...

Page 3: ...treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide...

Page 4: ...STIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS LEFT SIDE RIGHT SIDE NOT LESS THAN 14 TO PER...

Page 5: ...d slide unit back until nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be pla...

Page 6: ...625 Max 33 8 MANTELS A mantel may be installed if desired see Figure 4 Woodwork such as wood trims mantels or any other combustible material projecting from front face must not be placed within 9 of...

Page 7: ...cal Cover Plate and Electrical Bushing Fireplace Chassis Ground To Power Source Receptacle Supplied Power Source Wiring Not Supplied Prewired Receptacle and Ground Sheet Metal Screws Figure 7 Outside...

Page 8: ...ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combinations of 12 18 24 36 and 48...

Page 9: ...Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See Detail B Ceiling Support Pipe 12S 8DM VENTING INSTALLATION Continued Return Elbow Offset Elbow Offset Elbow Return Elbow Offset E...

Page 10: ...ectangular opening must be cut 1 Determine center point where pipe will penetrate the roof 2 Determine center point of the roof Pitch is the distance the roof drops over a given span usually 12 A 6 12...

Page 11: ...ply waterproof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace system must be...

Page 12: ...shroud is to be installed contact manufacturer for specifications 24 Min 24 Min 18 Min Typ Figure 18 Multiple Chase Installation 10 2 Min 10 3 Min 2 Min 3 Min Level of Flue Gas Outlet Figure 19 10 Fo...

Page 13: ...ent Install gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap...

Page 14: ...rther operating guidelines instructions and warranty informa tion please refer to your homeowner s guide or contact your dealer GLASS DOORS Glass doors are optional with this fireplace When fireplace...

Page 15: ...pplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always g...

Page 16: ...PARTS WOOD BURNING FIREPLACE MODELS WRT2042WS WRT2042WSI WCT2042WS WCT2042WSI 11 27 30 23 22 24 10 14 25 4 17 3 2 1 18 5 20 28 12 7 15 9 16 13 8 26 6 29 19 21 MODEL CAT NO WRT2042WS F0687 WRT2042WSI...

Page 17: ...m 1 10 108298 01 Front Face Weldment Smooth 1 108298 02 Front Face Weldment Louvered 1 11 106971 01 Left Side Brick Liner 1 12 108310 01 Rear Brick Liner 1 13 106970 01 Right Side Brick Liner 1 14 108...

Page 18: ...Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Se...

Page 19: ...ered Screen ROUND TOP TERMINATIONS WITH LOUVERS W SLIP SECTION F0919 RLTT 8DM Round Top with Slip Section Louvers F0891 RLTT 8HT Hi Temp Round Top w Lvrd Screen and Slip Section SQUARE TOP TERMINATION...

Page 20: ...Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Support For Use With Chimney Heights In Exces...

Page 21: ...______ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____________________________...

Page 22: ...______ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____________________________...

Page 23: ...ust be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products wi...

Page 24: ...ecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 126631 01 Rev B 05 2015 P126631 01 1508 Elm Hill Pike Suite 108 Nashville TN 3...

Reviews: