INSTALLATION

Continued

We recommend that you install a sediment trap in supply 

line as shown in Figure 12. Locate sediment trap where it is 

within reach for cleaning. Install in piping system between fuel 

supply and appliance. Locate sediment trap where trapped 

matter is not likely to freeze. A sediment trap traps moisture 

and contaminants. This keeps them from going into appliance 

controls. If sediment trap is not installed or is installed wrong, 

appliance may not run properly.

 

CAUTION: Avoid damage to gas control. 

Hold gas control with wrench when connect

-

ing it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

 

WARNING: Test all gas piping and connec-

tions, internal and external to unit, for leaks 

after installing or servicing. Correct all leaks 

at once.

 

WARNING:  Never  use  an  open  flame  to 

check for a leak. Apply a noncorrosive leak 

detection fluid to all joints. Bubbles forming 

show a leak. Correct all leaks at once.

 CAUTION: Make sure external regulator has 

been installed between propane/LP supply and 

appliance. See guidelines under 

Connecting 

to Gas Supply

, page 8.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM 

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect appliance with its appliance main gas valve 

(control valve) and equipment shutoff valve from gas supply 

piping system. Pressures in excess of 1/2 psig will damage 

appliance regulator.

*  Purchase the optional equipment shutoff valve from your 

dealer.

**Minimum inlet gas supply pressure for purpose of input 

adjustment. 

Figure 12 - Gas Connection

  Pipe  Cap Tee

 Nipple    Joint

Gas Control 

3" Minimum

Sediment Trap

Equipment Shutoff Valve 

With 1/8" NPT Tap*

Approved Flexible 

Gas Hose (if allowed 

by local codes)

PROPANE/LP

 

From External 

Regulator

(11" W.C.** 

to 14" W.C. 

Pressure)

NATURAL

 

From Gas 

Meter

(5" W.C.** 

to 10.5" 

W.C. 

Pressure)

2. Cap off open end of gas pipe where equipment shutoff 

valve was connected.

3.  Pressurize supply piping system by either opening pro

-

pane/LP supply tank valve for propane/LP gas or opening 

main gas valve located on or near gas meter for natural 

gas or using compressed air.

4.  Check all joints of gas supply piping system. Apply noncor-

rosive leak detection fluid to all joints. Bubbles forming show 

a leak. 

5.  Correct all leaks at once.
6.  Reconnect appliance and equipment shutoff valve to gas 

supply. Check reconnected fittings for leaks. 

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.  Close equipment shutoff valve (see Figure 13).

2.  Pressurize supply piping system by either opening pro

-

pane/LP supply tank valve for propane/LP gas or opening 

main gas valve located on or near gas meter for natural 

gas or using compressed air.

3.  Check all joints from gas meter to equipment shutoff valve 

for natural gas or propane/LP supply to equipment shutoff 

valve for propane/LP (see Figure 14 or Figure 15, page 

10). Apply noncorrosive leak detection fluid to all joints. 

Bubbles forming show a leak. 

4.  Correct all leaks at once.

Figure 13 - Equipment Shutoff Valve

Open

Closed

Equipment 

Shutoff 

Valve

Figure 14- Checking Gas Joints (Propane/LP Only)

Control Valve 

Location

Propane/LP 

Supply Tank

Equipment 

Shutoff Valve

Summary of Contents for VTDGT24NR

Page 1: ...er appliance An LP cylinder not connected for use shall not be stored in the vicinity of this or any other appliance WARNING Improper installation adjustment alteration service or maintenance can caus...

Page 2: ...information consult a qualified installer service agency or the gas supplier WARNING This appliance is for installation only in a solid fuel burning masonry or UL127 factory built fireplace or in a l...

Page 3: ...alls and furniture 9 Do not use this appliance as a wood burning appliance Use only the logs provided with the appliance Do not burn solid fuels in this appliance 10 Do not run appliance where flammab...

Page 4: ...these instructions ELECTRONIC IGNITION SYSTEM This appliance has an electronic ignitor to light appliance fuel supply INSTALLATION WARNING Aqualified service person must install appliance Follow all...

Page 5: ...If you cannot meet these minimum clearances you must operate appliance with chimney flue damper open Go to Installing Damper Clamp Accessory for Vented Opera tion page 7 Heat Resistant Material A Figu...

Page 6: ...el Clearances When Using Hood Minimum Non Combustible Material Minimum Non Combustible Material Height Distances to Underside of Mantel Top of Fireplace Opening Underside of Mantel Shelf 12 A 18 20 22...

Page 7: ...This will insure adequate air flow and guard against sooting and controls being dam aged Raisefireplacefloorwithnoncombustible material Make sure material is secure Installation Items Needed hardware...

Page 8: ...reads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged appliance valves WARNING Use pipe joint sealant that is resistant to liquid petroleum LP gas...

Page 9: ...um inlet gas supply pressure for purpose of input adjustment Figure 12 Gas Connection Pipe Cap Tee Nipple Joint Gas Control 3 Minimum Sediment Trap Equipment Shutoff Valve With 1 8 NPT Tap Approved Fl...

Page 10: ...ee Checking Gas Connections page 9 9 If logs were removed from appliance for install remote ac cessory replace logs see Installing Logs and Lava Rock Page 11 10 Place remote receiver on fireplace floo...

Page 11: ...anual Flamescontacting logs will create soot LOG PLACEMENT It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplied with appliance Note Each log inclu...

Page 12: ...ertical portion of the burner tube Place this log on the base assembly by inserting it from the left side as shown in Figure 19 You will need to twist the log slightly to get it to fit against the bur...

Page 13: ...36 inch models D 028 See Figures 22 and 22A The split side of the log faces forward The log has a notch that fits around the burner tube on the right side The left side of the burner tube fits into th...

Page 14: ...ehind the knot on the top of the front right log 8 Find the back top log VFGT24 inch models D 062 or VFGT30 inch models D 023 or VTGF36 inch models D 029 See Figures 25 and 25A The left end of this lo...

Page 15: ...you don t smell gas go on the next step 6 Press in and turn control knob counterclockwise to the PILOT position Press in control knob for five 5 seconds see Figure 26 7 With control knob pressed in p...

Page 16: ...l areas burnersandcirculatingairpassagewaysofap plianceclean Inspecttheseareasofappliance before each use Have appliance inspected yearly by a qualified service person WARNING Failure to keep the prim...

Page 17: ...vary from pilot shown Thermocouple Thermopile 1 8 Pilot Burner Piezo Ignitor 3 8 to 1 2 LOGS If you remove logs for cleaning refer to Installing Logs and Lava Rock page 11 to properly replace logs Re...

Page 18: ...Gas Pressure in of water Max 14 W C Min 11 W C For purpose of input adjustment VTDGT24NR VTDGT30NR AND VTDGT36NR Rating Variable 29 000 40 000 Btu Hr Type Gas Natural Ignition Electronic Manifold Pre...

Page 19: ...n installed 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not cor rect REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing...

Page 20: ...lights keep control knob pressed in 30 seconds 3 Wait one minute for safety in terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or pro...

Page 21: ...from line Have gas line checked by local natural or pro pane LP gas company 3 Observe minimum installation clearances see pages 9 through 11 4 Clean burner see Cleaning and Maintenance page 16 or rep...

Page 22: ...ply propane LP only 3 Gas leak See Warning state ment at top of page 1 Low line pressure 2 ODS pilot is partially clogged 1 Gas leak See Warning state ment at top of page 2 Control valve or gas contro...

Page 23: ...wall above fireplace Fits openings 28 to 48 wide RECEIVER AND HAND HELD REMOTE CONTROL KIT MRC REMOTE READY MODELS ONLY For all models Allows the fireplace to be turned on and off by using a hand hel...

Page 24: ...SuperiorFireplaces US com 127038 01A 24 PARTS REMOTE READY CONTROL MODELS VTDGT24NR VTDGT24PR VTDGT30NR VTDGT30PR VTDGT36NR VTDGT36PR 1 2 5 6 8 9 10 13 14 15 16 17 18 19 20 21 23 24 25 22 11 12 12 7...

Page 25: ...ase 2 13 125603 01 Grate Stainlees MF42 1 125603 02 Grate Stainlees MF48 1 14 111435 01 Ignitor Electric 1 15 125019 01 Bracket Ignitor 1 16 116559 02 Shutter Air NG 1 116559 03 Shutter Air LP 1 17 09...

Page 26: ...NO PART NO LOG ID NO DESCRIPTION QTY 1 125948 01 D 061 125573 01 D 019 125591 01 D 027 Log Front Right 1 2 125948 02 D 060 125573 02 D 018 125591 02 D 026 Log Back Left 1 3 125948 03 D 059 125573 03...

Page 27: ...ing purchase date Usually we will ask you to return the part to the factory SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition appliance will not pro...

Page 28: ...ll produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product...

Page 29: ...eriorFireplaces US com 127038 01A 29 KEEP THIS WARRANTY Model located on product or identification tag Serial No located on product or identification tag Date Purchased Keep receipt for warranty verif...

Page 30: ...www SuperiorFireplaces US com 127038 01A 30 NOTES...

Page 31: ...www SuperiorFireplaces US com 127038 01A 31 NOTES...

Page 32: ...127038 01 Rev A 01 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P127038 01...

Reviews: