background image

SuperiorFireplaces.US.com

127035-01C

17

TROUBLESHOOTING

 WARNING: Turn off appliance and let cool before servicing. Only a qualified service person should service 

and repair appliance.

Note:

 All troubleshooting items are listed in order of operation.

Remote /Ignitor has a special feature. It will allow heat from the burner to dry the probe and burner assembly due to excess moisture, caused 

by rain, humidity or condensation. To activate:

• 

Press and hold the HI and LO buttons on the transmitter for 30-45 seconds. This allows the sparking to start and the burner to ignite.

• 

Release the HI and LO buttons, after the allotted time, sparking will stop and the burner will go out.

• 

Press and hold the ON button and sparking will start again and burner should ignite.

• 

Release the ON button. The sparking will stop, and the burner should stay ON.

• 

Repeat if necessary.

POSSIBLE CAUSE

1. Ignitor electrode not connected to ignitor 

cable

2. Ignitor cable pinched or wet

3. Broken ignitor cable

4. Bad ignitor

5. Ignitor electrode positioned wrong

6. Ignitor electrode broken

7. Battery not installed, battery power low or 

battery not installed correctly (electronic 

ignition models only)

1. Gas supply turned off or equipment shutoff 

valve closed

2. Air in gas lines when installed

3. Depleted gas supply (propane/LP only)

4. Control module not in REMOTE position

5. Gas control valve pressure setting is not 

correct

6. Inlet gas pressure is too low

7. Burner orifice(s) clogged

8. Wire disconnected from gas control

9. Ground wire issue

REMEDY 

1. Reconnect ignitor cable

2. Free ignitor cable if pinched by any metal 

or tubing. Keep ignitor cable dry

3. Replace ignitor

4. Replace ignitor 

5. Adjust ignitor wires as shown in Figure 

28 on page 13. Replace ignitor assembly 

if repositioning does not correct the 

problem

6. Replace ignitor

7. Install new alkaline battery in remote 

control and battery pack. Verify batteries 

are installed correctly. (5.4 volts batter-

ies required to operate valve system)

1. Turn on gas supply or open equipment 

shutoff valve

2.  Repeat igniting operation until air is 

removed

3. Contact local propane/LP gas company

4. Set control module to REMOTE position

5. Contact qualified service person to check 

pressure

6. Contact local natural or propane/LP gas 

company

7. Clean burner (see Cleaning and Main-

tenance, page 15) or replace burner 

orifice(s)

8. See Wiring Diagram, page 16

9. Verify black ground wire from module is 

secured under screw adjacent to ignitor

OBSERVED PROBLEM

When ''ON'' button on remote control is 

pressed, there is no spark at ignitor assembly

When ''ON'' button on remote control is 

pressed, there is spark at ignitor but no 

ignition

Summary of Contents for VRE4543

Page 1: ...uivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Do not store or use gasoline...

Page 2: ...y be present even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any cha...

Page 3: ...box or on adjacent walls or furniture 8 Do not run fireplace where flammable liquids or vapors are used or stored under dusty conditions SAFETY Continued 9 Do not use this fireplace to cook food or b...

Page 4: ...Flange Access Door Top Spacers PRODUCT FEATURES OPERATION This fireplace is clean burning It requires no outside venting There is no heat loss out a vent or up a chimney Heat is generated by realistic...

Page 5: ...e mantels may discolor INSTALLATION Continued Figure 2 Framing Clearances for One Sided Application Figure 3 Framing Clearances for See Thru Application 17 50 53 25 38 15 25 53 25 38 17 50 53 25 38 Fi...

Page 6: ...6 INSTALLATION Continued Figure 6 VRE4543E Series Dimensions 11 13 16 16 1 2 17 1 2 5 8 29 13 16 8 1 4 1 55 1 16 52 47 44 1 16 29 25 32 7 1 32 16 9 32 2 716 1 816 8 255 13 217 1 816 3 208 Gas Line Acc...

Page 7: ...Aqualifiedservicepersonmustconnect fireplace to gas supply Follow all local codes CAUTION Never connect propane LP fireplace di rectly to the propane LP supply This fireplace requires an external reg...

Page 8: ...s This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged fireplace valves Never use sealant on flare threads WARNING Use pipe joint sealant that is resist...

Page 9: ...alve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 11 2 Pressurize supply piping system by either...

Page 10: ...rd mounting bracket and replace screws FINISHING FIREPLACE FOR INSTALLATION The VRE4543 series fireplace come with the rear panel semi installed If you will be using the fireplace for a one sided regu...

Page 11: ...r Figure 20 Installing Access Door Retaining Brackets for See Thru Applications Figure 21 Installing Side Face Filler for See Thru Applications Removing Rear Interior Wall 1 Through firebox opening in...

Page 12: ...the electronic access cover See Figure 23 3 Remove electronic access cover by gently pulling up and out of the fireplace There are two switches connected to cover 4 The control module is located on t...

Page 13: ...shield that is covering the module and remove the screw on top Use a small thin object like a paper clip not sharp points to press and release the learn button There will be a beep sound from the mod...

Page 14: ...1 STOP Read the safety information column 1 2 Make sure equipment shutoff valve is fully open 3 Turn safety shutoff switch to the OFF position 4 Remove access cover 5 Turn equipment shutoff valve cloc...

Page 15: ...any large clumps of dust have now been pushed into the burner repeat steps 3 and 4 above BURNER PRIMARY AIR HOLES Air is drawn into the burner through the holes in the fitting at the burner entrance...

Page 16: ...Orange Red Brown Black Solenoid White Brown Brown Green Ignitor Pilot I S AUX AF 5000MOD AF 4000 AF 4000B P Control Module Black Black SWI SWI GND Red HI LO Main Black BATTERY PACK Black Red Black Re...

Page 17: ...losed 2 Air in gas lines when installed 3 Depleted gas supply propane LP only 4 Control module not in REMOTE position 5 Gas control valve pressure setting is not correct 6 Inlet gas pressure is too lo...

Page 18: ...tor assembly is relighting the burner 4 Wire connection loose or wire broken REMEDY 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Main tenance page 18 or replace bu...

Page 19: ...every one second Gas odor during combustion POSSIBLE CAUSE 1 Appliance burning vapors from paint hair spray glues cleaners chemicals new carpet etc See IMPORTANT statement above 2 Low fuel supply prop...

Page 20: ...SuperiorFireplaces US com 127035 01C 20 PARTS MODELS VRE4543EN AND VRE4543EP 1 2 4 4 4 4 5 8 6 7 3 9 10 11 19 20 21 12 12 13 14 4 22 15 16 18 17...

Page 21: ...399 Brass Elbow 2 11 111817 01 Flextube 1 12 125932 01 Burner Gasket 2 13 126050 02 Electronic Access Cover LVFO 1 14 126051 01 Insulation Heat Shield 1 15 125976 02 Bracket Valve Components 1 16 1460...

Page 22: ...5768 03 Access Door Stainless 1 13 125766 02 Side Face Filler Stainless 2 14 125975 02 Fireplace Hood Stainless 1 15 126399 01 Glass tempered 1 16 126397 01 Bracket Glass Retainer 2 17 125753 02 Pebbl...

Page 23: ...ified heat for propane LP unit propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SERVICE You may have further questions about i...

Page 24: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 25: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 26: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 27: ...to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in...

Page 28: ...ns pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2014 IHP LLC P N 127035 01 Rev C 04 2015 P127035 01 1508 Elm Hill P...

Reviews: