background image

9

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Notes:

•  All appliances are factory-equipped with a 

fl exible gas line connector and 1/2 inch shutoff 
valve (see 

Figure 19

 on 

Page 12 

).

• See 

Massachusetts Requirements

 on 

Page 

3

  for additional requirements for installations 

in the state of Massachusetts in the USA.

•  The gas supply line should Not be connected 

to the appliance until 

Step 7

 (

Page 11 

).

•  A pipe joint compound rated for gas should be 

used on the threaded joints. 

Ensure 

propane 

resistant compounds are used in propane 
applications. Be very careful that the pipe 
compound does not get inside the pipe.

•  It is recommended to install a sediment trap 

in the supply line as close as possible to the 
appliance (see 

Figure 19 , Page 12 

).  Appli-

ances using Propane  should have a sediment 
trap at the base of the tank.

•  Check with local building offi cial for local code 

requirements (i.e. are below grade penetrations 
of the gas line allowed?, etc).

Step 4. INSTALL VENT SYSTEM

Install the Vent System & Exterior Ter-
mination:

In the United States, vent installation must 
conform with local building codes. In the 
absence of local codes, vents must be installed 
in accordance with the current edition of the 
National Fuel Gas Code (ANSI-Z223.1). 

In Canada, vent installation must conform with 
local building codes. In the absence of local 
codes, vents must be installed in accordance 
with the current edition of the National Standard 
of Canada CAN/CGA-B149.1 or B149.2 Instal-
lation Code.

This gas fi replace must be vertically vented 
using listed 5 in. type-B, double-walled vent 
pipe and a listed vent termination.

Slip the fi rst 5 inch (127 mm) section of B-
Vent over the fi replace fl ue outlet and secure 
with  three (minimum) sheetmetal screws (# 
8 or larger), and install the remainder of the 
B-Vent to the outside. Minimum overall height 
of the vent system and appliance must be 10' 
(2.54 m) vertical - no offset 

(see Figure 13)

;

 

or 12' (3.7 m) when an offset up to 60 degrees 
from the vertical is used - this offset may start 
at the fi replace fl ue collar 

(see Figure 14 on 

Page 10 ).  

The maximum overall height of 

the vent system and appliance should not 
exceed 40 feet.

  

Install the B-vent system in accordance with 
the vent manufacturer's instructions. 

Figure 13

1" (25 mm)

Minimum

Firestop

Step 3. POSITION APPLIANCE

Position the appliance within the framing 
and secure with nailing brackets.

Flue Outlet

Collar

Securing

Screws

Figure 12

Note:

 Refer to the vent manufacturers instal-

lation instructions for variations of venting 
techniques. If common venting of several units 
is contemplated, it should be discussed with an 
architect and the local Building Department.

Do not place insulation materials within 1 in. 
of the gas vent system.

       CAUTION  

This appliance cannot be vented 
horizontally.

       IMPORTANT

If propane is used, be aware that 
if tank size is too small (i.e. under 
100-lbs, if this is the only gas 
appliance in the dwelling. Ref. 
NPFA 58), there may be loss of 
pressure, resulting in insuffi cient 
fuel delivery (which can result in 
sooting,  severe delayed ignition or 
other malfunctions). Any damage 
resulting from an improper instal-
lation, such as this, is not covered 
under the limited warranty.

Figure 10  

 

(see *

Note)

Side

Framing

Unit Nailing Flange

(No clearance to

combustible

framing is required)

Left Side Front Corner of Fireplace Shown

 (Right Side Requirements the Same)

Unit Being Secured By Its Nailing Flanges

To The Framing

Anchor

Tab

Figure 11

Floor Nailing Tabs

Secure the fi replace to the fl oor as shown in  

Figure 11. 

* Note:  

The nailing fl anges, combustible mem-

bers and screw heads located in areas directly 
adjacent to the nailing fl anges, are EXEMPT from 
the 1/2” clearance to combustible requirements 
for the fi rebox outer wrapper.  Combustible 
framing may be in direct contact with the nail-
ing fl anges and may be located closer than 1/2” 
from screw heads and the fi rebox wrapper in 
areas adjacent to the nailing fl anges. Frame the 
opening to the exact dimensionsspecifi ed in the 
framing details of this manual.

Fireplace may be anchored to fl oor. Bend down two 
anchor tabs (one on each side) located at the base 
of the fi replace and secure to the fl oor by nailing 
with 8d nails or equivalent (see 

Figure 11

)

.

Note: 

Some units 

only have one 
anchor tab on 
each side.

Type Type B-Vent 5 in. (127 mm)

10 Feet (3 Meters) 

Minimum

f i r e - p a r t s . c o m

Summary of Contents for SSBV-3530CNE

Page 1: ...le home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certif...

Page 2: ...Misc Codes Standards TheInstallationmustconformtolocalcodesor in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the Natural Gas and Propane Instal lat...

Page 3: ...as Valve Electronic Models Electronic models have a fixed rate gas valve Input of electronic models is shown in Table 3 MASSACHUSETTS REQUIREMENTS Theseappliancesareapprovedforinstallationin the follo...

Page 4: ...i fication or alteration may void the warranty certification and listings of this unit WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches d...

Page 5: ...n If the fireplace is being installed on a cement slab in cold climates a sheetofplywoodorotherraisedplatformcanbe placedunderneathtopreventconductingcoldup into the room It also helps to sheetrock in...

Page 6: ...rmation and consult your local building code to determine if you need additional support If you plan to raise the fireplace and hearth extension build the platform assembly then position fireplace and...

Page 7: ...7 Vertical Vent Termination Clearances Roof Pitch is X 12 Minimum Height from Roof to Lowest Discharge Opening X 12 1 25 mm Minimum Note Venting terminals shall not be recessed into a wall or siding G...

Page 8: ...Finishing Materials if any Rough Framing Face Unfinished Shown Optional FOAK Outside Air Kit A Outside Chase G C J Back Wall of Chase Enclosure Including Finishing Materials if any Rough Framing Face...

Page 9: ...maximum overall height of the vent system and appliance should not exceed 40 feet Install the B vent system in accordance with the vent manufacturer s instructions Figure 13 1 25 mm Minimum Firestop S...

Page 10: ...tionalfield providedjunctionboxwithrecep tacle may be installed at the front of the control compartment on either side of the cabinet See Figure 16 It will be held in place by a conduit fitting and lo...

Page 11: ...safetyhazard Theappliancemustbe electrically grounded in accordance withlocalcodesor intheabsenceof local codes the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22...

Page 12: ...ator through several cycles including the closed position Ensuring proper operation and freedom of movement Return the actuator arm to the closed position Outside Air Control Lever and Securing Screw...

Page 13: ...t Lightinginstructionslabel can be found in the control compartment see Figure 20 When first lighting the appliance it will take a few minutes for the line to purge itself of air Once purging is compl...

Page 14: ...o 1 5 Place the top left log B as shown The top forkonlog B fitsintonotchonlog A The bottom of the log rests on the subfloor SSBV 3530 Install as Follows Carefully position the ceramic fiber logs into...

Page 15: ...ere 1through5 andper theinstructionson Page14 A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A P...

Page 16: ...1through5 andper theinstructionson Page14 D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 PlaceEmbers andVolcanicSto...

Page 17: ...ng black tip the air shutter opening may need to be adjusted Iftheairshutteropeningsclosedtoofar sooting maydevelop Sootingisindicatedbyblackpuffs developingatthetipsofverylongorangeflames Sootingresu...

Page 18: ...nting action start by holding a smoke producing device within an inch of one edge side edge not top or bottom edge of one glass enclosure panel The smoke should be drawn toward the edge of the glass e...

Page 19: ...FOAK 4LD Combustion Air Kit w o duct INSTALLATION ACCESSORIES The following accessory items are available for use in the installation of these appliances See Homeowners Manual for a complete list of a...

Page 20: ...cablecodesandrequire ments of the authorized having jurisdiction If the information in these instructions is not fol lowed exactly a fire explosion or production of carbon monox ide may result causing...

Page 21: ...ntactingtheorificestripcouldcause stripdistortionrenderingthepilotinop erative Also avoid wrench contact to any of the other pilot parts Use a 7 16 open end wrench and turn the pilot hex fitting count...

Page 22: ...he Igniter assembly use extreme care to prevent damage and break age Do not apply any leverage to the Igniter assembly while restoring the retainer clip to its original position All Models Step 8 Remo...

Page 23: ...23 NOTE THIS PAGE LEFT BLANK INTENTIONALLY fire parts com...

Page 24: ...th Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor fo...

Reviews: