background image

16

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 12 - Framing Ceiling Opening

A.

 

Frame ceiling opening - 

Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center mark 

(

Figure 12

)

.

Figure 13 - Attaching the Vent Adaptor

Align the dimple (four places) of the 

upper vent section with the opening 

of the locking incline channel on 

the lower vent section or appliance 

collar. Twist vent component 

clockwise to engage and seal until 

arrow and dimple align.

Dimple

Locking Incline 

Channel

Connected Vent 

Sections

Arrow

Arrow

Adaptor on Appliance Collar 

or Vent Section

B.

 

Attach adaptor (with probe) to appliance 

collar - 

Secure Vent

®

 SV4.5 direct-vent sys-

tem components are unitized concentric pipe 

components featuring positive twist lock con-

nections (see

 Figure 13

).

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels. The dimpled end of the adaptor fits 

over the appliance collar to create the positive 

twist lock connection.

10-1/2" min. 

(267 mm)

Ceiling Framing

Plumb Bob

10-1/2" min. 

(267 mm)

To attach a vent component to the adaptor on 

appliance collar, align the dimpled end over the 

adaptor collar, adjusting the radial alignment 

until the four locking dimples are aligned with the 

inlet of the four inclined channels on the collar 

(refer to 

Figure 13

). Push the vent component 

against the collar until it fully engages, then twist 

the component clockwise, running the dimples 

down and along the incline channels until they 

seat at the end of the channels. 

E.

 

Support the vertical vent run sections -

Support the vertical portion of the venting 

system every eight feet (2.4 m) above the 

fireplace vent outlet.

 One method of support 

is by utilizing field provided support straps 

(conventional plumber's tape). Secure the 

plumber's tape to the framing members with 

nails or screws.

 

Strap the tape around the vent, 

securing the ends of the tape to the framing. 

If desired, sheet metal screws #6 x 1/2" length 

may be used to secure the support straps to 

the vent pipe. 

F. Change vent direction to horizontal/inclined 

run - 

At transition from or to a horizontal/in-

clined run, install the SV4.5E45 and SV4.5E90 

elbows in the same manner as the straight vent 

sections. The elbows feature a twist section to 

allow them to be routed about the center axis 

of their initial collar section to align with the 

required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 

only so as to avoid the possibility of unlocking 

any of the previously connected vent sections 

(see

 

Figures 13 and 15)

.

The unitized design of the Secure Vent

®

 com-

ponents will engage and seal both the inner and 

outer pipe without the need for sealant or screws. 

If desired a #6 x 1/2" screw may be used at the 

joint, but it is not required as the pipe will securely 

lock when twisted.

C. Attach vent components to each other - 

Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments shown in 

Figures 16 and 17 on Page 17

.

To add another vent component to a length of 

vent run, align the dimpled end over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four 

locking dimples are aligned with the inlets of 

the four incline channels of the previous section. 
Push the vent component against the previ-

ous section until it fully engages, then twist 

the component clockwise running the dimples 

down and along the incline channels until they 

seat at the end of the channels. 

This seating 

position is indicated by the alignment of the 

arrow and dimple as shown in

 

Figure 13.

D.

 

Install firestop/spacer at ceiling - 

When 

using Secure Vent, use SV4.5VF firestop/spacer 

at ceiling joists. If there is living space above 

the ceiling level, the firestop/spacer must be 

installed on the bottom side of the ceiling. If 

attic space is above the ceiling, the firestop/

spacer must be installed on the top side of 

the joist. Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each corner.

A firestop spacer is required.

Maintain 1" (25 mm) clearance to combus-

tibles, framing members, and attic or ceiling 

insulation when running vertical chimney 

sections. Attic insulation shield (H3907) may 

be used to obtain the required clearances 

indicated here. See installation accessories 

on Page 30. The gap between the vent pipe 

and a vertical firestop may be sealed with 

noncombustible caulking.

8-1/8”

(206 mm)

4-13/16”

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

G.

 

Continue installation of horizontal/inclined 

sections - 

Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step C.

 Install support straps 

every three feet (914 mm) along horizontal/

inclined vent runs using conventional plumber’s 

tape (

Figure 16

 on 

Page 17

). 

NOTE: Maintain the horizontal/inclined run in 

a straight, slightly elevated plane - approxi-

mately 1/4" per foot (20 mm per meter) - in 

a direction away from the fireplace. Smaller 

rise per foot run ratios are acceptable, down 

to at or near level. Use a carpenter’s level to 

measure from a constant surface and adjust 

the support straps as necessary.

NOTE: Maintain the required clearances to 

combustibles: 1" (25 mm) at all sides for all 

vertical runs; and 3" (76 mm) at the top, 1" (25 

mm) at sides, and 1" (25 mm) at the bottom 

for all horizontal/inclined runs.

Blocking

Support Straps

(Plumber's 

tape)

8' (2.4 m)

Maximum

1/2" (13 mm) 

minimum 

clearance to 

combustibles

Figure 14 - Supporting Vertical Vents

Figure 15 - Vent Elbow Sections

INNOVATIVE HEARTH PRODUCTS  •  POWER VENT DV GAS FIREPLACES  (DRT6340/45TYN)  •  INSTALLATION INSTRUCTIONS

NOTE: Attic insulation shield (H3907, see 

Page 30) must be installed when blown 

or loose-fill insulation is used, and is 

required for all attic installations.

Summary of Contents for Signature DRC6340TYN

Page 1: ...tique Cet appareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utils e Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any ot...

Page 2: ...EZ PAS UNE VITRE NON REFROIDIE NE LAISSEZ JAMAIS UN ENFANT DE TOUCHER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude...

Page 3: ...se toca Mantengaalosni osalejadosdela chimeneaenfuncionamiento Supervise enformacercanaalosni osencualquier cuartodondehayaunachimenea funcionandoparaimpedirelcontactocon elvidrio Mantenga la ropa mob...

Page 4: ...Page 43 Electronic Appliance Inspection Page 44 Ordering Replacement Parts Page 45 Accessory Components Page 46 Lighting Instructions Page 48 Maintenance Schedule Page 50 Troubleshooting Page 51 Repl...

Page 5: ...TH PRODUCTS POWER VENT DV GAS FIREPLACES DRT6340 45TYN INSTALLATION INSTRUCTIONS WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer t...

Page 6: ...370 m above sea level using the standard burner orifice sizes marked with an in Table 4 For elevations above 4500 ft contact your gas supplier or qualified service technician Deration At higher elevat...

Page 7: ...ng the location the aesthetic and functional use of the appliance are primary concerns However vent system routing to the exterior and access to the fuel supply are also important Due to high temperat...

Page 8: ...12 12 4 0 1 22 12 12 to 14 12 5 0 1 52 14 12 to 16 12 6 0 1 83 16 12 to 18 12 7 0 2 13 18 12 to 20 12 7 5 2 29 20 12 to 21 12 8 0 2 44 The vent air intake termination clearances above the high side of...

Page 9: ...or assembly 36 910 mm within a height of 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 36 910 mm 36 910 mm J Clearance to nonmechanical air supply inlet to buil...

Page 10: ...rated 175 F or higher on the underside of the mantel MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sid...

Page 11: ...bed See the page numbers references in the follow ing steps for detailed procedures Step 1 Page 11 Construct the appliance framing Position the appliance within the framing and secure with nailing bra...

Page 12: ...ow Model No A B C D E F G H J 40 in in 50 5 8 39 1 4 45 25 5 16 34 37 5 8 33 3 32 29 9 32 34 3 4 mm 1286 997 1143 643 864 956 840 744 883 45 in in 56 11 16 44 1 4 47 7 8 28 3 8 40 1 8 43 5 8 38 3 32 3...

Page 13: ...83 5 8 59 1 8 41 7 8 mm 1286 2124 1502 1064 45 in in 56 3 4 89 7 8 63 1 2 44 7 8 mm 1441 2283 1613 1140 C Back wall of chase enclosure including any finishing materials D A B Figure 9 Corner Framing w...

Page 14: ...onal Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or Canada CAN CGA B149 1 latest edition These fireplaces are designed tested and listed for operation and installation only with Secure Vent SV4 5...

Page 15: ...1 1 1 0 8 4 0 4 1 1 0 0 0 1 1 1 2 9 4 1 4 1 0 1 0 0 1 2 1 5 9 9 4 5 2 6 1 4 0 0 0 1 0 1 1 1 4 0 5 2 4 1 0 0 1 0 1 2 1 5 1 1 5 5 2 6 2 4 0 0 0 0 1 1 1 1 5 0 2 5 5 7 3 3 4 0 2 0 1 1 1 4 1 1 3 5 5 2 4 4...

Page 16: ...otrequiredasthepipewillsecurely lock when twisted C Attachventcomponentstoeachother Other vent sections may be added to the previously installedsectioninaccordancewiththerequire mentsshowninFigures16a...

Page 17: ...5HF Secure Vent firestop spacer must be used anytime vent pipe passes through a combustible wall Maintain the horizontal inclined run in a straight slightly elevated plane approximately 1 4 per foot 2...

Page 18: ...sections in horizontal inclined run as described in Step E Install support straps every three feet 1914 mm along horizontal inclined vent runs using conventional plumber s tape see Figure 16 on Page...

Page 19: ...m NOTE Centerline of Vent Piping is NOT the Same as the Centerline of the Frame Opening 6 to 48 Vent Section Telescopic vent section Elbow or Appliance Collar Base of Appliance 3 76 mm 1 25 4 mm Adapt...

Page 20: ...the fireplace to the newly installed junction box near the termination Ensure the cable is safety plated to prevent damage from framing nails and finish drywall screws Route it into the lower control...

Page 21: ...orten it to fit within the junction box cover WARNING Crimp connectors may be used on stranded cables such as SJOT cable only Solid wire Romex must be connected per the National Electric Code NEC 70 l...

Page 22: ...this door or replace cracked or broken glass with any materials other than those provided by the appliance manufacturer Theglassdoorofthisappliance must only be replaced as a complete unit as provided...

Page 23: ...e C When the gas lines are tested and leak free be sure to rinse off the leak testing solution D Re install the access plate making certain the gasket has not been damaged Step 7 INSTALL FIREBOX LINER...

Page 24: ...and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion sooting and poor flame quality Logs get very hot a...

Page 25: ...d Push It Towards The Rear 3 2 4 1 6 5 7 Log Number Description 1 Log Center 2 Log Rear 3 Log Center Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 6 Log Set Align Ho...

Page 26: ...and seated firmly 2 Positionthedoorframeinfrontofthefirebox openingandengagethebottomflangeover therailatthebottomofthefireboxopening 3 Swing the door up and back Ensure the gasketseatsevenlyasthedoo...

Page 27: ...finish the installation Leave the ON REMOTE OFF wall switch in the REMOTE position and turn the remote switch OFF Use the remote to adjust the flame height as desired CAUTION Soot will be produced if...

Page 28: ...WED in the clearance zones around vent compo nents Keep this area free from combustible materials Figure 44 Finished Wall Insulation is NOT ALLOWED in the clearance zones around vent components Keep t...

Page 29: ...ement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les traces degraisseoud huil...

Page 30: ...lex 6 pieces 91L67 SF GC7 6 Gear Clamp 7 5 190 5 mm for flex 6 pieces Listed Secure Vent Components Cat No Model No Description 77L70 SV4 5L6 6 152mm Vent Section 77L71 SV4 5L12 12 305mm Vent Section...

Page 31: ...enfants ou les adultes peuvent subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour e...

Page 32: ...contr le le foyer Figure A Choisissez la langue qui est principalement parl e dans la r sidence du propri taire 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour liminer la poussi re et les trac...

Page 33: ...area heaters They must not be equipped with wall thermostats or remote controls with thermostat functions CAUTION Hotwhileinoperation Donot touch Severe Burns may result Keep children clothing furnitu...

Page 34: ...me breadth height and width will diminish 4 for every 1 000 feet of altitude INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT6340 45TYN INSTALLATION INSTRUCTIONS Input BTU HR Natural Gas Mo...

Page 35: ...ldren and others may be susceptible to accidental contact burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to a fireplace or stove install an ad...

Page 36: ...ction The life span of the receiver batteries depends on various factors Quality of the batteries used Number of ignitions of the appliance etc When the receiver batteries are low no beep willbeemitte...

Page 37: ...receiver or transmitter are low or depleted the appliance can be turned on manually by sliding the ON REMOTE OFF slider switch to the ON position This will bypass the remote control feature of the sy...

Page 38: ...lsofoundonapull outpanellocated in the control compartment Always keep the appliance area clear and free from combustible materials gasoline and other flammable liquids Before re lighting the fireplac...

Page 39: ...the contemporary burner floor kit skip this step and instead refer to the instructions provided with the kit Inspect Wiring Refer to wiring diagram on Page 48 CAUTION Label all wires prior to disconn...

Page 40: ...gage the nut insert and fasten with two screws to secure the door 4 Installthedoormodestyshieldontopflange glassdoorasfollows grabthedoormodesty shield with both hands with the open hem going down and...

Page 41: ...not impinge any flames WARNING DO NOT attempt to install the logs until the appliance installation has been completed the gas line connected and tested for leaks and the initial burner operation has b...

Page 42: ...ter Left 4 Log Center Right 5 Log Rear Top 6 Log Front Left 7 Log Front Center Table 16 Log Set Align Hole At Bottom Of Log 5 Over The Pin On Log 2 6 5 7 2 Figure 61 Placing Logs 5 6 and 7 Engage Log...

Page 43: ...tion Sooting is caused by incomplete combustionintheflamesandlackofcombustion air entering the air shutter opening To achieve a warm yellow orange flame with an orange body that does not soot the shut...

Page 44: ...the flame move the adjustment air shutter located on the lower venturi back or forward to increase or reduce the air shutter opening respectively Position the air shut ter to the factory setting as s...

Page 45: ...e 108 Nashville TN 37210 Visit us at SuperiorFireplaces US com PRODUCT REFERENCE INFORMATION We recommend that you record the important reference information about your fireplace in the space provided...

Page 46: ...Kits The andiron kits attach to the grate assembly without the use of hardware Firebox Accessories Cat No Model Description 88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Volcanic Stone H8312 PGE B...

Page 47: ...ce Barrier Kits These screen panel kits create a barrier to prevent direct contact with the hot glass The screen panel affixes directly to the front glass enclosure panel Oak Log Set Cat No Model H867...

Page 48: ...tat on remote control to desired setting 12 If the appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier OPERATING INSTRUCTIO...

Page 49: ...on REMOTE 10 Appuyez sur le bouton ON OFF pour s lectionner ON 11 Ajustez le thermostat sur la t l commande l ajustement d sir 12 Si l appareil ne se met pas en marche suivez les instructions intitul...

Page 50: ...the system being exposed to cold weather Also inspect wall straps or plumbers s tape to ensure it is secure and in place Appliance Checkout Qualified Service Technician Perform the appropriate applian...

Page 51: ...ner lights then immediately goes out Gas is not reaching the fireplace Check the gas supply and gas shutoff valves call a service technician if required Loose wires to the valve or ignition module Che...

Page 52: ...Does the Pilot Flame Cover the Flame Rod Is the Sensor Wire in Good Condition Is There Continuity to Ground from the Pilot Burner No Replace Control Module Does Pressure Switch Open During Operation...

Page 53: ...e Tubing H2283 1 H2284 1 13 Connector Male H2285 1 H2285 1 14 Orifice Natural Gas H7924 1 H8141 1 15 Bag of Glowing Embers 88L53 1 88L53 1 16 Grate Assembly H4907 1 H4907 1 17 Gas Line Flexible Connec...

Page 54: ...AMS ILLUSTRATIONS ARE NOT TO SCALE 29 15 21 22 7 17 13 12 6 8 11 9 5 1 4 16 3 20 19 18 31 30 14 REPLACEMENT PARTS INNOVATIVE HEARTH PRODUCTS POWER VENT DV GAS FIREPLACES DRT6340 45TYN INSTALLATION INS...

Page 55: ...lamp 7 5 190 5 mm for flex 6 pieces INSTALLATION ACCESSORIES Listed Secure Vent Components Cat No Model No Description 77L70 SV4 5L6 6 152mm Vent Section 77L71 SV4 5L12 12 305mm Vent Section 77L72 SV4...

Page 56: ...General Information 900344 00 01 2015 Innovative Hearth Products SuperiorTM DRT DRC6300 Powervent Series Direct Vent Gas Fireplaces 56 NOTES...

Page 57: ...e subjected to normal use The Product is designed to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will...

Page 58: ...styles and products Consult your local distributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products LLC P N 900344 00 Rev NC 01 2015 1508 Elm Hill Pike Suite 108 Nashvi...

Reviews: