
Superiorfireplaces.US.com
126900-01_B
6
INSTALLATION
Continued
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to the leading edge of the
damper as shown in Figure 3. If for any reason this clamp doesn't
work on your fireplace, another suitable clamp or permanent stop
must be installed, or the damper blade must be cut or removed.
CONNECTING TO GAS SUPPLY
WARNING: A qualified service person must connect
log set to gas supply. Follow all local codes.
Installation Items Needed
Before installing log set, make sure you have the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve
• adjustable (crescent) wrench or pliers
• sediment trap
• tee joint
• pipe wrench
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of 1/2" diam-
eter or greater to allow proper gas volume to log set.
If pipe is too small, undue loss of volume will occur.
Figure 3 - Attaching Damper Clamp
Damper
Clamp
Damper
Clamp
Damper
Manufactured Fireplace
Masonry Fireplace
Damper
Installation must include an equipment shutoff valve with "T" style
handle, gas union and, for propane/LP gas only, a plugged 1/8" NPT
tap. Locate NPT tap within reach for test gauge hook up. NPT tap
must be upstream from log set (see Figure 4).
IMPORTANT:
Install equipment shutoff valve in an accessible loca-
tion. The equipment shutoff valve is for turning on or shutting off
the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will prevent
excess sealant from going into pipe. Excess sealant in pipe could
result in a clogged burner injector.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
* Purchase the optional equipment shutoff valve from your dealer.
** Minimum inlet pressure for purpose of input adjustment.
Figure 4 - Gas Connection
3" Minimum
From Gas Meter
(5" W.C.** to 10.5"
W.C. Pressure)
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible Gas
Hose (no longer than 36" if
required by local codes)
Tee Pipe Cap
Joint Nipple
Sediment Trap
We recommend that you install a sediment trap in the supply line as
shown in Figure 4. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants. This keeps them
from going into log set controls. If sediment trap is not installed or
is installed wrong, log set may not run properly.