background image

www.Superiorfireplaces.US.com

126616-01A

14

OPERATION AND MAINTENANCE GUIDELINES

GLASS DOORS

Cabinet type glass doors are optional with this fireplace. Check with 

your local distributor for availability.
To install glass doors, refer to installation instructions that are in-

cluded with kit. When fireplace is in operation, doors must be fully 

open or fully closed position only or a fire hazard may be created 

(see Figure or 31).
A fireplace equipped with glass doors operates much differently 

than a fireplace with an open front. A fireplace with glass doors has 

a limited amount of air for combustion. Excessive heat within the 

fireplace can result if too large a fire is built or if combustion air gate 

is not completely open.

IMPORTANT: 

The following tips should be used to assure that both 

fireplace and glass door retain their beauty and function properly. 

• 

Both the flue damper and glass doors must be fully opened 

before starting a fire. This will provide sufficient combustion 

air and maintain safe temperatures in firebox.

• 

The glass must be allowed to warm slowly and evenly. The tem-

pered glass will withstand a gradual temperature rise to 550° F, 

which is more than a normal fire will generate. Such materials 

as pitch/wax laden logs, very dry mill end lumber and large 

amounts of paper or cardboard boxes. Always keep the fire well 

back from the doors and never allow flames to contact the glass.

 " WARNING: FIREPLACES EQUIPPED WITH DOORS 

SHOULD BE OPERATED ONLY WITH DOORS FULLY 

OPEN OR DOORS FULLY CLOSED. IF DOORS ARE LEFT 

PARTLY OPEN, GAS AND FLAME MAY BE DRAWN OUT 

OF THE FIREPLACE OPENING, CREATING RISKS OF 

BOTH FIRE AND SMOKE".

Figure 31 - Cabinet Glass Doors

Cleaning Glass

Clean glass with any commercial glass cleaner or soap and water. 

Do not use any abrasive material to clean glass. Do not clean glass 

with any cool water if glass is still hot from the fire. To remove doors, 

refer to instructions included with glass door kit.

DAMPER MECHANISM

The damper control lever is located inside the fire chamber (see Fig-

ure 32). Make sure lever is cool before handling. Pull down to close 

and push up to open. Damper must be open when lighting a fire. 

Not doing so will cause smoke spillage into the room. When firebox 

is not in use, close damper to prevent down drafts to enter room.

GRATE

OUTSIDE AIR
HANDLE
PULL TO CLOSE
PUSH TO OPEN

DAMPER CONTROL LEVER
PULL DOWN TO CLOSE
PUSH UP TO OPEN

Figure 32 - Damper Operation

OUTSIDE AIR MECHANISM

The outside air handle is located at the right hand side of firebox 

rear refractory (see Figure 32). Pull to close, push to open. Always 

open mechanism when starting a fire. This provides adequate outside 

combustion air. Close mechanism when not in use to prevent cold 

air from entering room. Periodically check your outside air intake 

vent hood for any possible obstructions such as snow, bushes, etc.

Glass Doors Must be Fully Open 

(as Shown) or Fully Closed when 

Appliance is in Operation

Summary of Contents for Custom WRT40PFWS

Page 1: ...e is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21 60 Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard...

Page 2: ...re hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace or any of the components manu factured by IHP unless otherw...

Page 3: ...urn veryquickly DONOTusetreatedwood charcoal coal trash driftwoodorwoodsthathavebeendippedintar pitch pine tar creosote etc Wood products made with synthetic binders such as plywood produce ab normall...

Page 4: ...up has occurred When creosote has accumulated 1 8 3mm ormore itshallberemoved to reduce the risk of a chimney fire SAFETY Continued Figure 1 Dimensions WARNING Always leave glass doors fully opened or...

Page 5: ...locate in or near an area where gasoline or other flam mable liquids may be stored The firebox area must be kept clear and free from these combustible materials The typical installation for this firep...

Page 6: ...of fireplace see Figure 8 Figure 6 Framing Firebox with Z Type Ember Protectors Figure 7 Ember Protectors Figure 8 Nailing Flanges HEARTH EXTENSIONS A hearth extension projecting a minimum of 20 in fr...

Page 7: ...t For operating instructions please refer to your owner s manual FIREPLACE INSTALLATION Continued 8 Max K Factor 84 1 1 2 Typ 1 1 2 Typ Noncombustible Hearth Extension Z Type Ember Protector Noncombus...

Page 8: ...engths of 12 18 36 and 48 The actual lineal gain for each is measured after each section is fully connected Lineal gain is the actual measurable length of a part after two or more parts are connected...

Page 9: ...and Accessories page 16 VENTING INSTALLATION Continued 10 FOOT RULE All chimney terminations must extend a minimum of 3 feet above the highest point where it passes through the roof and must be at le...

Page 10: ...n usually 12 A 6 12 pitch means that the roof drops 6 for each 12 one measure horizontally down from roof rafters 3 Use roof opening chart Figure 23 to determine correct opening length and flashing re...

Page 11: ...th the termination being used Nail Only Outer Perimeter of Flashing Storm Collar Underlap Shingles at Bottom Figure 24 Flashing Installation Flashing Cone Overlap Shingles Top and Sides Only Figure 25...

Page 12: ...ombustible material may be used for facing glass tile brick etc as long as proper clearances are adhered to and fireplace openings are not obstructed in any way see Minimum Clearance to Combustibles p...

Page 13: ...tween gas line and refractory knockout hole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be...

Page 14: ...oors and never allow flames to contact the glass WARNING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENORDOORSFULLYCLOSED IFDOORSARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT...

Page 15: ...h surface temperatures and to stay away from these to avoid burns or clothing igni tion Young children should be carefully supervised when they are in the same room as fireplace OPERATION AND MAINTENA...

Page 16: ...R FS 10 for Straight Pipe 30FS 10 for 30 Angled Run DOUBLE WALL 30 ELBOW OFFSET 30E 12DM Also available in triple wall Return Elbow Starter Elbow DOUBLE WALL PIPE 12 12DM 18 12DM 24 12DM 36 12DM 48 12...

Page 17: ...DM 6 12 TO 12 12 PITCH V12F 10DM ECONO TOP TERMINATION STL 12DM BI FOLD GLASS DOOR DG36PN Brushed Brass DC36PN Platinum DBPPN36 Black ACCESSORIES Continued OUTSIDE AIR KIT FOR FLOOR INSTALLATION AK4 R...

Page 18: ...____________________________________ ______________________________________________________ ______________________________________________________ _____________________________________________________...

Page 19: ...____________________________________ ______________________________________________________ ______________________________________________________ _____________________________________________________...

Page 20: ...design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2014 IHP LLC P N 126616 01 Rev A 01 20...

Reviews: