background image

Superiorfireplaces.US.com

126746-01D

10

VENTING INSTALLATION 

A B-type venting system must be connected to the appliance for 

venting to the outside of the building.
IHP defines installation standards of this product. Third party prod-

ucts must be installed to their specific standards.
Standing codes requirements concerning B-type vent installations 

may vary within your state, province or local codes jurisdiction. 

Therefore, it is recommended that you check with your local build-

ing codes for specific requirements or in absence of local codes, 

follow Section 7.0 of the current National Fuel Gas Code NFPA No. 

54/ANSI Z223.1.
This gas appliance must be vented to the outdoors only and may not 

be terminated into an attic space or into a chimney flue servicing a 

solid fuel burning appliance.
This appliance may be vented through a manufactured chimney 

system or a masonry chimney using a B-vent adapter or a chimney 

liner system if all are listed, inspected and approved by local codes 

and/or building authorities.
The examples shown in Figure 9, are typical of most B-vent instal-

lations and code practices.
Example 1 shows the minimum allowable system height and lateral 

offset for a 60° or greater inclination. Code specifies that offsets at 

60° or greater are considered horizontal and must follow the 75% 

rule for lateral to total vertical system height. Codes also allows only 

one offset in the total system when at 60° or greater. The total vertical 

height in this example represents the minimum height of 8 feet and 

therefore the allowable lateral is 6 feet when the 75% rule applies. If 

the lateral length must exceed 75% then the system must be sized 

in accordance with the Category I venting tables.

Example 2 shows a multiple offset each at 45° of inclination. Multiple 

offsets are permitted if they do not exceed 45° of inclination. The 

total lengths of the two offsets are not required to meet the 75% 

allowable rule.
Example 3 shows a single offset at 45° of inclination and therefore the 

lateral length at 10 feet of offset does not have to meet the 75% rule.
In each case the offsets must be supported and firestops must be 

positioned wherever the vent must pass through a subfloor, ceiling 

joist or an attic overhang. The vent pipe must terminate vertically 

into a listed type vent cap and extend a sufficient height through an 

approved roof flashing, roof jack or a roof thimble. At all points the 

listed clearances must be maintained.
Vent terminations must be located in accordance with height and 

proximity rules of NFPA No. 54. These rules apply to vents at 12" 

diameter or less and require a minimum height in accordance with 

the roof pitch and a minimum of 8 feet distance from a vertical wall 

or obstruction (see Figure 10, page 11).
If venting horizontally through a side wall becomes necessary, a listed 

thimble (38FST recommended) approved for use with B-type vent 

must be used. Check with your local codes before venting through 

a side wall. 

Figure 9 - Typical B-Vent Configuration

Maintain

Listed

Clearance

12' Min.

45°

6'

8'

12' Min.

60°

45°

Position

Firestop

Position

Firestop

Listed

Vent Cap

Listed Vent Cap

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Support 

Each

Lateral 

At Least 

Every

6 Feet

Maintain

Listed

Clearance

EXAMPLE 2

EXAMPLE 1

Maintain

Listed

Clearance

12' Min.

45°

Position

Firestop

Listed

Vent Cap

Maintain

Listed

Clearance

10'

EXAMPLE 3

Summary of Contents for BRT2032TEN

Page 1: ...ncindie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance W...

Page 2: ...lation and operational procedures For assis tance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanent...

Page 3: ...he fireplace in high traffic areas in windy or drafty areas 5 This fireplace reaches high temperatures Keep children and adults away from hot surfaces to avoid burns or clothing igni tion Fireplace wi...

Page 4: ...an the type of gas approved for use in this gas appliance Installation must conform with local codes or in the absence of local codes with the current National Fuel Gas Code ANSI Z223 1 This fireplace...

Page 5: ...PROPANE LP Max Input Rating 15 000 Btu Hr 25 000 Btu Hr Manifold Pressure 10 WC 2 49 kPa 10 WC 2 49 kPa Minimum Supply Pressure 11 WC 2 74 kPa 11 WC 2 74 kPa Maximum Supply Pressure 13 WC 3 23 kPa 13...

Page 6: ...d or at a premium and since the space required to enclose the appliance would be located beyond an outside wall this would also reduce the cutting of joists roof rafters and such Check local codes for...

Page 7: ...ling 0 Clearance Ceiling 1 2 5 cm Min Clearance to B Vent s Outer Pipe Required Air Spaces are Indicated with an Do Not Pack with Insulation or Any Other Material DO NOT BLOCK OR OBSTRUCT OPENINGS 0 C...

Page 8: ...itting at the end of flexible gas line remove fitting and replace with a 37 degree flare 3 4 12 1 2 NPT female fitting WARNING When finishing appliance do not overlap combustible material onto the bla...

Page 9: ...t above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT...

Page 10: ...lateral length must exceed 75 then the system must be sized in accordance with the Category I venting tables Example 2 shows a multiple offset each at 45 of inclination Multiple offsets are permitted...

Page 11: ...8 12 to 9 12 2 0 0 61 Over 9 12 to 10 12 2 5 0 76 Over 10 12 to 11 12 3 25 0 99 Over 11 12 to 12 12 4 0 1 22 Over 12 12 to 14 12 5 0 1 52 Over 14 12 to 16 12 6 0 1 83 Over 16 12 to 18 12 7 0 2 13 Ove...

Page 12: ...TALLATION Figure 13 Installing the WRC Remote Receiver Figure 13A Installing Battery into Back of Handset Fireplace Receptacle Remote Control Receiver Extension Cord Ignition Module Plug Pull to Remov...

Page 13: ...leaks after the installation is completed After ensuring that the gas valve is on apply a non corrosive leak detection solution to all connections and joints If bubbles appear leaks can be detected an...

Page 14: ...1 2 gap under the lower grate members to allow air to flow see Figure 21 LOG PLACEMENT FOR BRT2032TEN MODEL 1 Place front log onto front of grate sliding log all the way forward against grate fingers...

Page 15: ...ace top of log 4 into notch on log 1 Rest log 4 on the center of grate as shown in Figure 26 5 Place top of log 5 into notch on top right of log 1 see Figure 26 Rest log 5 between two middle grate fin...

Page 16: ...ge of firebox opening 4 Tilt door assembly fully vertical until outer pivot pin snaps into mounting hole in upper spring clip see Figure 30 5 Once top and bottom pins are secured unfold door into clos...

Page 17: ...ly Opened Door Figure 32 Removing Glass Doors Spring Clip Press Spring Clip to Release Pivot Pin Remove Bottom Pin From Pivot Plate While Sliding Door Out of the Upper Track Pivot Plate Fold Bi Fold D...

Page 18: ...TRUCTIONS NOTICE During initial operation of new fireplace burning logs will give off a paper burning smell Orange flame will also be present Open damper or window to vent smell This will only last a...

Page 19: ...s panel 7 Fully close glass doors if installed Figure 34 Pilot OPTIONAL HAND HELD REMOTE OPERATION Note The WRC receiver and hand held remote control kit must be purchased separately see Accessories p...

Page 20: ...ng page 21 Figure 36 Typical Flame Pattern BRT2332TEN BRT2532TEN Models BRT2032TEN Model WARNING Installation and repair should be done by a qualified service person The appliance should be inspected...

Page 21: ...service and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier to check pressure 5 Have a qualified technician replace pilot line 6 Replace...

Page 22: ...let blocked 3 Burner flame holes blocked 4 Improper venting or excessive blockage 5 Excessive amounts of embers and pan mate rial OBSERVED PROBLEM Nogastoburner althoughwallswitchandvalve are set to t...

Page 23: ...n calling please have your model and serial numbers of your fireplace ready You can also visit our web site at IHP US com ACCESSORIES Purchase these accessories from your local dealer If they can not...

Page 24: ...032TEN 33 43 41 15 19 24 14 30 26 29 3 14 12 13 23 35 16 31 32 32 38 39 40 40 4 34 21 20 22 5 5 37 42 1 1 36 28 25 9 2 7 17 11 6 27 10 11 24 3 18 18 24 9 NG LP 24 8 24 8 24 4 24 9 24 12 24 10 24 11 24...

Page 25: ...03 Burner Pan 1 24 2 109794 01 Burner Tube 1 24 3 107748 01 Burner Bracket 1 24 4 107985 01 Pilot Shield 1 24 5 109793 01 Divider Pan 1 24 6 11209 Nut 10 24 1 24 7 11147 Screw 10 24x1 2 1 24 8 901066...

Page 26: ...3 43 41 15 19 24 14 30 26 29 17 14 12 13 24 3 18 18 24 9 NG LP 24 8 24 8 24 4 24 9 24 12 24 10 24 11 24 6 24 2 24 5 24 1 24 7 23 10 36 9 36 35 16 31 32 32 38 39 40 40 4 34 21 8 46 45 44 44 11 37 42 1...

Page 27: ...12 06 Burner Assembly 1 24 1 107742 03 Burner Pan 1 24 2 109037 01 Burner Tube 1 24 3 107748 01 Burner Bracket 1 24 4 107985 01 Pilot Shield 1 24 5 901681 01 Burner Clamp 1 24 6 11209 Nut 10 24 1 24 7...

Page 28: ...al KEY NO PART NO DESCRIPTION QTY 109109 01 Log Set 1 105958 05 Front Log 1 2 105960 05 Rear Log 1 3 901100 02 Top Right Log 1 4 901102 02 Top Left Log 1 1 4 2 3 1 2 3 4 5 KEY NO PART NO DESCRIPTION Q...

Page 29: ...TOFF SWITCH EV2 SUPPLY INCOMING MAIN GAS EV1 TO GAS LINE BURNER 24V AC 120V AC 120V AC INCOMING OR BREAKER FUSE BOX OFF ON SUPPLIED WALL SWITCH GREEN BLACK WHITE 120v 60Hz 0 7A ELECTRICAL RATING BLACK...

Page 30: ...__________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 31: ...to burn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in...

Page 32: ...mation Printed in U S A 2013 IHP LLC P N 126746 01 Rev D 10 2014 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 IHP US com KEEP THIS WARRANTY Model located on product or identification...

Reviews: