www.SuperiorFireplaces.US.com
126861-01A
10
INSTALLATION
Continued
Figure 4 - Framing Clearances for One
Sided Application
Figure 5 - Framing Clearances for See-
Thru Application
53.25"
38"
17.50"
53.25"
38"
15.25"
53.25"
38"
17.50"
53.25"
38"
15.25"
Figure 7 - Clearances for Combustible
Mantels
Ref.
Mantel
Depth Ref.
Mantel
from
Top of
Opening
1
12"
A
24"
2
9"
B
21"
3
6"
C
18"
4
4"
D
16"
5
2"
E
14"
A
B C
D E
1
2
3
4
5
Wall
Supplied firebox
hood must be
used at all times.
Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel
shelf.
Noncombustible
material may project
off this surface above
the firebox hood
Figure 6 - Installing Concrete Board
Concrete
Board
8"
Combustible
Material May
Be Used
TOP VIEW
SAFE
ZONE
Perpendicular
Wall
33°
4" to Face Opening
5"