EFFECTIVE HEIGHT
OF TERMINETION CAP
EFFECTIVE HEIGHT
OF TERMINETION CAP
EFFECTIVE HEIGHT
OF TERMINETION CAP
EFFECTIVE HEIGHT
OF TERMINETION CAP
30E-8DM
30E-8DM
UP TO
6 FT (1.83 m)
MAX.
UP TO
6 FT (1.83 m)
MAX.
11.5 FT
(3.50 m)
MINIMUM
HEIGHT
11.5 FT
(3.50 m)
MINIMUM
HEIGHT
MAX. HEIGHT
50 FT (15.24 m)
ANY SYSTEM
MIN. HEIGHT
22 FT (6.71 m)
WITH 2 ELBOW SETS
MAX. HEIGHT
OF 50 FT. (15.24 m)
VENTING INSTALLATION
Continued
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above highest point where it passes through roof and
must be at least 2 feet above highest point of the roof that is within
a horizontal distance of 10 feet (see Figure 25).
10
'
(3.05 m)
10
'
(3.05 m)
2
'
(0.61 m)
Min.
2
'
(0.61 m) Min.
3
'
(0.92 m)
Min.
3
'
(0.92 m)
Min.
Level of
Flue Gas Outlet
Figure 25 - 10 Foot Rule
CHIMNEY SUPPORT BRACKET KIT: CSK-8DM
If exposed portion of chimney is greater than five feet above roofline,
support wires are recommended to keep chimney secured. Support
wires must be attached to chimney support brackets. Chimney
support brackets must be attached to outer pipe of chimney with
self-drilling screws provided in kit (screws must not penetrate in-
ner flue pipe). The angle of support wires should not be more than
45° from horizontal when fastened to roof. Place chimney support
brackets approximately 18" below fireplace termination and space
brackets approximately 120° apart (see Figure 26) Follow instruc
-
tions included in kit.
Figure 27 - Typical Residential Installations
Figure 26 - Support Wires
Chimney
Support Bracket
Support Wire
Cable
Ferrule
Eye
Bolt
Angle of Support Wire
Should Not Be More Than
45° From Horizontal
120°
120°
120°
Top View of
Chimney
Self Drilling Screws
18" (458 mm)