background image

17

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Zero Clearance Fireplace Installation

This appliance may be installed in a masonry or factory built/zero clear-

ance (ZC) fireplace. When installing in a ZC fireplace, the ZC grate must 

be removed and the ZC damper must be removed or secured open. The 

ZC doors, screen, refractory or masonry lining, baffles and smoke shelf 

may be removed if necessary to install the gas insert. However, do not cut 

or alter the fireplace components. The removal of any parts to facilitate 

installation must not alter the integrity of the inner or outer shells of the 

fireplace cabinet. Any parts removed must be replaceable if the insert is 

taken out of the fireplace or the fireplace clearly marked with a paint stick 

that "This fireplace has been altered and is no longer safe to operate." 

This appliance is designed to fit into a ZC fireplace with a minimum firebox 

height of 19-1/2" (495mm).  

If the factory-built fireplace has no gas access hole(s) provided, an ac-

cess hole of 1-1/2" (37.5 mm) or less may be drilled through the lower 

sides or bottom of the firebox in a proper workmanship like manner. This 

access hole must be plugged with a non-combustible insulation after the 

gas supply line has been installed.

Si le foyer préfabriqué ne comporte pas d’orifices d’amenée du gaz, un 

orifice d’au plus 37,5 mm (1,5 po) peut être pratiqué, selon les règles 

de l’art, dans la partie inférieure des parois ou au fond de la chambre de 

combustion. Cet orifice doit être obturé au moyen d’isolant incombustible 

une fois la conduite de gaz en place.

The installer must mechanically attach the marking supplied with the gas 

fireplace insert to the inside of the firebox of the fireplace into which the 

gas fireplace insert is installed. See 

Figure 1

 on 

Page 10.

Conversion from Standard 40,000 BTU Natural Gas To Optional 
33,000 BTU Natural Gas Input

To convert input from 40,000 BTU's to 33,000 BTU's. (Assuming the 

front door is already removed)

1.   Remove the log rack (Use a 5/32" allen wrench) by removing two 

screws on the front of the log rack and then pulling the log rack out 

the front of the firebox.

2.   Remove the burner by sliding the burner to the right off the main 

burner orifice and out of the air shutter tube.  The burner can now 

be pulled out of the firebox and carefully placed aside.

3.    Remove the main burner orifice (1/2" wrench) by turning the wrench 

counterclockwise to loosen and remove.

4.      Install new burner orifice #H5924 by placing the orifice in the bulkhead 

and turning clockwise.  Using a wrench, tighten the orifice until snug.  

(Pipe dope or other approved gas line sealant will need to be applied 

to the orifice before it is inserted into the bulkhead)

5.   Reinstall burner by completing Step 3 in reverse.

6.   Reinstall log rack by completing Step 2 in reverse.

7.    The foil sticker supplied, stating DRI3030TEN-33 or DRI2530TEN-33, 

will need to be affixed below the model name on the serial number 

label (located in the control compartment).

Figure 9

Log Rack

Rear Log

Firebox Panel Kit and Log Set Installation

If logs are not installed according to the log installation instructions, 

flame impingement and improper combustion could occur and result in 

soot and/or excessive production of carbon monoxide (CO), a colorless, 

odorless, toxic gas.

The size and position of the log set is critical to achieve a safe, reliable 

and attractive flame pattern.  Any attempt to use a different log set in the 

fireplace will void the warranty and will result in incomplete combustion, 

sooting and poor flame quality.

1.  Remove the log rack (2 screws) and install the rear log on the retainer. 

See 

Figures 8 and 9

.

2.  Place the rear firebox panel on the brackets and reinstall the log rack 

with the rear log.

 IMPORTANT!!! SCREWS PASS THROUGH THE LOG 

RACK AND THE BURNER PAN.

3. Install the side firebox panels by sliding them into place. See 

Figure 10.

Figure 8 - Log Rack Screws

Summary of Contents for DRI2530TEN

Page 1: ...tely call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by...

Page 2: ...O CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact ac...

Page 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Page 4: ...t Leveling 14 Fan Control Module Switch RDV 33 40 TCC models only 15 Installation 15 21 Venting Installation 15 USING THIS MANUAL Please read and carefully follow all of the instructions found in this...

Page 5: ...avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit cett...

Page 6: ...porcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor de control en el panel de control del artefacto verifique que el interruptor opera el artefacto encend...

Page 7: ...pareil Figure A Choisissezlalanguequiestprincipalementparl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Rep rezlat l commandeetnettoyez lasoigneuse ment pour limi...

Page 8: ...se or anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the...

Page 9: ...ver use solid fuels such as wood paper cardboard coal or any flammable liquids etc in this appliance Plated surfaces must be cleaned with glass cleaner and a clean soft cloth before firing the first t...

Page 10: ...ural gas or propane Is NOT for use with solid fuels Is approved for sitting rooms and or bedrooms This appliance is suitable for installation into masonry or factory built fireplaces Fireplace Require...

Page 11: ...a nationally recognized testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified to ANSI Z21 88 CSA...

Page 12: ...r Propane LP Bedrooms Remote Control Electrical The standard blower motor requires 120 Volts AC for operation The fireplaceisnotdependentontheblowertooperate WARNING Electrical Grounding Instructions...

Page 13: ...A 31 1 2 800mm Front Opening Width B 19 1 2 495mm Height C 18 457mm Rear Width D 16 406mm Fireplace Depth Top View Left Side View Right Side View Front View A B C D Figure 3 Minimum Fireplace Cavity...

Page 14: ...learances Please note that the DRI3030TEN 33 and DRI2530TEN 33 mantel clear ances are 4 less than the DRI3030TEN 40 and DRI2530TEN 40 mantel clearances as shown in Figure 4A DRI3030TEN 40 and DRI2530T...

Page 15: ...for installation and vent termination These appliances are approved for use with the following vent kits Amerivent Flex Liner 3 X 35 3AFL 35 Adaptor w Flashing 4DCAT33 Termination Cap 4DVC Selkirk Fle...

Page 16: ...e sealed around the vent pipes Use a non combustible seal off plate i e 22 gage sheet steel or unfaced fiberglass insulation 8 lb per square foot density minimum to seal around the vent pipes Whicheve...

Page 17: ...l 33 000 BTU Natural Gas Input To convert input from 40 000 BTU s to 33 000 BTU s Assuming the front door is already removed 1 Remove the log rack Use a 5 32 allen wrench by removing two screws on the...

Page 18: ...oundpanelsinfrontoftheholesonthesurroundbrackets Next insert two slotted 1 4 truss screws for each side surround panel and secure loosely 5 Fasten the top surround panel with the remaining two truss s...

Page 19: ...Figure 15 The panel has keyhole slots where it mounts to the base Loosen the two nuts securing the panel using 3 8 wrench Carefully move out the panel far enough to access the back Do not pull the pa...

Page 20: ...leak test solution retighten if necessary If the pressure is not sufficient make sure the gas supply line is large enough the supply regulator is properly adjusted and the total gas load for the resid...

Page 21: ...air will result in bigger flames and more color To adjust the air shutter insert a regular screwdriver into the slide adjustment and slide it side to side see Figures 19a and 19b CAUTION The air shut...

Page 22: ...ance will not operate follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier TO TURN OFF GAS TO APPLIANCE 1 Turn the burner ON OFF switch in the control...

Page 23: ...IT Proflame Stepper Electronic Pilot Assembly Electronic Pilot Assembly Unit Mounted Controls Unit Mounted Controls Intermittent Standing Pilot Mode On Auto Pilot Mode Switch Thisappliancecanbeswitche...

Page 24: ...to indicate that it is ready to synchronize with the Remote transmitter Install 3 AAA type batteries in the Remote transmitter battery bay located on the base of the Remote With the batteries already...

Page 25: ...ned off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the high position s...

Page 26: ...per main burner operation at both high and low flame OPERATION DRI3030TEN Model Only No Blue Flame Center Soot at Flame Tip Dark Orange Flame IMPROPERLY BURNING FLAME Soot above Flame Tip No Soot at F...

Page 27: ...E RECEIVER BLOWER SPEED CONTROL PILOT ON AUTO SWITCH AC DC ADAPTER POWER OUTLET BOX 6 WHT 5 BLUE WHT BLK WHT BLK BLK BLK 4 GRN GRN 8 GRN 3 GRAY 14 RED 9 GRN 2 RED 1 RED 3 BLK 2 BLK 1 RED PILOT ROOM AI...

Page 28: ...W 10 ORG 13 BLK 12 BRN 14 RED 4 PUR WHT BLK BLK WHT 4 GRN 8 GRN 2 BLK 3 BLK 1 RED 9 WHT 3 GRAY 2 RED GRN 1 2 3 4 1 Figure 28C Electronic Control Schematic Model DRI3030TEN NOTE SWITCH CONDITIONS GIVEN...

Page 29: ...n those approved for use with this appliance o Check that the chimney and its outlet are open and free of soot block age or debris The venting system should be periodically examined by a qualified age...

Page 30: ...not attempt to substitute the materials used on these doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while...

Page 31: ...Unplug the power supply cord from the electrical outlet prior to removing theblower Theblowercanbeaccessedthroughthebackwallofthefirebox Remove the insert face glass door log set and firebox liner pan...

Page 32: ...and lifting up slightly and then out away from the unit 3 Lay the facade face down on a soft surface that will not scratch the paint 4 Using a 3 8 socket remove the six nuts holding the left 1 and rig...

Page 33: ...ion on Pages 17 and 18 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed vent...

Page 34: ...equires H8457 Conversion Kit For Model DRI2530TEN with Manual Hi Lo Regulator 26 H8507 Cassette Assembly NG 40 000 BTU if LP also requires H8459 Conversion Kit For Model DRI3030TEN with Auto Hi Lo Reg...

Page 35: ...DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS DRI3030TEN AND DRI2530TEN 1 27 26 2 3 4 5 15 6 7 16 37 14 36 25 33 34 21 22 23 13 32 31 30 29 28 8 17 9 10 11 20 19 33 21 34 22 23 12 24 18 38...

Page 36: ...0 BTU input to optional 33 000 BTU input Cat No Description H5924 Orifice Main Burner 36 Natural Gas 33 000 BTU H5925 Orifice Main Burner 51 Propane 33 000 BTU Firebox Panel Kits required accessory Ca...

Page 37: ...8 Black Trim Includes black trim x x x H8556 RDV DBV FP3341 D 33 x 41 Black Trim Includes black trim x x x H8557 RDV DBV FP3348 D 33 x 48 Black Trim Includes black trim x x x 75362 RDV DBV FP2941 B1 2...

Page 38: ...000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUST BE PROPER...

Page 39: ...CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A...

Page 40: ...iance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Page 41: ...or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damage...

Page 42: ...distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial num...

Reviews: